Honeywell V4055F Product Data Download Page 4

V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL

65-0029—01

4

WARNING

Explosion Hazard.

Can cause explosion, serious injury or death.

1. Turn off gas supply before starting installation.

2. Disconnect power supply for valve actuator before 

beginning installation.

3. Install the valve so the arrow on the valve body 

points in the gas flow direction.

Install Valve

The actuator is mounted directly on the valve bonnet after the 

valve is installed in the gas supply line. Refer to the instruction 

sheet packed with the gas valve for details of installation. 

When installing the valve, ensure that:

1.

Sufficient clearance.is left for installation and service of 

the actuator.

2.

Ambient temperatures at the valve location will remain 

within -40°F to +150°F (-40°C to +66°C).

Install Accessory Switches (If Needed)

A SPDT switch may be installed to operate an auxiliary load up 

to 1/2 hp (0.37 kW). The switch may be adjusted to operate at 

any point in the valve stroke.

A valve-closed indication switch may also be installed on any 

V4055 actuator to provide a valve seal overtravel interlock 

(valve-closed indication) when used with a V5055C or E valve 

(with double seal).

Fig. 2. V4055 actuator with cover removed.

NOTE: A V5055A, B or D valve can also be fitted with a bon-

net assembly with 2 seals to provide a valve seal 

overtravel interlock.

The SPDT valve-closed indication switch is installed to make 

or break a circuit when the valve is in the closed position. The 

switch is not adjustable.

NOTE: Mark the actuator or valve to indicate any changes 

made.

To install the switches, proceed as follows:

1.

Remove the actuator faceplate (2 screws).

2.

Remove the silver-colored barrier to expose the actuator 

stem.

3.

Insert the auxiliary switch in the position indicated in Fig. 

2. Fasten with 2 screws through the actuator base.

4.

Insert the valve-closed indication switch in the position 

shown in Fig. 2. The valve-closed indication switch 

mounts against the side of the actuator housing. The 

mounting holes are spaced to mount the switch only in 

the correct position. Fasten with 2 screws through the 

actuator base.

5.

If only 1 switch is used, install the narrow barrier included 

with the switch in the unused space.

6.

Mount the actuator before making wiring connections 

and adjustments to the switch.

M23961

133568

AUXILIARY

SWITCH

133569

VALVE-

CLOSED

INDICATION 

SWITCH

EACH SWITCH SECURED 

BY TWO SCREWS FROM

UNDERSIDE OF BASE

IF ONLY ONE SWITCH IS

USED, INSTALL BARRIER

IN OPEN POSITION

ADJUSTING SCREW

FOR AUXILIARY SWITCH

Summary of Contents for V4055F

Page 1: ...ow only when the gas valve is fully closed Ambient temperature rating of 40 F to 150 F 40 C to 66 C Valve and actuator may be mounted in any position Optional field adjustable spdt auxiliary switch rated at 112 hp 0 37 kW may be added in the field Standard enclosure meets NEMA 1 IP30 general purpose requirements Red light indicates when valve is ready to open Rocker switch allows manual operation ...

Page 2: ...0 Hz and 50 60 Hz models Mounting Means Actuator mounts directly to valve bonnet with 2 setscrews positioned 90 angular degrees apart Valve and actuator can be mounted in any position Mounting Dimensions See Fig 1 Replacement Parts 130928 Red Indicator Lamp Accessories 133568 Auxiliary Switch Bag Assembly 133569 Valve Closed Indication Switch Bag Assembly Approvals UL and FM IRI Approvable Electri...

Page 3: ...HOLES 8 ON 3 3 4 95 RADIUS M23960 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 VALVE SIZE INCH 13 1 8 13 1 8 13 1 8 13 1 8 13 1 4 13 3 4 13 3 4 16 3 16 333 5 333 5 333 5 333 5 336 5 349 0 349 0 411 0 2 3 4 2 3 4 2 3 4 2 3 4 2 7 8 3 3 8 3 3 8 5 13 16 70 0 70 0 70 0 70 0 73 0 85 5 85 5 128 0 8 3 16 8 3 16 8 3 16 8 3 16 8 5 16 8 13 16 8 13 16 11 7 32 208 0 208 0 208 0 208 0 211 1 224 0 224 0 285 0 5 3 4 5 3 4 5 3 4...

Page 4: ... seal Fig 2 V4055 actuator with cover removed NOTE A V5055A B or D valve can also be fitted with a bon net assembly with 2 seals to provide a valve seal overtravel interlock The SPDT valve closed indication switch is installed to make or break a circuit when the valve is in the closed position The switch is not adjustable NOTE Mark the actuator or valve to indicate any changes made To install the ...

Page 5: ...he installation is complete cycle the valve several times with the manual fuel shutoff cock closed before testing the system in actual operation Service The actuator is not field repairable except for replacing the auxiliary switch valve closed indication switch and READY TO OPEN light See INSTALLATION section for procedure Do not disassemble the valve actuator If the actuator should fail to opera...

Page 6: ...ds 12 Replace the damper crank arm assembly 13 Re attach the wires removed from the actuator terminals and turn on the electrical power 14 With the gas still off cycle the actuator to check for proper mechanical operation CAUTION Be sure to perform a bonnet seal and seat leak check after installation Be sure to read and follow all instructions that come with the actuators valves seal and bonnet ki...

Page 7: ...V4055F G FLUID POWER ACTUATOR WITH MANUAL CONTROL 7 65 0029 01 ...

Page 8: ... Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com V4055F G FLUID POWER ACTUATOR WITH MANUAL CONTROL U S Registered Trademark 2007 Honeywell International Inc 65 0029 01 M S Rev 06 07 ...

Reviews: