Honeywell VISIONPRO TB8220U Installation Instructions Manual Download Page 14

TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT

62-3070—07

14

TROUBLESHOOTING (TABLE 7)

Table 7. Troubleshooting.

Symptom

Possible Cause

Action

Display does not come on.

Thermostat is not being powered.

Check for 24 Vac between C and Rc.
Check that AAA batteries are installed 
correctly and are good.

Temperature settings do not 
change.

The upper or lower temperature limits 
were reached.

Check temperature setpoints.
Check Installer Setup Numbers 0600 and 
0610; modify as needed.

The keypad is fully locked.

Check Installer Setup Number 0670 to 
change keypad locked options.

Heating or cooling does not 
come on.

Thermostat minimum off-time is 
activated.

Wait up to five minutes for the system to 
respond.

System selection not set to Heat or 
Cool.

Set system Selection to correct position.

System type Selection is incorrect.

Check Installer Setup Number 0170 and 
make sure correct System type is chosen.

Thermostat is calling for Heat 
(Heat on) or Cool (Cool on) but 
no heating or cooling is 
running.

Heating or cooling equipment is not 
operating.

Check wiring.
Check Installer Setup Number 0170 and 
make sure correct system type is chosen.
Verify operation of equipment in System Test 
mode.

Heat does not turn on (Heat 
On is solid in the display).

Heating equipment failure.

Check for 24 Vac at the equipment on the 
secondary side of the transformer between 
power and common. If voltage is not present, 
check the heating equipment to find the 
cause of the problem.

Check for 24 Vac between the heat terminal 
(W) and transformer common. If 24 Vac is 
present, the thermostat is functional. Check 
the heating equipment to find the cause of 
the problem.

Loose or broken wire connection 
between thermostat and heating 
equipment.

Check for 24 Vac between the heat terminal 
(W) and transformer common. If voltage is 
not present, check wire connection (loose or 
broken) between the thermostat and the 
heating equipment.

Heat pump puts out cool air in 
the heat mode and warm air in 
the cool mode.

Changeover Valve (Installer Setup 
Number 0190) is not configured to 
match the changeover required by the 
installed heat pump.

Set Changeover Valve (Installer Setup 
Number 0190) to match the changeover 
required by the installed heat pump.

Both the heating and cooling 
equipment are running at the 
same time.

The heating equipment is not a heat 
pump but the System Type (Installer 
Setup Number 0170) is set to Heat 
Pump.

Set System Type (Installer Setup Number 
0170) to match the installed heating and/or 
cooling equipment.

Heating and cooling wires are shorted 
together.

Separate the shorted heating and cooling 
wires.

Cooling does not turn on (Cool 
On is solid in the display).

Cooling equipment failure.

Check for 24 Vac at the equipment on the 
secondary side of the transformer between 
power and common. If voltage is not present, 
check the cooling equipment to find the 
cause of the problem.

Check for 24 Vac between the cool terminal 
(Y) and transformer common. If 24 Vac is 
present, the thermostat is functional. Check 
the cooling equipment to find the cause of 
the problem.

Loose or broken wire connection 
between thermostat and cooling 
equipment.

Check for 24 Vac between the cool terminal 
(Y) and transformer common. If voltage is not 
present, check the wire connection (loose or 
broken) between the thermostat and the 
cooling equipment.

Summary of Contents for VISIONPRO TB8220U

Page 1: ...ngs given in instructions and on the product to ensure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installati...

Page 2: ...in holes Tap the wall anchors provided into the drilled holes until flush with the wall 5 Pull the wires through the wire hole on the wallplate and position the wallplate over the wall anchors 6 Insert the mounting screws into the wall anchors and tighten Fig 3 Install wallplate WIRING IMPORTANT All wiring must agree with applicable codes ordinances and regulations Use 18 gauge thermostat wire Shi...

Page 3: ...r the W7459 TR terminal When using dual transformers at the thermostat the heating transformer must power the economizer The A signal is powered from the R terminal and energizes the economizer to signal occupied status and drive the damper to the set minimum position Table 3 Wiring Diagrams M19917 WALLPLATE M22266 WALL OPENING WIRE SHADED AREA Terminal Designation Description Rc see Note 1 Power ...

Page 4: ...4V COMMON CONNECTION IS OPTIONAL WHEN USED THE COMMON MUST CONNECT TO THE COOLING TRANSFORMER SECONDARY 1 3 2 3 2 Y2 L A W2 S1 S2 2 RC R W Y G C ECONOMIZER L1 HOT L2 1 24 VAC L1 HOT L2 1 24 VAC M22783A OUTDOOR INDOOR TEMPERATURE SENSOR HEAT RELAY POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FACTORY INSTALLED JUMPER WHEN USING BATTERIES THE 24V COMMON CONNECTION IS OPTI...

Page 5: ...NG BATTERIES THE 24V COMMON CONNECTION IS OPTIONAL 1 3 2 3 COOL RELAY 1 HEAT RELAY 1 COOL RELAY 2 Y2 L A W2 S1 S2 2 RC R W Y G C L1 HOT L2 1 24 VAC ECONOMIZER M22787A HEAT RELAY 2 OUTDOOR INDOOR TEMPERATURE SENSOR FAN RELAY POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE FACTORY INSTALLED JUMPER WHEN USING BATTERIES THE 24V COMMON CONNECTION IS OPTIONAL WHEN USED T...

Page 6: ...ROL AS EITHER O OR B IN THE INSTALLER SETUP OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE OUTDOOR INDOOR TEMPERATURE SENSOR 3 Y2 L A W1 S1 S2 2 RC R O B Y G C 4 L1 HOT L2 1 24 VAC 5 ECONOMIZER COMPRESSOR CONTACTOR ECONOMIZER M22790A CHANGEOVER VALVE FAN RELAY 1 2 3 4 5 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOA...

Page 7: ...21 A 10K ohm sensor to provide a temperature averaging network Fig 21 Wiring four C7189U 10K ohm Sensors to provide a temperature averaging network M27481 S1 S2 T T SUBBASE TR21 T T TR21 T T TR21 T T TR21 M27482 S1 S2 SUBBASE TR21 A T4 T3 TR21 A T4 T3 1 1 1 THE TR21 A IS A 10K OHM SENSOR M27483 T4 T3 TR21 A 1 1 THE TR21 A IS A 10K OHM SENSOR S1 S2 T T SUBBASE TR21 T T TR21 M22935 WIRES MUST HAVE A...

Page 8: ...rmostat is designed to under normal use automatically keep current time and day in memory for up to ten years once the calendar is set There are two ways to set the calendar for this thermostat SETTING CALENDAR WHEN THERMOSTAT IS FIRST POWERED When the thermostat is first powered the display is ready to set the calendar and time The thermostat proceeds through a sequence of setup screens See Fig 2...

Page 9: ...TESTS TABLE 4 Fig 26 Entering Installer Setup Installer System Tests Use the Installer System Test to test the heating cooling and fan Refer to the latter portion of Table 4 CAUTION Equipment Damage Hazard Minimum compressor off time is bypassed during Installer System Test Avoid cycling compressor quickly IMPORTANT Use Installer System Test to test heating cooling and fan The setting chosen for S...

Page 10: ...stages Selection in this stage changes default CPH of second stage cool 0230 CPH for second stage compressor 3 1 6 Only shown if two stages of cool selected 0240 CPH for first stage conventional heat 5 1 12 Only shown if system is conventional with heat stages Selection in this stage changes default CPH of second stage heat 0250 CPH for second stage conventional heat 9 1 12 Only shown with at leas...

Page 11: ...ys of the week With 2 selected the Cancel Period option does not appear on the display 0580 Minimum Compressor Off Time 5 0 Off 2 2 minutes 3 3 minutes 4 4 minutes 5 5 minutes Only shown if system has cool stages 0600 Heat Temperature Range Stops 90 40 to 90 F 4 to 32 C Only shown if system has heat stages 0610 Cool Temperature Range Stops 50 50 to 99 F 10 to 37 C Only shown if system has cool sta...

Page 12: ... oversized equipment 0695 Recovery Cool Ramp Rate 3 0 20 F hour Only shown if system has cool stages 0 disables ramped recovery step setpoint change at period start time 0700 Temperature Display Offset 0 3 1 5 3 F 1 5 C 2 1 0 2 F 1 0 C 1 0 5 1 F 0 5 C 0 0 0 0 F 0 0 C 1 0 5 1 F 0 5 C 2 1 0 2 F 1 0 C 3 1 5 3 F 1 5 C This offset applies to both the control temperature and to the display temperature f...

Page 13: ...oint Temperature in Installer Setup Number 0350 OPERATION IN HEAT MODE ABOVE BALANCE POINT OUTDOOR TEMPERATURE When the outdoor temperature is above the selected Balance Point Temperature ISU 0350 only the compressor operates and the fan G terminal energizes when the thermostat calls for heat OPERATION IN HEAT MODE BELOW BALANCE POINT OUTDOOR TEMPERATURE When the outdoor temperature is below the s...

Page 14: ...e thermostat is functional Check the heating equipment to find the cause of the problem Loose or broken wire connection between thermostat and heating equipment Check for 24 Vac between the heat terminal W and transformer common If voltage is not present check wire connection loose or broken between the thermostat and the heating equipment Heat pump puts out cool air in the heat mode and warm air ...

Page 15: ...tem setting to Heat System Type Installer Setup Number 0170 is set to Cool Only Set System Type Installer Setup Number 0170 to match the installed heating and or cooling equipment Cannot set the system setting to Cool System Type Installer Setup Number 0170 is set to Heat Only or Heat Only with Fan Set System Type Installer Setup Number 0170 to match the installed heating and or cooling equipment ...

Page 16: ...4 4 C to 65 6 C Operating Relative Humidity Non condensing 5 to 90 Thermostat Dimensions 3 3 4 in 95 mm high x 6 in 152 mm wide x 1 3 8in 35 mm deep Accessories C7089U Outdoor Sensor 10K ohm NTC C7189U Remote Indoor Sensor 10K ohm NTC C7772 Flush Mount Remote Indoor Sensor 20K ohm NTC TR21 Wall Mount Remote Indoor Sensor 20K ohm NTC TR21 A Wall Mount Remote Indoor Sensor 10K ohm NTC Perchlorate Ma...

Reviews: