VPI Pressure Independent Control Valves & Actuators
31-00383-01
20
In Operation for DN50
–
DN250
During operating of MRP75MAC and MRE75MAC actuators, users will see below display screens which shows
multiple symbols and information. Carefully go through below table to familiarize with display indications during
operation with the meaning each symbol and operation.
Table 7. Display details during operation
Display
Description
Valve
Indicates unit scale system
l/sec or l/min or GPM.
mA or VDC.
Indicates battery level.
Basic version with no battery (MRP75MAC)
Failsafe version with battery (MRE75MAC).
Battery level low, charging needed.
Medium battery level.
Battery charged.
Alarm indicator.
Blinking if actuator is still functional (warning).
Fully on if actuator is not working (critical).
Current flow rate
1
.
Indicates current flow rate in l/sec,
l/hr or GPM.
CONTROL SIGNAL 2.0 VDC
FEEDBAC SIGNAL 2.0 VDC
VALVE 50H
PRESSURE RANGE 30-800 KPAD
MAXIMUM FLOW RATE 6.580 L/SEC
OPERAT DIRECT NC
ACTUAT.MODE LIN FLO
FAIL SAFE DIRECT CLOSE
ERROR CODE 01
Use
to go to next information line and
to go to the
previous.
Table 8. List of information from upper part of display during operation
Information
Meaning
Options
Control signal
Indicates value of control signal.
0-10 VDC or 0-20 mA or Open/Stop/Close
Feedback signal
Indicates value of feedback signal.
0-10 VDC or 0-20 mA
Valve
Indicates valve model.
50H, 65H, 80L … See,
Table 5. List of Reference Valve Codes
more options.
Pressure range
Indicates pressure range.
32-320 kPaD, 40-320 kPaD ...
Maximum flow rate
Indicates selected maximum de-
signed flow rate.
Depends on valve etc.
l/sec, l/hr or GPM
Operational direction
Indicates direction of rotation.
NO or NC
Actuator mode
Indicates control mode
Linear flow, Equal percentage, Linear rotation or Linear Signal.
Failsafe direction
Indicates failsafe direction.
Open or Closed
Valid for failsafe actuator models
Critical Alarm
Indicates alarm error code.
01, 03, 05 (without failsafe) or 06.
Only if critical alarm is present.
NOTE 1:
The flow rate shown on the actuator display is a calculated value. Flow rates below 1.0 valve rotation is shown as
indications, illustrated with an apostrophe in front of the flow rate. If display shows “NA” the valve model has not been
chosen in programming menu step 2.