V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

60-2099—9

4

Fig. 1. Approximate mounting dimensions of V4062 Actuators in in. (mm).

Table 7. Approximate Mounting Dimensions of V4062 Actuators with V5055 and V5097 Valves.

a

 Valve size using accessory pipe adapter fitting.

INSTALLATION

When Installing This Product…

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained experienced, flame 

safeguard control technician.

4.

After installation is complete, check out product 

operation as prided in these instructions.

WARNING

Electrical Shock Hazard.

Can cause serious injury or death.

Disconnect power supply before making wiring 

connections to prevent electrical shock and 

equipment damage.

IMPORTANT

1. All wiring must comply with all applicable electrical 

codes, ordinances, and regulations. All wiring must be 

NEC Class 1.

2. Voltage and frequency of the power supply connected to 

this control must agree with those marked on the device.

3. Loads connected to the auxiliary switch and/or 

proof-of-closure switch, if used, must not exceed the 

ratings given in the Specifications section.

4. When replacing a V6034 Actuator with a V4062, the 

V5034 Valve body must be changed to a V5055 Valve.

5. Do not attempt to use the V4062 Actuator with the 

V4055/V5034 Adapter. Differences in stem travel can 

prevent correct low fire adjustment.

Valve Size

a

 (in.)

V5055

V5097

Dim. A

Dim. B

Dim. C

Dim. D

Dim. A

Dim. B

Dim. C

Dim. D

in.

mm

in.

mm

in.

mm

in.

mm

in.

mm

in.

mm

in.

mm

in.

mm

Small 

Body

3/4

11-1/8

283

2-3/4

70

8-3/16

208

5-3/4

146

11-1/8

283

2-3/4

70

8-3/16

208

2-1/2

64

1

11-1/8

283

2-3/4

70

8-3/16

208

5-3/4

146

11-1/8

283

2-3/4

70

8-3/16

208

2-/12

64

1-1/4

11-1/8

283

2-3/4

70

8-3/16

208

5-3/4

146

11-1/8

283

2-3/4

70

8-3/16

208

2-1/2

64

1-1/2

11-1/8

283

2-3/4

70

8-3/16

208

5-3/4

146

11-1/8

283

2-3/4

70

8-3/16

208

2-1/2

64

2

11-1/8

286

2-7/8

73

8-5/16

211

8-3/8

213

11-3/4

298

3-3/8

86

8-3/8

213

4

102

Large 

Body

2

11-3/4

298

3-3/8

86

8-13/16 224

9-1/4

235

11-3/4

298

3-3/8

86

8-3/8

213

4

102

2-1/2

11-3/4

298

3-3/8

86

8-13/16 224

9-1/4

235

11-3/4

298

3-3/8

86

8-3/8

213

4

102

3

11-3/4

298

3-38

86

8-13/16 224

9-1/4

235

11-3/4

298

3-3/8

86

8-3/8

213

4

102

4

14-1/8

359

5-13/16 148

11-7/32 285

12-1/2

318

D

A

1

1

 (33)

KNOCKOUT FOR 
1/2 INCH CONDUIT (4)

5 (127)

1-9/32

27/32 (21)

3-23/32 (95)

6-3/4  (172)

C

B

ALLOW 4 INCH (102 MM) CLEARANCE FOR ACTUATOR REMOVAL.

M17755

VALVE

VALVE

Summary of Contents for V4062A

Page 1: ...ch meets code standard insurer requirements Damper shaft models are available with or without spring return shaft extends out both sides and rides in Delrin bushings used with standard damper crank arm part no 7616BR Red OPEN indicator attached to the actuator stem shows when the valve is even slightly open yellow SHUT indicator on the valve stem shows only when the gas valve is fully closed Ambie...

Page 2: ...e conditions are changed Models V4062A HI LO OFF Gas Valve Actuator V4062B HI LO OFF Gas Valve Actuator high pressure V4062D HI LO OFF Gas Valve Actuator with proof of closure switch Use with V5055 V5097C E double seal gas valves for valve seal overtravel interlock Do not use V4062 with V5034 Valve body Electrical Ratings Standard V4062A D Actuators Table 1 60 Hz 26 second opening 50 Hz 32 second ...

Page 3: ...3 mm radius for 7616BR Damper Crank Arm ordered separately NOTE Damper shaft drives damper crank arm in one direction only optional return spring is available on damper shaft to turn damper crank arm in opposite direction See Table 6 Table 6 Actuator Torque With and Without Return Spring Ambient Operating Temperature Rating 40 to 150 F 40 to 66 C for 60 Hz models 10 to 158 F 23 to 70 C for 50 Hz a...

Page 4: ...y switch and or proof of closure switch if used must not exceed the ratings given in the Specifications section 4 When replacing a V6034 Actuator with a V4062 the V5034 Valve body must be changed to a V5055 Valve 5 Do not attempt to use the V4062 Actuator with the V4055 V5034 Adapter Differences in stem travel can prevent correct low fire adjustment Valve Sizea in V5055 V5097 Dim A Dim B Dim C Dim...

Page 5: ... in the position indicated in Fig 2 Fasten with two screws through the actuator base 4 Insert the proof of closure switch in the position shown in Fig 2 The proof of closure switch mounts against the side of the actuator housing The mounting holes are spaced to allow mounting the switch only in the correct position Fasten with two screws through the actuator base 5 If only one switch is used insta...

Page 6: ...o control the valve When all wiring connections are complete replace the actuator faceplate CAUTION Equipment Damage Hazard Can cause equipment damage or improper and dangerous operation Label all wires prior to disconnection when servicing valves Wiring errors can cause improper and dangerous operation Fig 4 Typical hookup for V4062 Actuator Fig 5 Connecting Max Flow Limit Switch to the actuator ...

Page 7: ...rmined low fire setting for the burner being used 5 Tighten the setscrew in the cam 6 Replace the wiring compartment cover Alternate Procedure To adjust the low fire setting after the burner is in operation use the following instructions 1 Remove the wiring compartment cover 2 Check to be sure the low fire adjustment is set at MAX to assure a safe lightoff Low fire adjustment is preset at the fact...

Page 8: ...UTION Equipment Damage Hazard Unskilled technicians can damage the equipment Only experienced trained flame safeguard control service technicians should service or replace this control Service The actuator is not field repairable except for replacing the auxiliary switch or valve closed indication switch See Installation section for procedure Do not disassemble the valve actuator If the actuator s...