PRODUCT DATA
65-0230-07
V5097A-E
Industrial Gas Valves
APPLICATION
The V5097A-E Gas Valves are used with the V4055, V4062
and V9055 Fluid Power Actuators to control gas flow to
commercial and industrial burners.
While it is possible to combine any V5097 gas valve with any
V4055, V4062, or V9055 fluid actuator, a limited range of
combinations apply to the application most often used. See
FEATURES
• Used with natural or liquefied petroleum (LP) gases.
• V5097 normally closed valves are rated for final shutoff
service (safety shutoff).
• V5097A,C,D,E Valves are for on-off service.
• V5097B Valve has a characterized guide and in
combination with the V4055, V4062 and V9055 Fluid
Power Actuators, provides slow-opening, HI-LO-OFF,
and modulating functions, respectively.
• V5097C,E Valves have a double seal and are used
with V4055D,E Fluid Power Actuators to provide
proof-of-closure switch and valve seal overtravel
interlock.
• V5097D,E Valves are for high pressure applications
• Two valve body types (small and large) applicable to
seven pipe sizes:
— Small body type for 3/4 in. (19 mm), 1 in. (25 mm),
1-1/4 in. (32 mm), 1-1/2 in. (38 mm) and 2 in. (51
mm) pipes.
— Large body type for 2 in. (51 mm), 2-1/2 in. (64 mm)
and 3 in. (76 mm) pipes.
• Eight pipe adapter sizes 3/4 in. (19 mm) to 3 in. (76 mm)
have NPT or BSP-PL threaded connections.
• V5097 version provides three 1/4 in. upstream and
two 1/4 in. downstream taps and plugs. CE version
provides an additional downstream tap and plug.
• Valve body rating of 75 psi (5 bar); body passes
Underwriters Laboratories Inc. burst test.
• Yellow SHUT indicator attached to the valve stem
provides indication of the valve closed position.
• Unpainted die-cast aluminum body.
Contents
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
To Size Two Identical Valves Piped In Series ...................
Installation ........................................................................
Operation and Checkout ..................................................
Service Information .......................................................... 10