Standard-Opening and Slow-Opening Pressure Regulator

1. The gas control outlet pressure should match the

manifold pressure listed on the appliance nameplate.

2. With the main burner operating, check the gas control

flow rate using the meter clocking method or check the gas
pressure using a manometer connected to the gas control
outlet pressure tap. Refer to Fig. 4.

3. If necessary, adjust the pressure regulator to match the

appliance rating. Refer to Table 7 or 8 for the factory set
nominal outlet pressures and adjustment ranges.

a. Remove the pressure regulator adjustment cap and

screw.

b. Using a screwdriver, turn the inner adjustment

screw clockwise           to increase or counterclock-
wise  

 to decrease the main burner gas pressure.

c. Always replace the cap screw and tighten firmly to

assure proper operation.

4. If the desired outlet gas pressure or gas flow rate cannot

be achieved by adjusting the gas control, check the gas
control inlet pressure using a manometer at the inlet pressure
tap. If the inlet pressure is in the normal range (refer to Table
7 or 8), replace the gas control. Otherwise, take the necessary
steps to provide proper gas pressure to the gas control.

Step-Opening Pressure Regulator

1. The gas control outlet pressure should match the

manifold pressure listed on the appliance nameplate.

2. With main burner operating, check the gas control

flow rate using the meter clocking method or check the gas

pressure using a manometer connected to the gas control
outlet pressure tap. Refer to Fig. 4.

3. If necessary, adjust the pressure regulator to match

the appliance rating. Refer to Table 7 or 8 for factory set
nominal outlet pressures and adjustment ranges.

a. Remove the pressure regulator adjustment cap screw.
b. Using a screwdriver, turn the inner adjustment screw

clockwise 

  to increase or counterclockwise  

to decrease the main burner gas pressure.

c. Always replace the cap screw and tighten firmly to

assure proper operation.

4. If desired outlet pressure or flow rate cannot be

achieved by adjusting the gas control, check the inlet
pressure using a manometer at inlet pressure tap or up-
stream of the gas control. If the inlet pressure is in the
normal range (refer to Table 7 or 8), replace the existing gas
control. Otherwise, take the necessary steps to provide
proper gas pressure to the gas control.

5. Carefully check main burner lightoff at the step

pressure. Assure the main burner lights smoothly and
without flashback to the orifice and that all ports remain lit.
Cycle the main burner several times, allowing at least 30
seconds between cycles for the regulator to resume the step
function. Repeat after allowing main burner to cool.
Readjust the full rate outlet pressure if necessary to im-
prove lightoff characteristics.

TABLE 5—PRESSURE REGULATOR SPECIFICATION PRESSURES IN in.

Outlet Pressure

Nominal Factory

Nominal Inlet

Setting

Setting Range

Type of

Pressure

Full

Full

Model

Gas

Range

Step

Rate

Step

Rate

Standard-,

Natural

5.0 - 7.0

3.5

3.0 - 5.0

Slow-opening

LP

12.0 - 14.0

10.0

8.0 - 12.0

Step-

Natural

5.0 - 7.0

0.9

3.5

3.0 - 5.0

opening

LP

12.0 - 14.0

2.2

10.0

8.0 - 12.0

TABLE 6—PRESSURE REGULATOR SPECIFICATION PRESSURES IN kPa.

Outlet Pressure

Nominal Factory

Nominal Inlet

Setting

Setting Range

Type of

Pressure

Full

Full

Model

Gas

Range

Step

Rate

Step

Rate

Standard-,

Natural

1.2 - 1.7

0.9

0.7 - 1.2

Slow-opening

LP

2.9 - 3.9

2.7

2.0 - 3.0

Step-

Natural

1.2 - 1.7

0.2

0.9

0.7 - 1.2

opening

LP

2.9 - 3.9

0.9

2.7

2.0 - 3.0

CHECK SAFETY SHUTDOWN PERFORMANCE

WARNING

FIRE OR EXPLOSION HAZARD CAN
CAUSE PROPERTY DAMAGE, SEVERE
INJURY, OR DEATH

Perform the safety shutdown test any time work is
done on a gas system.

1. Place gas control knob in PILOT position. Main

burner should go off and pilot should remain lit.

2. Extinguish pilot flame. Pilot gas flow should stop

within 2-1/2 minutes. Safety shutoff of pilot gas proves
complete shutdown since safety shutoff valve prevents
main burner and pilot gas flow.

3. Relight pilot burner and operate system through one

complete cycle to assure all controls operate properly.

7

69-0683—1

!

Summary of Contents for VR4300

Page 1: ...ontinuous pilot gas controls are used in gas fired applianceswithcapacitiesupto300feet3 houratoneinchwc pressure drop 5 7 meters3 hour at 0 25 kPa on natural gas They include a manual valve safety shutoff two automatic operators a pressure regulator pilot adjustment and a con duit cover See Table 1 for temperature ranges and regulator types BODY PATTERN Straight through body pattern INLET X OUTLET...

Page 2: ...gascontrolsetfornaturalgasonLPgas or a gas control set for LP gas on natural gas To convert a gas control from natural gas to LP gas or from LP gas to natural gas contact your Honeywell representative Convert standard or slow opening gas controls from one gas to another with a conversion kit ordered sepa rately Order part number 393691 to convert from natural to LP gas Order part number 394588 to ...

Page 3: ...as Control 1 Mount the gas control 0 90 degrees in any direction including vertically from the upright position of the gas control knob 2 Mount the gas control so gas flow is in the direction of the arrow on the bottom of the gas control 3 Thread pipe the amount shown in Table 4 for inser tion into gas control Do not thread pipe too far Valve distortion or malfunction may result if the pipe is ins...

Page 4: ...ply before making wiring con nections to prevent electrical shock or equipment damage 1 Checkthepowersupplyratingonthegascontroland assure it matches the available supply Install thermostat and other controls as required 2 When the gas control is installed external to the appliance install the conduit cover on the conduit fitting Do not secure conduit cover at this time 3 Connect control circuit t...

Page 5: ...Inches Meters Inches Meters Inches Meters 12 0 3 47 1 2 30 0 8 18 0 5 18 0 5 41 1 0 26 0 7 16 0 4 24 0 6 35 0 9 22 0 6 14 0 4 30 0 8 29 0 8 18 0 5 11 0 3 36 0 9 23 0 6 15 0 4 9 0 2 40 1 0 19 0 5 12 0 3 7 0 2 48 1 2 11 0 3 7 0 2 60 1 5 Do not use Fig 7 Installing thermocouple to the power unit Fig 8 Wiring connections for 120 volt control 5 69 0683 1 120V THERMOSTAT POWER SUPPLY PROVIDE DISCONNECT ...

Page 6: ...ascontrolknobdownaboutoneminute then release If the pilot flame goes out turn the gas control knob clockwise to OFF and repeat steps 1 through 3 If pilot flame remains lit turn the gas control knob counterclockwise to ON ADJUST THE PILOT BURNER FLAME The pilot flame should envelop 3 8 to 1 2 inch 10 to 13 millimeters of the thermocouple tip Refer to Fig 9 To adjust the pilot flame 1 Remove the pil...

Page 7: ...er operation 4 If desired outlet pressure or flow rate cannot be achieved by adjusting the gas control check the inlet pressure using a manometer at inlet pressure tap or up stream of the gas control If the inlet pressure is in the normalrange refertoTable7or8 replacetheexistinggas control Otherwise take the necessary steps to provide proper gas pressure to the gas control 5 Carefully check main b...

Page 8: ...e energizing step opening model to assure lightoff at step pressure IFTHEPILOTBURNERFLAMEWILLNOTLIGHT 1 Assure the main gas supply valve is open and the pilot gas supply line is purged of air 2 Attempt to light pilot burner flame following proce dures in Light the Pilot Burner Flame page 6 If pilot burner flame still will not light a Check the pilot gas adjustment screw If closed readjust the pilo...

Page 9: ...c power to the appliance 3 Remove the gas control access panel 4 Push in the gas control knob slightly and turn clock wise to OFF NOTE The gas control knob cannot be turned from PILOT to OFF unless it is pushed in slightly Do not force the gas control knob 5 Wait five minutes to clear out any unburned gas If you then smell gas STOP Follow step 3 in the Warnings above If you do not smell gas contin...

Page 10: ...nd Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley Minnesota 55422 Scarborough Ontario M1P 2V9 QUALITY IS KEY Printed in U S A ...

Reviews: