Rev. A
5
CSMU000835
09/15/03
2.2
MOUNTING THE CAMERA, CONTINUED
Setting dip
switches
5.
Several operation options and modes are selectable via
DIP switches. (Models CSC110BU/CSC110CU only.)
Option
Description
Pulse Counter
Controls the amount of pulses (either
1 or 3 pulse mode) that need to be
detected before the detector activates.
LED Indicator
Lights LED when movement is
detected. Only disable the LED
indicator after successfully walk
testing the detector.
Relay Operation
Selectable to Normally Open (N.O.)
or Normally Closed (N.C.). If one
side of relay grounding is required,
install the relay grounding jumper as
JP1.
Set the switches using the following information:
Option
Sw
ON
OFF
Pulse Counter
1
3 Pulse Mode
1 Pulse Mode
LED Indicator
2
LED ON
LED OFF
Relay Operation
3
Relay N.C.
Relay N.O.
6.
Attach the front cover.
7.
Connect the unit to a UL listed power supply or Ultrak
observation system.
2.3
WARM UP TIME
The detector will warm up for the first 90 seconds after
applying power.