Caractéristiques (suite)

Pression statique 

externe

Débit d’air fourni net

Débit d’air brut

Débit d’air fourni

Sortie

Pa

po c.e.

l/s

pi

3

/min

l/s

pi

3

/min

l/s

pi

3

/min

25

0.1

98

208

102

218

99

210

50

0.2

94

200

99

210

95

202

75

0.3

87

186

93

199

88

188

100

0.4

82

175

88

188

83

176

125

0.5

74

157

78

167

75

159

150

0.6

65

138

72

152

65

139

175

0.7

60

127

64

135

60

128

200

0.8

53

112

60

127

53

113

225

0.9

44

94

54

114

45

95

250

1

38

81

41

86

39

82

Performance du VNT5200E1000 en matière de ventilation

Performance du VNT5200E1000 en matière d’énergie

Température de l’air 

fourni

Débit d’air fourni net

Énergie 

moyenne

Efficacité de 

récupération 

sensible

Efficacité 

sensible 

apparente

°C

°F

l/s

pi

3

/min

Watts

%

%

Chauffa

g

e

0

32

35

74

75

58

69

0

32

50

106

100

51

66

0

32

70

149

126

44

64

-15

5

35

74

80

58

69

35

95

35

74

75

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0

50

100

150

200

250

0

25

50

75

100

125

150

175

200

0

10

20

30

40

50

60

70

80

90

100

110

MF32369

DÉBIT D’AIR (pi

3

/min)

VNT5200E1000

DÉBIT D’AIR (l/s)

PRESSION

STATQUE

EXTERNE

(Pa)

PRESSION

STATQUE

EXTERNE

(po c.e)

DÉBIT D’AIR FOURNI NET

Efficacité de récupération totale = 53%

Systèmes de ventilation VRÉ/VRC TrueFRESH™   69-2480EF—05

40

Summary of Contents for TrueFRESH ERV

Page 1: ...t Collars 4 Installation Kit Optional Controls 1 Vision Pro IAQ 2 True IAQ 3 Dehumidistat H8908D 4 Prestige IAQ 5 20 40 60 Minute Boost Control and 6 W8150 Ventilation Control A1 A2 B C G G5 G4 Tools required to install ERV HRV Aluminum foil tape UL181B Standard screwdriver Crescent wrench Hex driver 1 4 in Accessories not included 6 in diameter insulated duct 6 in diameter duct Two 6 in diameter ...

Page 2: ...ement de l appareil non conforme aux présentes instructions pourrait entraîner des dommages à l appareil lui même ou aux commandes INSTRUCTIONS POUR L INSTALLATION COMMEN CENT À LA PAGE 33 Installation Checklist Included in This Box A1 ERV HRV VNT5150H1000 or VNT5150E1000 or A2 ERV HRV VNT5200H1000 or VNT5200E1000 B Heat Energy Recovery Core C Filter 2 D Installation Guide E Duct Collars 4 F Insta...

Page 3: ... INSTALLATION continued Dehumidistat Wiring 23 W8150 Ventilation Control Wiring 23 Honeywell 20 40 60 Minute Boost Control Timer 23 Control Panel 24 Balancing Steps 25 Balancing Reset 26 Checkout 26 MAINTENANCE Periodic Maintenance 27 Cleaning 28 Troubleshooting 29 Parts List 30 WARRANTY 5 Year Limited Warranty 32 Prior to installing serious consideration must be taken to ensure this ventilation s...

Page 4: ...ion system for outdoor application Do not pull or twist power cord when disconnecting it from the ventilation system Grasp the plug firmly not the cord Do not modify the power plug in any way if modified risk of electric shock fire or even damage to the unit may occur Do not use the ventilation system for removal of flammable fumes gases or connect directly to any appliances Use a 120 VAC outlet o...

Page 5: ...ove chart outlines the minimum requirements for continuous ventilation Room Count Calculation Method Living Space Number of Rooms x CFM or L s CFM Required Master Bedroom x 20 cfm or 10 L s Basement x 20 cfm or 10 L s Single bedroom x 10 cfm or 5 L s Living Room x 10 cfm or 5 L s Dining Room x 10 cfm or 5 L s Family Room x 10 cfm or 5 L s Recreation Room x 10 cfm or 5 L s Other x 10 cfm or 5 L s K...

Page 6: ...0H1000 or VNT5150E1000 H 22 1 2 in 572 mm W 11 1 2 in 295 mm L 29 1 2 in 749 mm VNT5200H1000 or VNT5200E1000 H 22 1 2 in 572 mm W 16 1 2 in 422 mm L 29 1 2 in 749 mm FRONT CLEARANCE OF 25 INCHES 635 MM IS REQUIRED FOR SERVICING UNIT ALL DUCT CONNECTIONS ARE 6 IN 150 MM 2 1 H W L 1 2 M28919 TrueFRESH ERV HRV Ventilation Systems 69 2480EF 05 4 Drain tubing diameter 1 2 in 12 7 mm Flexible Duct 2 6 i...

Page 7: ...38 80 34 73 Supply Temperature Net Supply Air Flow Average Power Sensible Recovery Apparent Sensible C F L s CFM Watts Efficiency Effectiveness Heating 0 32 31 66 88 66 78 0 32 42 89 104 64 76 0 32 56 119 114 63 72 25 13 32 67 86 59 77 VNT5150H1000 Ventilation Performance VNT5150H1000 Energy Performance TrueFRESH ERV HRV Ventilation Systems 69 2480EF 05 5 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 50 100...

Page 8: ... 40 86 Supply Temperature Net Supply Air Flow Average Power Sensible Recovery Apparent Sensible C F L s CFM Watts Efficiency Effectiveness Heating 0 32 55 118 106 61 71 0 32 75 160 132 58 65 0 32 87 185 150 55 62 25 13 57 120 105 58 72 VNT5200H1000 Ventilation Performance VNT5200H1000 Energy Performance TrueFRESH ERV HRV Ventilation Systems 69 2480EF 05 6 VNT5200H1000 AIR FLOW L S 0 0 1 0 2 0 3 0 ...

Page 9: ...erature Net Supply Air Flow Average Power Sensible Recovery Apparent Sensible C F L s CFM Watts Efficiency Effectiveness Heating 0 32 30 64 75 52 67 0 32 45 96 100 44 64 0 32 55 117 126 40 62 15 5 30 64 80 52 67 35 95 30 64 75 VNT5150E1000 Ventilation Performance VNT5150E1000 Energy Performance Total Recovery Efficiency 49 TrueFRESH ERV HRV Ventilation Systems 69 2480EF 05 7 VNT5150E1000 AIR FLOW ...

Page 10: ... Ventilation Performance VNT5200E1000 Energy Performance Supply Temperature Net Supply Air Flow Average Power Sensible Recovery Apparent Sensible C F L s CFM Watts Efficiency Effectiveness Heating 0 32 35 74 75 58 69 0 32 50 106 100 51 66 0 32 70 149 126 44 64 15 5 35 74 80 58 69 35 95 35 74 75 Total Recovery Efficiency 53 TrueFRESH ERV HRV Ventilation Systems 69 2480EF 05 8 0 0 0 1 0 2 0 3 0 4 0 ...

Page 11: ...ervice reminders Controls other indoor air quality equipment Manual Dehumidistat H8908DSPST and Automatic Ventilation Controls W8150A1000 Manual humidity control with intuitive comfort settings Automatic W8150 ventilation control to ASHRAE standard or for continuous operation The ERV HRV unit may be used with one of the following external controls Prestige YTHX9321R5012 and Prestige IAQ Comfort Sy...

Page 12: ...al applications only Must be installed in accordance with all national and local regulations building and safety codes Flex duct is recommended for connecting to the ERV HRV collars to reduce vibration noise M24745 Electrical Requirements 120 VAC outlet Ground fault interrupter GFI and dedicated circuit recommended This application uses a devoted duct system for the supply and the exhausting of st...

Page 13: ...rced air system s manufacturer The forced air system s blower does not have to run when the unit is operating but is recommended for maximum effectiveness NOTE For the minimum distance between the fresh air connection and the forced air system check with your local building codes and forced air system manufacturer NOTE For dwellings with multiple forced air systems Honeywell recommends one ERV HRV...

Page 14: ...eck with your local code or the forced air system s manufacturer NOTE For minimum distance between return and forced air system check with your local building codes and forced air system manufacturer NOTE Fresh air must always be down stream from the exhaust air in the return air duct of the forced air system NOTE Furnace blower is required to operate when ventilation is required Set the furnace b...

Page 15: ...ortant to install an electric receptacle 120 Vac near the unit a separate circuit breaker is also recommended It is best to have access to a condensate drain near the ERV HRV unit to avoid having to use a condensate pump NOTE Installation is not recommended in unconditioned areas such as an attic or crawl space where the temperature can fall below 32 ºF 0 ºC NOTE Ducting in unconditioned areas mus...

Page 16: ...es you to save time and effort by offering a simplified hanging system NOTE If the unit is not level improper drainage will occur and could lead to moisture and leakage problems 2 Pull on middle of strap while gently lifting unit upward to raise the unit 3 Make final adjustments to ensure that the HRV ERV is level TIP Removing the core unit makes installation easier since the unit weighs less with...

Page 17: ...lated flex 1 Insert the vinyl duct over the hooks on the duct collar and seal with a supplied 30 inch tie wrap 2 Insert insulation inside the outer ring of the duct collar 3 Finish by taping the duct on the collar 4 Slide collar onto unit TIP Attach the flex duct to the collar first and then attach the collar to the unit 5 Secure collar with the supplied 5 8 in hex head screws IMPORTANT Always fix...

Page 18: ...a condensate pump if you don t have access to the floor drain Drainless Application NOTE If installing an ERV unit VNT5150E1000 or VNT5200E1000 in a region where the outdoor temperature does not drop below freezing the condensate drain line does not need to be installed and the unit may be installed as a drainless application 1 Insert the threaded drain adapter through the bottom of the ERV with t...

Page 19: ...sion cord Ensure that the receptacle s polarization is correct NOTE If the LED light on the ERV HRV control panel remains green the motors do not energize and the controls do not operate this can indicate that the polarization in the main AC outlet is inverted IMPORTANT Always consult a qualified technician to ensure proper installation of main power Installing outside hoods for the fresh air and ...

Page 20: ...ll increase and will operate at maximum speed when the outdoor temperature is 4 F 20 C or less Defrost cycle runs for 4 minutes with the supply fan off followed by 40 minutes of continuous normal operation Defrost cycles will continue to repeat as long as the temperature is 23 F 5 C or less TrueFRESH ERV HRV Ventilation Systems 69 2480EF 05 18 M28986 The wiring terminal block is located behind the...

Page 21: ... a ventilation call from a wall control turns it on in high speed TrueFRESH ERV HRV Ventilation Systems 69 2480EF 05 19 Wiring continued Controls Wiring M28987 SENSOR TYPE C R SENSORS W2 W Y W3 G Y2 U3 L U3 U3 U2 U1 U1 RC RH R C S2 S2 S1 S1 IAQ DEVICE 24 VAC TO THERMOSTAT EQUIPMENT IAQ CONTROL 24 V POWER THM5421R OR OR OR CONV Follow this diagram if using a Prestige 2 wire IAQ and RF EIM ...

Page 22: ...NTILATOR M28988 NOT USED NOT USED C Rc R U1 U1 U2 U2 C Rc R U1 U1 U2 U2 U1 U1 Configurable IAQ relay for humidifier dehumidifier or vent U2 U2 Configurable IAQ relay for humidifier dehumidifier or vent Follow this diagram if using a Prestige Thermostat Interlock not shown VisionPRO IAQ Equipment Interface Module M28989 H1 M2 D1 M2 V1 T2 U H N OR ...

Page 23: ...AT COOL thermostat with ventilation contacts could use a different wall control for ventilator ERV HRV is used in conjunction with a conventional HEAT COOL thermostat or other wall control Follow this diagram for General Ventilator Wiring FURNACE 24 VOLT TERMINAL BLOCK POWERED VENTILATOR R W G Y C R W G Y THERMOSTAT VENTILATION CONTACTS M28990 M28991 C Y W G R Y W G R FURNACE 24 VOLT TERMINAL BLOC...

Page 24: ...e the G and Y terminals are coupled together in the thermostat fan and cool are simultaneously energized This wiring method will prevent turning on the cooling system when the ventilator turns on the furnace fan NOTE Only use this wiring method for systems where G and Y are coupled at the thermostat OLDER STYLE THERMOSTAT FAN G COOL Y ARE COUPLED FORCED AIR SYSTEM FURNACE 24 VOLT TERMINAL BLOCK FA...

Page 25: ...5 23 Follow this diagram if using the Honeywell 20 40 60 Minute Boost Control Timer Follow this diagram if using a Dehumidistat M28994 M28996 B G R Follow this diagram if using a W8150 Ventilation Control M28995 FAN TIMER EARD 6 AT120 XFMR W8150A DAMPER C R AUX REMOTE ...

Page 26: ...y control OFF When the selector switch is in the off position the unit will not operate even when there s a call for ventilation by an external control and buttons Used to adjust the continous speed setting Speed Control used as a Balancing Control In balancing mode the LED indicator is yellow and the selector switch functions as a Balancing Control to set the high speed of the motors for balancin...

Page 27: ...Left motor fresh air a Use a pitot tube or flow station to measure the air flow in the fresh air duct and exhaust air duct b Move the mode selector switch to adjust the air flow in the duct with the higher reading INTER Exhaust air right OFF Fresh air left c Press the or buttons to adjust the air flow to the desired high speed setting d Move the mode selector switch to the CONT position to proport...

Page 28: ...ion and the external controls to the desired settings Inspect the ducting to ensure that there are no kinks and correct as necessary LED 3 POSITION SELECTOR SWITCH SPEED CONTROL BUTTONS AND Speed Control Open for Instructions M32371 NOTE Once balancing is completed balancing cannot be changed without resetting the unit To reset 1 Press the and buttons simultaneously for 10 seconds 2 Indicator ligh...

Page 29: ...en spray rinse and let dry Filters Four times per year or as needed vacuum the filters Replace filters as needed 1 Inside the Unit Once a year or as needed clean the interior of the unit walls and drain pan with a mild and non abrasive soap It is recommended to use products that are environmentally friendly 2 Energy Recovery Core Unit VNT5150E1000 and VNT5200E1000 Once a year or as needed vacuum t...

Page 30: ...ring the panel to its fully open position Remove both filters from the top left and right sides of the Core then vacuum both filters Slide out the Core and clean according to the instructions on the previous page 3 Clean inside of unit with a damp cloth and wipe dry when finished 4 Replace the Core and the two filters re latch the side panel then reconnect the AC power to the unit Cleaning Steps ...

Page 31: ... dryer is vented to the outdoors 3 Wait for outside temperature to change For example it can be very humid at times in the summer 4 Verify balancing of the ERV HRV unit see Balancing Steps on page 25 LED on control panel remains green If the LED light on the ERV HRV control panel remains green the motors do not energize and the controls do not operate This can indicate that the Polarization in the...

Page 32: ...0053952 014 Latch Hinge Kit 5 50053952 011 Condensation Drain Fitting Kit 6 50053952 009 Adjustable Hanging Straps set 7 50053952 008 6 diameter Plastic Keeper 8 50053952 007 6 diameter Plastic Double Collar 9 50053952 012 Replacement LVC electronic board speed control 10 50053952 013 Replacement HVC electronic board 11 50053952 015 Front Access Door Honeywell OS List Honeywell OS Number Controls ...

Page 33: ...tion TrueFRESH ERV HRV Ventilation Systems 69 2480EF 05 31 3 11 2 9 8 7 6 4 5 1 10 3 4 M28997 See the Parts List table on page 30 for items referenced by figure numbers 1 through 11 in the exploded illustration below ...

Page 34: ...is shown by Honeywell that the defect or malfunction was caused by damage which occurred while the product was in the possession of a consumer Honeywell s sole responsibility shall be to repair or replace the product within the terms stated above HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ...

Page 35: ...distat H8908D 55 Câblage du régulateur de ventilation W8150 55 Commande de minuterie de ventilation à haute vitesse pour 20 40 ou 60 minutes 55 Panneau de commande 56 Procédure d équilibrage 57 Réinitialisation de l équilibrage 58 Vérification 58 ENTRETIEN Entretien périodique 59 Nettoyage 60 Dépannage 61 Liste des pièces 62 GARANTIE Garantie limitée de 5 ans 64 Avant l installation plusieurs élém...

Page 36: ...un usage à l intérieur seulement Ne tirez ni ne tordez le cordon d alimentation lorsque vous débranchez ce dernier du système de ventilation Saisissez fermement la fiche et non le cordon d alimentation Pour éviter les risques de décharge électrique d incendie et de dommages à l appareil ne modifiez pas la fiche N utilisez pas cet appareil pour l évacuation de gaz ou de vapeurs inflammables et ne l...

Page 37: ...ontinue Méthode d évaluation des besoins en matière de ventilation selon le nombre de pièces Espaces habités Nombre de pièces x l s ou pi3 min l s nécessaires Chambre à coucher principale x 10 l s ou 20 pi3 min Sous sol x 10 l s ou 20 pi3 min Chambre secondaire x 5 l s ou 10 pi3 min Salon x 5 l s ou 10 pi3 min Salle à manger x 5 l s ou 10 pi3 min Salle familiale x 5 l s ou 10 pi3 min Salle de jeu ...

Page 38: ...000 H 572 mm 22 50 po W 295 mm 11 50 po L 749 mm 29 50 po VNT5200H1000 ou VNT5200E1000 H 572 mm 22 50 po W 422 mm 16 50 po L 749 mm 29 50 po UN DÉGAGEMENT DE 635 MM 25 PO EST NÉCESSAIRE DEVANT L APPAREIL POUR SON ENTRETIEN TOUS LES RACCORDS DE CONDUIT ONT UN DIAMÈTRE DE 150 MM 6 PO 2 1 MF28919 H W L 1 2 Systèmes de ventilation VRÉ VRC TrueFRESH 69 2480EF 05 36 Diamètre du drain de condensation 12 ...

Page 39: ...e l air fourni Débit d air fourni net Énergie moyenne Efficacité de récupération sensible Efficacité sensible apparente C F l s pi3 min Watts Chauffage 0 32 31 66 88 66 78 0 32 42 89 104 64 76 0 32 56 119 114 63 72 25 13 32 67 86 59 77 Performance du VNT5150H1000 en matière de ventilation Performance du VNT5150H1000 en matière d énergie 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 50 100 150 200 250 0 25 5...

Page 40: ...ir fourni Débit d air fourni net Énergie moyenne Efficacité de récupération sensible Efficacité sensible apparente C F l s pi3 min Watts Chauffage 0 32 55 118 106 61 71 0 32 75 160 132 58 65 0 32 87 185 150 55 62 25 13 57 120 105 58 72 Performance du VNT5200H1000 en matière de ventilation Performance du VNT5200H1000 en matière d énergie 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 50 100 150 200 250 300 0 ...

Page 41: ...fourni net Énergie moyenne Efficacité de récupération sensible Efficacité sensible apparente C F l s pi3 min Watts Chauffage 0 32 30 64 75 52 67 0 32 45 96 100 44 64 0 32 55 117 126 40 62 15 5 30 64 80 52 67 35 95 30 64 75 Performance du VNT5150E1000 en matière de ventilation Performance du VNT5150E1000 en matière d énergie MF32370 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 50 100 150 200 250 0 25 50 7...

Page 42: ... ventilation Performance du VNT5200E1000 en matière d énergie Température de l air fourni Débit d air fourni net Énergie moyenne Efficacité de récupération sensible Efficacité sensible apparente C F l s pi3 min Watts Chauffage 0 32 35 74 75 58 69 0 32 50 106 100 51 66 0 32 70 149 126 44 64 15 5 35 74 80 58 69 35 95 35 74 75 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 50 100 150 200 250 0 25 50 75 100 12...

Page 43: ...tion Peut aussi servir à commander d autres appareils de régulation de la qualité de l air ambiant Déshumidistat manuel H8908DSPST et régulateur de ventilateur automatique W8150A1000 Régulation manuelle de l humidité selon des points de consigne intuitifs Régulateur W8150 assurant la régulation automatique de la ventilation selon le code de l industrie ASHRAE ou fonctionnant en continu Le VRE VRC ...

Page 44: ...ux codes du bâtiment et aux codes de sécurité nationaux et locaux Il est recommandé de fixer des gaines flexibles aux raccords de conduit du VRE VRC afin de réduire le bruit causé par les vibrations M24745 Exigences relatives au système électrique Prise V c a Un disjoncteur différentiel et un circuit réservé sont recommandés Cette application est fondée sur l utilisation d un système de conduits d...

Page 45: ...du fabricant du système à air pulsé Pour une efficacité maximale il est recommandé de faire fonctionner la soufflante du système à air pulsé en même temps que le VRE VRC REMARQUE Pour connaître la distance minimale nécessaire entre le raccord d air frais et le système à air pulsé consultez les codes du bâtiment locaux et le fabricant du système à air pulsé REMARQUE Dans les habitations comportant ...

Page 46: ...ur connaître la distance minimale nécessaire entre le conduit de retour d air et le système à air pulsé consultez les codes du bâtiment locaux et le fabricant du système à air pulsé REMARQUE L apport d air doit toujours être en aval de l air vicié dans le conduit de retour d air du système à air pulsé REMARQUE La soufflante de l appareil de chauffage doit fonctionner en même temps que le système d...

Page 47: ...able que ce dernier soit protégé par un disjoncteur séparé Il est préférable d installer le VRE VRC à proximité d un tuyau d évacuation de condensation de sorte que vous n ayez pas à recourir à une pompe à condensation REMARQUE Il n est pas recommandé d installer l appareil dans un endroit non climatisé comme un grenier ou un vide sanitaire où la température peut descendre sous 0 ºC 32 ºF REMARQUE...

Page 48: ...mplifié du VRE VRC permet une installation rapide et facile REMARQUE Si l appareil n est pas de niveau son drainage pourrait ne pas être adéquat ce qui entraînerait des fuites et des problèmes liés à l humidité 2 Tirez le milieu de la courroie tout en soulevant doucement l appareil 3 Pour terminer effectuez les ajustements nécessaires pour mettre l appareil de niveau CONSEIL Le fait de retirer le ...

Page 49: ... raccord de conduit et scellez le tout à l aide de l une des attaches autobloquantes de 76 20 cm 30 po fournies 2 Insérez l isolant à l intérieur de l anneau extérieur du raccord de conduit 3 Pour terminer fixez la gaine au raccord à l aide de ruban à conduits 4 Glissez le raccord sur l appareil CONSEIL Fixez d abord la gaine flexible au raccord de conduit puis le raccord à l appareil 5 Fixez le r...

Page 50: ...s au siphon de sol utilisez une pompe à condensation Application sans vidange REMARQUE Si vous installez un VRE VNT5150E1000 ou VNT5200E1000 dans une région ou la température extérieure n est jamais inférieure au point de congélation il est inutile d installer un tuyau d évacuation de condensation l appareil peut donc être installé sans vidange 1 Insérez l adaptateur de tuyau d évacuation fileté s...

Page 51: ...larité de la prise est adéquate REMARQUE Si le voyant DEL du panneau de commande du VRE VRC demeure vert les moteurs ne se chargent pas et les commandes ne fonctionnent pas cette situation pourrait être causée par une inversion de la polarité de la prise c a IMPORTANT Pour une installation adéquate de l alimentation électrique principale faites appel à un technicien qualifié Installation de hottes...

Page 52: ...mpérature extérieure est de 20 C 4 F ou moins Le cycle de dégivrage dure 4 minutes pendant lesquelles le ventilateur d air frais est éteint et est suivi de 40 minutes de ventilation continue La fonction de dégivrage continuera de se mettre en marche périodiquement tant que la température extérieure sera de 5 C 23 F ou moins Systèmes de ventilation VRÉ VRC TrueFRESH 69 2480EF 05 50 M28986 La bloc d...

Page 53: ...arche en haute vitesse à partir d une commande murale Systèmes de ventilation VRÉ VRC TrueFRESH 69 2480EF 05 51 Câblage suite Câblage des commandes à distance MF28987 SENSOR TYPE C R SENSORS W2 W Y W3 G Y2 U3 L U3 U3 U2 U1 U1 RC RH R C S2 S2 S1 S1 IAQ DEVICE 24 VAC TO THERMOSTAT EQUIPMENT IAQ CONTROL 24 V POWER THM5421R OR OR OR CONV Suivez ce schéma si vous utilisez un module d interface d équipe...

Page 54: ...AQ QUALITÉ DE L AIR AMBIANT CONFIGURABLE POUR HUMIDIFICATEUR DÉSHUMIDIFICATEUR OU ÉVENT U2 U2 RELAIS IAQ QUALITÉ DE L AIR AMBIANT CONFIGURABLE POUR HUMIDIFICATEUR DÉSHUMIDIFICATEUR OU ÉVENT THERMOSTAT PRESTIGE ALIMENTATION DU VENTILATEUR Suivez ce schéma si vous utilisez un thermostat Prestige verrouillage non représenté H1 M2 D1 M2 V1 T2 U H N OR MF28989 Module d interface d équipement VisionPRO ...

Page 55: ...liser une autre commande murale pour le ventilateur Le VRE VRC est utilisé de concert avec un thermostat à commande de chauffage et de refroidissement classique ou un autre type de commande murale Suivez ce schéma pour le câblage général du ventilateur R W G Y C R W G Y BLOC DE RACCORD 24 VOLTS POUR L APPAREIL DE CHAUFFAGE ALIMENTATION DU VENTILATEUR THERMOSTAT CONTACTS DE VENTILATION MF28990 BLOC...

Page 56: ...t d éviter l activation du refroidissement lorsque le système actionne le ventilateur de l appareil de chauffage REMARQUE N utilisez cette méthode de câblage que pour un système où G et Y sont couplées dans le thermostat MF28993 VENT VENT TrueIAQ DÉSHUM DÉSHUM Suivez ce schéma pour l autre option de raccord au système à air pulsé MF28992 C Y W G R Y W G R L ANCIEN MODÈLE DE VENTILATEUR AVEC THERMO...

Page 57: ...ma si vous utilisez la minuterie Honeywell pour la ventilation à haute vitesse 20 40 ou 60 minutes Suivez ce schéma si vous utilisez un déshumidistat M28994 M28996 B G R Suivez ce schéma si vous utilisez un régulateur W8150 MF28995 MINUTERIE EARD 6 AT120 XFMR W8150A DAMPER C R AUX REMOTE ...

Page 58: ...OFF l appareil ne fonctionne pas et ne peut être mis en marche par une commande externe Boutons et S utilisent pour régler la vitesse au mode de fonctionnement continu Réglage de la vitesse et mode équilibrage Au mode équilibrage le voyant DEL est jaune et le sélecteur change de fonction et règle la vitesse des deux moteurs aux fins d équilibrage du débit d air air frais et air vicié Les trois typ...

Page 59: ...uation de l air b Déplacer le sélecteur pour régler le débit dans le conduit présentant le résultat le plus élevé INTER air vicié droit OFF arrêt air frais gauche c Appuyez sur les boutons ou pour régler le débit d air à la valeur souhaitée pour le régime haute vitesse d Déplacez le sélecteur à la position CONT pour régler la vitesse relative des deux moteurs CONDUIT D AIR FRAIS GAUCHE CONDUIT D A...

Page 60: ...sition désirée et réglez les commandes externes aux paramètres souhaités Assurez vous qu aucun conduit n est entortillé REMARQUE L appareil doit être réinitialisé avant chaque nouvelle procédure d équilibrage Réinitialisation 1 Appuyez simultanément sur les touches et pendant 10 secondes 2 Le voyant deviendra jaune après 5 secondes 3 Le voyant deviendra vert après 10 secondes 4 Relâchez les deux b...

Page 61: ...au et laissez les sécher Filtres Nettoyez les filtres à l aide d un aspirateur quatre fois par année ou au besoin Remplacez les filtres au besoin 1 Intérieur de l appareil Une fois par an ou au besoin nettoyez l intérieur de l appareil parois et bac à récupération avec un savon doux non abrasif L utilisation de produits respectueux de l environnement est recommandée 2 Système de ventilation à récu...

Page 62: ... ce qu il soit complètement ouvert Retirez les deux filtres situés en haut à gauche et à droite du noyau puis nettoyez les à l aide d un aspirateur Faites glisser le noyau vers l extérieur et nettoyez le en suivant les directives des pages précédentes 3 Nettoyez l intérieur de l appareil avec un linge humide et essuyez le une fois que vous avez terminé 4 Replacez le noyau et les deux filtres rever...

Page 63: ...ué vers l extérieur de la maison 3 Attendez que les conditions climatiques changent L air peut être très humide durant l été par exemple 4 Vérifiez l équilibrage de votre appareil VRE VRC reportez vous à la procédure d équilibrage à la page 57 Les voyants DEL du panneau de commande restent verts Quand le voyant DEL sur le panneau de commande de votre VRE VRC reste vert les moteurs ne sont pas sous...

Page 64: ...ières et loquets 5 50053952 011 Trousse pour raccord d évacuation de la condensation 6 50053952 009 Courroies de suspension réglables jeu 7 50053952 008 Conduit de collet en plastique de 6 po de diamètre 8 50053952 007 Double collet en plastique de 6 po de diamètre 9 50053952 012 Carte électronique basse tension de rechange commande de la vitesse 10 50053952 013 Carte électronique haute tension de...

Page 65: ... de ventilation VRÉ VRC TrueFRESH 69 2480EF 05 63 3 11 2 9 8 7 6 4 5 1 10 3 4 M28997 Voir le tableau Liste des pièces à la page 62 les articles sont référencés par numéros 1 à 11 correspondant aux numéros de la vue éclatée ci dessous ...

Page 66: ...Systèmes de ventilation VRÉ VRC TrueFRESH 69 2480EF 05 64 ...

Page 67: ...Systèmes de ventilation VRÉ VRC TrueFRESH 69 2480EF 05 65 ...

Page 68: ...roduit était en la possession d un consommateur La responsabilité de Honeywell se limite à réparer ou à remplacer le produit sous réserve des conditions énoncées ci dessus HONEYWELL NE SAURAIT EN AUCUN CAS ÊTRE TENUE RESPONSABLE DES PERTES NI DES DOMMAGES Y COMPRIS LES DOMMAGES ACCESSOIRES OU CONSÉCUTIFS DÉCOULANT DIRECTEMENT OU INDIRECTEMENT D UN MANQUEMENT À TOUTE GARANTIE EXPLICITE OU IMPLICITE...

Reviews: