Honeywell V4062A Manual Download Page 1

PRODUCT DATA

60-2099-9

® U.S. Registered Trademark
Copyright © 2001 Honeywell •  All Rights Reserved 

V4062A,B,D

HI-LO-OFF Fluid Power

Gas Valve Actuator

APPLICATION

The V4062 Gas Valve Actuator in combination with a V5055, 

VE5000

a

 or V5097 Gas Valve provides three-position control 

of the gas supply to commercial and industrial burners.

FEATURES

• When energized, the V4062 Actuator opens the

 V5055/VE5000/V5097 Gas Valve to the low-fire 

position. The actuator opens the valve to the fully open 

position when the line voltage contacts are made.

a

 VE5000 is a European manufactured and approved valve for 

European use only.

• When used with the V5055, V5097 or VE5000

a

 Gas 

Valve, the combination is rated for final safety shutoff 

service.Although the V4062 can be used with all V5055 

or V5097 Valve models, the V5055/V5097B with 

characterized guide is recommended for optimum 

control and low-fire repeatability.

• The standard model has an opening time of 

26 seconds at 60 Hz, or 32 seconds at 50 Hz. A 

fast-opening model is available, with timings of 

13 seconds at 60 Hz, or 16 seconds at 50 Hz.

• Maximum closing time is one second, which meets 

code, standard, insurer requirements.

• Damper shaft models are available with or without 

spring return; shaft extends out both sides and rides 

in Delrin bushings; used with standard damper crank 

arm (part no. 7616BR).

• Red OPEN indicator attached to the actuator stem 

shows when the valve is even slightly open; yellow 

SHUT indicator on the valve stem shows only when 

the gas valve is fully closed.

• Ambient temperature range is -40° to 150°F (-40° to 

66°C) for 60 Hz models; -10° to 158°F (23° to 70°C) for 

50 Hz and 50/60 Hz models.

• Models available with factory adjusted, field-

adjustable, single-pole-double throw (spdt) auxiliary 

switch rated at 1/2 hp (0.37 kW). Auxiliary switch can 

be added in the field.

• Low-fire position is adjustable with adjusting wrench, 

part no. 135796 (included with the actuator).

• Standard enclosure meets NEMA 1 (IP30) general 

purpose requirements.

• V4062/V5055C,E and V4062/V5097C,E combinations 

available with a proof-of-closure switch and double 

valve seal (valve seal overtravel interlock) to meet 

specific code/standard/insurer requirements.

• Model available to be used with series 60 floating type 

controller.

• Model available with adjustable maximum flow switch.

Contents

Application ........................................................................

1

Features ...........................................................................

1

Specifications ...................................................................

2

Ordering Information  ........................................................

2

Installation ........................................................................

4

Wiring ...............................................................................

6

Adjustments ......................................................................

7

Operation ..........................................................................

8

Service and Checkout  ......................................................

8

Summary of Contents for V4062A

Page 1: ...ch meets code standard insurer requirements Damper shaft models are available with or without spring return shaft extends out both sides and rides in Delrin bushings used with standard damper crank arm part no 7616BR Red OPEN indicator attached to the actuator stem shows when the valve is even slightly open yellow SHUT indicator on the valve stem shows only when the gas valve is fully closed Ambie...

Page 2: ...e conditions are changed Models V4062A HI LO OFF Gas Valve Actuator V4062B HI LO OFF Gas Valve Actuator high pressure V4062D HI LO OFF Gas Valve Actuator with proof of closure switch Use with V5055 V5097C E double seal gas valves for valve seal overtravel interlock Do not use V4062 with V5034 Valve body Electrical Ratings Standard V4062A D Actuators Table 1 60 Hz 26 second opening 50 Hz 32 second ...

Page 3: ...3 mm radius for 7616BR Damper Crank Arm ordered separately NOTE Damper shaft drives damper crank arm in one direction only optional return spring is available on damper shaft to turn damper crank arm in opposite direction See Table 6 Table 6 Actuator Torque With and Without Return Spring Ambient Operating Temperature Rating 40 to 150 F 40 to 66 C for 60 Hz models 10 to 158 F 23 to 70 C for 50 Hz a...

Page 4: ...y switch and or proof of closure switch if used must not exceed the ratings given in the Specifications section 4 When replacing a V6034 Actuator with a V4062 the V5034 Valve body must be changed to a V5055 Valve 5 Do not attempt to use the V4062 Actuator with the V4055 V5034 Adapter Differences in stem travel can prevent correct low fire adjustment Valve Sizea in V5055 V5097 Dim A Dim B Dim C Dim...

Page 5: ... in the position indicated in Fig 2 Fasten with two screws through the actuator base 4 Insert the proof of closure switch in the position shown in Fig 2 The proof of closure switch mounts against the side of the actuator housing The mounting holes are spaced to allow mounting the switch only in the correct position Fasten with two screws through the actuator base 5 If only one switch is used insta...

Page 6: ...o control the valve When all wiring connections are complete replace the actuator faceplate CAUTION Equipment Damage Hazard Can cause equipment damage or improper and dangerous operation Label all wires prior to disconnection when servicing valves Wiring errors can cause improper and dangerous operation Fig 4 Typical hookup for V4062 Actuator Fig 5 Connecting Max Flow Limit Switch to the actuator ...

Page 7: ...rmined low fire setting for the burner being used 5 Tighten the setscrew in the cam 6 Replace the wiring compartment cover Alternate Procedure To adjust the low fire setting after the burner is in operation use the following instructions 1 Remove the wiring compartment cover 2 Check to be sure the low fire adjustment is set at MAX to assure a safe lightoff Low fire adjustment is preset at the fact...

Page 8: ...UTION Equipment Damage Hazard Unskilled technicians can damage the equipment Only experienced trained flame safeguard control service technicians should service or replace this control Service The actuator is not field repairable except for replacing the auxiliary switch or valve closed indication switch See Installation section for procedure Do not disassemble the valve actuator If the actuator s...