GB
MU0H-2327GE23 R0618
9
Honeywell GmbH
*Contact the manufacturer to modify.
5.1 Setting procedure
Other parameters can be set, if necessary, without a preferential path.
5.2 Setting parameter SET 4: PRESETTING
The presetting flow rate of valve V5004TF can be set through the parameter SET 4 of the M5004 actuator: the parameter should
set between the max and min presetting flow rate of the valve. SET 3 should be left at 0.
6
Ratio of Value of Flow According to Flow Curve
SET12*
Value on
display
Max. voltage control signal
Selection max voltage control value with UP/DOWN buttons
and confirmation with MODE button
SET13
Actuator rotation speed 1.5 RPM Selection of actuator rotation speed with UP/DOWN buttons
and confirmation with MODE button
Actuator rotation speed 1 RPM
Actuator rotation speed
automatic
SET14
Voltage feedback signal
Selection of feedback signal type with UP/DOWN buttons
and confirmation with MODE button
Voltage feedback signal
Current feedback signal
Current feedback signal
SET 9
SET 4
SET 2
SET 10
Valve
V5004TF
1050
V5004TF
1065
V5004TF
1080
V5004TF
1100
V5004TF
1125
V5004TF
1150
V5004TF
1200LF
V5004TF
1200HF
V5004TF
1250LF
V5004TF
1250HF
Max
presetting
flow rate
(m
3
/h)
20
30
30
55
90
150
200
300
300
500
Min
presetting
flow rate
(m
3
/h)
2
3
3
5.5
9
15
20
30
30
50
POSITION of
VALVE LIFT
(Unit: %)
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
LINEAR CURVE
(Unit: %)
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
EQUAL
PERCENTAGE
CURVE (Unit: %)
0 2 3 4 4 5 6 8 10 12 14 17 21 25 31 38 46 56 68 82 100