Honeywell VE4000 Series Instruction Sheet Download Page 1

Honeywell

 

VE4000 & VE5000 SERIES  

CLASS "A" GAS VALVES 

  INSTRUCTION 

SHEET 

 

ISTR0018  1602RA-NE 

 

 

APPLICATION 

These series class A gas valves are used for control and 
regulation of gaseous fluids in gas power burners, atmospheric 
gas boilers, melting furnaces, incinerators and other gas 
consuming appliances 
 
 

GENERAL 

  

DESCRIPTION 

 
VE4000 Series Gas Valve 
The VE series gas valves offer a series of functionalities: 

 

Gas valves, Normally Closed. 

 CPI 

switch 

optional 

 

Gas valves for use with Honeywell V4055, V4062 and 
V9055 fluid power actuators. 

 

Relief valves Normally Open. 

 

Adjustable opening characteristics optional 

  

FEATURES 

 

 

The VExxxxX1xxx series gas valves have a wrench boss  
as well on inlet side as on outlet side for pipe fitting 
incorporated in the valve housing. 

 

The VExxxxX3xxx and VE5xxxX3xxx series gas valves 
are equipped at both sides with mounting holes to adapt a 
pilot solenoid valve combination, to allow either internal or 
external pilot gas. Furthermore these valves are equipped 
with two M6 mounting holes to adapt an A4020A 
electronic leak test The VExxxxB series gas valves have 
an adjustable flow rate regulator on top of the coil. 

 

For the VE series gas valves a series of field replaceable 
connection boxes (including circuits) are available 

 

The VExxxxC series gas valves have adjustments for step 
pressure flow rate and opening speed in hydraulic damper 
unit on top of the coil. 

 

The VExxxxS series gas valves normally open relief 
valves have no option for mounting a CPI switch 

 

The VE5xxxX3xxx series gas valves can be equipped with 
a wide range of Honeywell fluid power actuators. These 
fluid power actuators are field replaceable. 

 
 
 

 

Subj

ect to cha

nge w

itho

u

t notice. All rig

h

ts reserve

d

.  

Summary of Contents for VE4000 Series

Page 1: ...e housing The VExxxxX3xxx and VE5xxxX3xxx series gas valves are equipped at both sides with mounting holes to adapt a pilot solenoid valve combination to allow either internal or external pilot gas Furthermore these valves are equipped with two M6 mounting holes to adapt an A4020A electronic leak test The VExxxxB series gas valves have an adjustable flow rate regulator on top of the coil For the V...

Page 2: ...egulated ON OFF VExxxxAxxxx Standard Standard Flow regulator VExxxxBxxxx Optional Optional 2 Adjustable opening and flow regulator VExxxxCxxxx Optional 1 Not available Motorized opening ON OFF VE5xxxAxxxx Not available VE5065A3xxx VE5085A3xxx Motorized opening characterized VE5xxxCxxxx Not available VE5065C3xxx VE5085C3xxx Safety relief valve ON OFF Normally Open with or without position indicatio...

Page 3: ...alve will function between 85 and 110 of the rated voltage Electrical connection VE4xxx VE6xxx VE8xxx Option 1 Wiring on terminal block on circuit cables entering box via PG Cable Gland Option 2 Connection by means of DIN plug on DIN faced connection located on front cover according to ISO4400 DIN EN 175301 803 Electrical connection VE5xxx series See product literature fluid power actuators Enclos...

Page 4: ...2 723 125 180 POWER CONSUMPTION Version S 200 mbar Model number 12 Volt 50 60Hz nominal 12 Volt 50 60Hz 110 of nominal 24Volt 50 60Hz nominal 24 Volt 50 60Hz 110 of nominal 24 Volt dc nominala b 24 Volt dc 110 of nominal 110 Volt 50 60Hz nominal 110 Volt 50 60Hz 110 of nominal 220 Volt 50 60Hz nominal 220 Volt 50 60Hz 110 of nominal VExx20S 16 19 17 21 14 17 16 19 POWER CONSUMPTION Version S 360 m...

Page 5: ...n alternative In order to tighten the pipe in the valve do not use the actuator as a lever but use a suitable wrench operating on the wrench bosses Main gas connection flanged valves Take care that dirt cannot enter the gas valve during handling Ensure the gas flows in the same direction as the arrow on the housing of the gas valve Ensure that inlet and outlet flanges are in line and separated fro...

Page 6: ...the box and tightened as shown in Fig 2 Specified torque for the nut 4 Nm Mounted PG gland shown in Fig 3 Specified torque PG gland 3 Nm Fig 2 Fig 3 After connecting wires L N PE to dedicated connectors on connector block the connection needs to closed by mounting the front cover Before placing the cover please check the correct position of seal as shown in Fig 4 The cover can only be mounted in o...

Page 7: ... in the slot of adjustment screw which is situated in center of the valve Turn screw driver counter clockwise to increase or clockwise to decrease step pressure Replace cap on top of the coil Step pressure adjustment Fig 8 Opening speed adjustment Remove the cap from top of the coil by loosening both screws Place screw driver in the slot of adjustment screw which is of center line Turn screw drive...

Page 8: ... 200 240 DIN BB0xxxxx VExx20 VExx25 24 PG BB0xxxxx 100 120 PG BB0xxxxx 200 240 PG BB0xxxxx VExx20 VExx25 24 DIN BB0xxxxx 100 120 DIN BB0xxxxx 200 240 DIN BB0xxxxx VExx32 VExx40 24 PG BB0xxxxx 100 120 PG BB0xxxxx 200 240 PG BB0xxxxx VExx32 VExx40 24 DIN BB0xxxxx 100 120 DIN BB0xxxxx 200 240 DIN BB0xxxxx Valve type Voltage Connection Ordering number VExx50 24 PG BB0xxxxx 100 120 PG BB0xxxxx 200 240 ...

Reviews: