HONEYWELL
HONEYWELL
HONEYWELL
HONEYWELL
CLASS “A” COMBINATION VALVES
VQ400M-Series
EN2R9081-C
October 2009
10
If common supply:
Loose screw (P) and cap (S). Turn coils and insert
adaptor (G).
Turn back coils and tight screw (P) and cap (S) by
tightening torque 2,5 Nm.
Connect corresponding contact by wires through
adaptor.
Tight cable support screws (C)
Place gaskets and cover lids in position (B)
Place screws (A) and tight.
Figure 6 Small model connected by common supply from outlet
side
Large models VQ440M-VQ450M
Each coil have to be supply separately.
Remove screws (A)
Take off protective cover lids and gasket (B)
Take off one from two plugs Pg11.
Prepare cables
•
Remove plastic outside insulation for about
50-75 mm.
•
Strip wires from plastic insulation for about
5-7mm.
Place cable support screw (C), steel ring(D), rubber
ring (E) and guide wires through the hole in the
cover to the connection block (F).
Connect wires between plates by tightening the
particular screws (F1, F2, F3)
•
Left: Phase
•
Middle: Earth connection
•
Right: Neutral
Tight cable support screws (C)
Place gaskets and cover lids in position (B)
Place screws (A) and tight.
Figure 7 Large model – V2 coil connected from outlet side
Wiring DIN plug
Follow the instructions supplied by the appliance
manufacturer as shown in the figures below. Coils
supply separate
Figure 8 Three pin electrical plug connector (according to
ISO 4400 / DIN EN 175301-803).