Honeywell V4295A,S Installation Instructions Manual Download Page 5

V4295A,S; V8295A,S SOLENOID GAS VALVES

5

65-0194—04

INSTALLATION

When installing this product...

1.

Read this instructions carefully. Failure to follow them 

could damage the product or cause a hazardous condi-

tion.

2.

Check the rating given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced, flame safe-

guard control technician.

4.

After installation is complete, check out product opera-

tion as provided in these instructions.

CAUTION

1. Turn off gas supply before starting installation.

2. Disconnect power supply before beginning 

installation to prevent electrical shock and 

equipment damage.

3. Do not remove seal over valve inlet or outlet 

until ready to connect piping.

Prepare piping and install valve (Fig. 5)

1.

Use new, properly reamed pipe which is free from chips.

2.

Do not thread pipe too far.

3.

Apply good quality pipe dope resistant to the action of 

LP gas, putting a moderate amount on the male threads 

only. If pipe dope lodges on the valve seat, it will prevent 

proper closure.

4.

Install valve in a horizontal pipe line, (refer to Fig. 5 for 

mounting position) with the gas flow matching the direc-

tion indicated by the arrow on the casting.

5.

Apply a parallel jaw wrench only to the wrench flats of 

the valve body, next to the pipe being inserted. A 

wrench applied to the valve body itself or to the end far-

thest from the pipe being inserted may distort the cast-

ing, resulting in malfunction on the gas valve.

6.

The gas flow 

must

 be in the same direction as the arrow 

on the body of the valve.

WARNING

If the flow is not in the same direction of arrow, 

valve may not shut off.

Fig. 5. Mounting position.

7.

Make electrical connections as illustrated in the wiring 

diagrams; see Fig. 6.

8.

Turn on main gas and with a soap solution, check valve 

installation for leaks.

WIRING

1.

Disconnect power supply 

before

 making wiring connec-

tions to prevent electrical shock and equipment dam-

age.

2.

Installation and wiring must be in conformance with 

National Electrical Code ANSI/NFPA 70, local codes 

and regulations.

3.

For normal installations, use moisture-resistance No. 14 

wire suitable for at least 167ºF (75ºC) if using a Flame 

Safeguard Primary Control, or 194ºF (90ºC) if using a 

Flame Safeguard Programming Control.

4.

For high temperature installations, use moisture resis-

tant No. 14 wire selected for a temperature rating above 

the maximum operating temperature.

5.

Check the power supply circuit. The voltage and fre-

quency must match those of the valve.

6.

Refer to Fig. 6 for typical V4295A,S field wiring with 

RM7800 (typical) Primary Safety Control. Refer to Fig. 7 

for typical V8295A,S field wiring with Primary Safety 

Control. Follow the burner manufacturer’s wiring dia-

gram, when provided. Refer to burner controller (pri-

mary safety control) wiring diagram for specific wiring 

terminal designations.

7.

Make wiring connections at the electrical terminations 

provided in the wiring compartment of the valve.

M28663

Summary of Contents for V4295A,S

Page 1: ...dels for vent double block and bleed valve applications consist of a direct electric on off operator for closing and opening of the valve Models are suitable for the control of gaseous fluids in gas consuming appliances according to international standards Models have 1 4 inch NPT inlet and outlet pressure taps Models have inlet screen to protect the valve from the entry of dirt SPECIFICATIONS Mod...

Page 2: ...Models Available Model Voltage Frequency Maximum Pressure Pipe size inch Thread type psi mbar V4295A N C 110 120 Vac 50 60 Hz 2 0 140 3 8 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 NPT V4295A N C 110 120 Vac 50 60 Hz 5 0 350 3 8 1 2 3 4 1 1 1 4 1 1 2 2 NPT V4295S N O 110 120 Vac 50 60 Hz 2 0 140 3 4 1 1 1 4 NPT V8295A N C 24 Vac 50 60 Hz 2 0 140 3 8 1 2 3 4 1 1 1 4 1 1 2 2 NPT V8295S N O 24 Vac 50 60 Hz 2 0 ...

Page 3: ... 1 2 0 2 0 8 0 1 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 400 0 4 1 0 P KPA X 100 Vg NATURAL GAS SG 0 64 CFH P IN W C 3 8 IN 1 2 IN 3 4 IN 1 IN 1 1 2 IN 1 1 4 IN 2 IN 2 1 2 IN 3 IN M28667 6 24 5 20 4 16 3 12 2 8 1 4 0 8 3 2 0 6 2 4 0 5 2 0 0 4 1 6 0 3 1 2 0 2 0 8 0 1 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 400 0 4 1 0 P KPA P IN W C 3 8 IN 1 2 IN 3 4 IN 1 IN 1 1 2 IN 1 1 4 IN 2 IN X 1...

Page 4: ...8662 E Table 4 Normally Closed See Fig 3 Pipe size A inch B inch C inch D inch E inch both sides Weight lbs 2 psi 5 psi 2 psi 5 psi 2 psi 5 psi 2 psi 5 psi 3 8 in NPT 2 7 8 4 7 16 4 7 16 2 3 16 2 3 16 3 3 4 3 3 4 2 3 16 2 5 2 2 1 2 in NPT 2 7 8 4 7 16 4 7 16 2 3 16 2 3 16 3 3 4 3 3 4 2 3 16 2 5 2 2 3 4 in NPT 3 7 16 5 1 4 5 13 16 2 3 16 2 1 2 3 3 4 4 1 16 2 3 4 4 0 4 4 1 in NPT 3 15 16 5 1 4 6 5 1...

Page 5: ...far thest from the pipe being inserted may distort the cast ing resulting in malfunction on the gas valve 6 The gas flow must be in the same direction as the arrow on the body of the valve WARNING If the flow is not in the same direction of arrow valve may not shut off Fig 5 Mounting position 7 Make electrical connections as illustrated in the wiring diagrams see Fig 6 8 Turn on main gas and with ...

Page 6: ... valve and make sure valve is closed when setting up pressure measuring equipment 3 Set thermostat or controller to energize the valve and check final outlet pressure 4 Start the system and observe its operation through at least one complete cycle to ensure the valve functions as described in the section Operation on page 6 Valve Leak Test Fig 8 This is a test for checking the closure tightness of...

Page 7: ...em to normal operation If two safety shutoff valves are used check each valve separately for closure tightness TROUBLESHOOTING CAUTION Use utmost care during troubleshooting Line voltage is present at the actuator for V4295A S and present in controller circuits Low voltage 24 Vac is present at the actuator for V8295A S and present in controller circuits IMPORTANT Do not assume that the valve must ...

Page 8: ...eeding d If there is proper voltage at the actuator but the valve still does not open first check that the gas pressure is normal e If the valve still does not open replace valve 2 If the valve will not close when one or more of the appropriate contacts in the thermostat or control ler limit s or flame safeguard control is open a Make sure that the gas flow is in the direction of the arrow on the ...

Reviews: