UVL-COIL ULTRAVIOLET LAMP KITS FOR AHU COILS

31-00402—02

6

Fig. 8. Installing UV Lamp.

Mount Power Supply(s)

Mount the power supply in a location (inside or outside of 
the HVAC system) that is convenient for access to the main 
power supply and for connection to the UV lamps. The 
power supply is weather resistant and is suitable for 
mounting inside or outside of the air handler.

Use the supplied self-taping sheet metal screws to mount 
the power supply in place through the mounting holes on 
the sides of the base. It is recommended to use wire boxes, 
cable strain relief fittings, or other sealing methods in order 
to pass the power cord and lamp cables into the interior of 
the air handler for connections.

Sight Glass Installation

The sight glass allows safe viewing of the UV light system 
when in operation. Find a suitable location such as a door 
to the HVAC system for the sight glass. Drill a 1” hole and 
press the base of the sight glass through it.

Fig. 9. Sight Glass Installation.

WIRING

WARNING

Electric Shock Hazard.
Can cause personal injury.

Turn off main power before making electrical 
connections.

Refer to electrical diagram (Fig. 10.) for proper connections 
of the power supply to the main power.

Fig. 10. Electrical Connections.

Connect Lamps and Cables

Arrange cables as needed for installation. If necessary, use 
cable strain relief fittings or other means to pass cables 
through the cabinets or air system walls. When UV lamps, 
power supplies, and cables are in place join the lamp and 
power supply cables by aligning the electrical pins and 
flanges on the rubber connectors and pushing them firmly 
together.

Fig. 11. Align Pins and Lamp Key.

MAINTENANCE

Honeywell UVC lights are made of Hard Quartz. Unlike Soft 
Quartz, these lamps do NOT need to be wiped of grease or 
other  contaminants, and are NOT affected by humidity. 
They are warranted for 2 years of UVC output, to 60% of 
their original output. Sizing guidelines are based on the 
end of lamp life output levels. 

Honeywell UV lamps are rated for two years germicidal 
effectiveness. The visible blue light will continue to 
illuminate, but does NOT have any germicidal 
effectiveness. Bulbs must be replaced on schedule for the 
system to function properly.

IMPORTANT

Use only Honeywell replacement lamps. Use of 
replacement lamps from other manufacturers 
voids the warranty. See Table 1
 for replacement 
lamp part numbers. 

UV Lamp

UV LAMP

UV LAMP

120-277 VAC

POWER SUPPLY

L1 BLACK

CONNECTORS

L2 or N WHITE

GND GREEN

Align Pins & Lamp Key

Push Firmly Together 

UV Lamp 

Power Supply 

Cable 

V Lamp 

Lamp Key

Summary of Contents for UVL-COIL-60D

Page 1: ...nside of air handlers or the exposed conditions of outdoor packaged air conditioning systems The number and placement of lamps is determined by the coil dimensions FEATURES UV C light irradiates coil air handler interior killing mold bacteria and viruses Scalable design allows wide variety of multi lamp configurations High quality water resistant lamps Mounts using off the shelf inch EMT conduit t...

Page 2: ...mm length UV C Power UVL 32 LAMP 28 W UVL 60 LAMP 54 W Output at 1 Meter UVL 32 LAMP 250 μW cm2 UVL 60 LAMP 395 μW cm2 Spectrum 100 254 nm Germicidal UV C Bulb Type Shielded Quartz Hot Filament Bulb Life 18 000 hours Accessories UVL 32 LAMP 32 inch replacement lamp UVL 60 LAMP 60 inch replacement lamp Table 1 Models Power supply not available for purchase outside of kit Part Number Description Rep...

Page 3: ...unting use optimal irradiation distance Fig 2 and lamp spacing Fig 3 diagrams to confirm than when installed the UV lamps will be positioned properly The UV lamps are mounted onto a framework of EMT tubing When two or more UV lamps are supported on a single length of EMT it is recommended to add an optional vertical support Fig 4 Table 2 Sizing Based on Coil Dimensions Table 3 Sizing Based on Unit...

Page 4: ...based on coil size WARNING Be careful of damage to equipment Ultraviolet light can cause color fading or degraded structure of plastic material found in HVAC equipment avoid plastic material or equipment with unknown performance against ultraviolet light in the area of irradiation WARNING UV Light Hazard Harmful to bare skin and eyes Can cause temporary or permanent loss of vision Do not look at t...

Page 5: ...h to the conduit tubing to support framework and prevents sagging on installations with three or more lamps per tubing length Measure the distance from floor to ceiling then measure and cut tubing 1 75 inches less than that length Use inch pipe coupling to extend the vertical support to the floor and ceiling for a snug fit Fig 7 Fig 7 Optional Vertical Support Install UV Lamps Snap UV Lamps into t...

Page 6: ...ower supply to the main power Fig 10 Electrical Connections Connect Lamps and Cables Arrange cables as needed for installation If necessary use cable strain relief fittings or other means to pass cables through the cabinets or air system walls When UV lamps power supplies and cables are in place join the lamp and power supply cables by aligning the electrical pins and flanges on the rubber connect...

Page 7: ...upply off then on 6 Install New UV Lamp s 7 Consult Factory UV Lamp s Flickering 1 UV Lamp s have reached end of effective service life Install new lamp s of same type 2 If unit is new check remote cables to ensure they are properly con nected 3 Reset power switch on power supply off then on 4 If new lamps still flicker consult factory UV Lamps Have burned Out Prematurely 1 Consult Factory Power S...

Page 8: ...well Building Technologies In the U S Honeywell 715 Peachtree Street NE Atlanta GA 30308 customer honeywell com buildingcontrols honeywell com U S Registered Trademark 2020 Honeywell International Inc 31 00402 02 M S Rev 09 20 Printed in United States ...

Reviews: