Honeywell VR4920Z 1000 Instruction Sheet Download Page 1

INSTRUCTION SHEET

VR4920Z 1000 AND 45.900.449-

DUAL VALVE ASSEMBLY APPLICABLE FOR BUILT--ON PURPOSES

EN1R--9181 0104R1--NE

DESCRIPTON

The VR4920Z 1000 dual valve has been specially developed

to have kits fit--on.

When a kit with a V7335A electric modulating regulator

(Modureg) is fitted on the dual valve assembly the type gas

control is equal to a VR4920M.
When a kit with a V4336A electric high low regulator is fitted

on the dual valve assembly the gas control is equal to a

VR4920P.

APPLICATION

The VR4920M provides the following functions:

Servo pressure regulation

Outlet pressure is held at a constant value regardless of

fluctuations of inlet pressure.

Modulating control

Between minimum and maximum outlet pressure gas

supply to the appliance is dependent on the electrical

signal to modulating coil.

Mechanical limitation of outlet pressure

The minimum and maximum burner pressures are

mechanically adjusted to guarantee good burner

performance in case the modulating control should

become out of range.

The VR4920M is designed to work together with the W9335

modulating Modureg control, W4115 logic control, T7335A

thermistor temperature sensor and an advanced range of

micro computer based modulating controls.

The VR4920P provides the following functions:

Servo pressure regulation

Outlet pressure is held at a constant value regardless of

fluctuations of inlet pressure.

High--Low control

Within the ranges specified a high and a low outlet

pressure can be mechanically adjusted and electrically

selected.

High outlet pressure to appliance will be established by

switching control voltage to High--Low coil on.

By switching voltage off, outlet pressure will drop to low

pressure setting.

1 Place gasket

note: orientation !!!

2 Fix operator with the four

screws provided

4 Fit Modureg or High--Low

regulator with the indent

beside the locating plug and

fix with the two screws

provided.

3 Place seal

5 Make soudness testing

6 Adjust Modureg or

High--Low setting

Fig. 1.

Subject

to

change

w

ithout

notice.

Printed

in

the

N

etherlands.

Summary of Contents for VR4920Z 1000

Page 1: ...ed to guarantee good burner performance in case the modulating control should become out of range The VR4920M is designed to work together with the W9335 modulating Modureg control W4115 logic control T7335A thermistor temperature sensor and an advanced range of micro computer based modulating controls The VR4920P provides the following functions Servo pressure regulation Outlet pressure is held a...

Page 2: ...et B Outlet C Inlet pressure tap D Outlet pressure tap E 6 3 mm terminals G Mounting holes M5 for connecting flanges H Earth screw K Pilot outlet connection L Pilot flow adjustment screw M Optional for inlet pressure tap 1 8 BSPT Fig 2 Dimensions VR4929M VR4920P ...

Page 3: ...nlet and outlet with an approved leak detection fluid If another gas leak is detected tighten adapter screws joints and pipe connections Replace the part if gas leak can not be stopped CAUTION Keep leak detection fluid away from electrical connections SPECIFICATIONS VR4920M Model VR4920M line voltage gas control fast opening with electric modulating regulator V7335A Ambient temperature 0 70 _C Min...

Page 4: ...and maintenance instructions carefully follow them If such instructions are not provided then follow the procedure as outlined below Allow time for pressure to stabilize before making adjustments It is recommended that the Modureg is operated a few times to ensure correct setting Remove cap before adjustment Take care that after any adjustment the cap is mounted WARNING The minimum pressure settin...

Page 5: ...e gauge to pipe line or to outlet pressure tap of gas control concerned to measure burner pressure measuring point must be as near to burner as possible Energize operator set control in operation and wait until an outlet pressure is recorded on pressure gauge Make sure Modureg is wired in the circuit Bring system in fixed setting mode Adjust current as low as needed to obtain the lowest pressure b...

Page 6: ... removed by putting a small screw driver in one of the slots and lifting the cap carefully while at the same time supporting the cap opposite to the screw driver see fig 5 page 7 WARNING Maximum pressure setting must first be adjusted then minimum pressure setting can be adjusted Any adjustment of maximum pressure setting influences minimum pressure setting Never adjust the maximum setting above t...

Page 7: ...wise to increase or counter clockwise to decrease pressure until desired minimum burner pressure is obtained Wire High Low regulator coil in circuit Check maximum pressure setting and re adjust if necessary Check minimum pressure setting again When High and Low pressure settings are correct replace cap Checkout Set appliance in operation after any adjustment and observe several complete cycles to ...

Page 8: ...R 9181 0104R1 NE Home and Building Control Combustion Controls Center Europe Honeywell BV Phileas Foggstraat 7 7821 AJ Emmen The Netherlands Tel 31 591 695911 Fax 31 591 695200 http europe hbc honeywell com ...

Reviews: