background image

1

60-1227—1

S. M.  •  Rev. 6-93  •           •  ©Honeywell Inc. 1993  •  Form Number 60-1227—1

T874A-F Multistage Thermostats

with Restricted Set Point

Q674A-E,G Subbases

Installation Instructions for the Trained Service Technician.

Application

The T874A-F Thermostats provide 24 to 30 Vac control

for heating and/or cooling systems. See Tables 1 and 2.

TABLE 1—HEATING AND/OR COOLING STAGES.

T874

A

B

C

D

E

F

Heating Stages

1

1

2

2

2

Cooling Stages

1

2

1

2

2

The Q674A-E,G Subbases provide wiring terminals,

system and fan switching, and mounting bases for T874
Multistage Thermostats.

TABLE 2—SWITCHING POSITIONS.

Q674

Switch Positions

Model

System

Fan

A

Heat-Auto-Cool

Auto-On

B

Heat-Off-Cool

Auto-On

C

Off-Auto

Auto-On

D

None

None

E

Off-Heat-Auto-Cool

Auto-On

G

Off-Auto

None

Operation

On a 2-heat thermostat, the two stages of heat make

sequentially as the temperature drops. Make refers to the
mercury switch initiating a call for heat or cool.

There are about 2

°

 F [1

°

 C] between stages so that the

second stage makes only when the first stage can not
handle the load. This is the interstage differential.

The LED indicators are light emitting diodes on the

subbase that light when something specific happens with-
in the system.

Up to four of the LEDs listed below may be included on

your subbase. When an LED lights, refer to the following
list for the meaning:

FILTER: Clogged filter needs replacement.

EM. HT.: Emergency heat is operating. The compres-

sor has failed, and the heat pump is not operating.
LED lights when system switch is placed in the EM.
HT. position.

AUX. HT.: Auxiliary heat is operating, which means the

weather is so cold that the heat pump can not handle
the load alone.

LOCKOUT: System is shut down and needs maintenance.
CHECK: System needs to be checked. See heating sys-

tem instructions for specific meaning.

SERVICE: See heating system instructions for specific

meaning.

LEDs are not field replaceable.

M3375

Recycling Notice

This control contains mercury in a sealed tube. Do not

place control in the trash at the end of its useful life.

If this control is replacing a control that contains mercury

in a sealed tube, do not place your old control in the trash.

Contact your local waste management authority for

instructions regarding recycling and the proper disposal of
this control, or of an old control containing mercury in a
sealed tube.

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to fol-

low them could damage the product or cause a hazardous
condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for your
application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out the product

operation as provided in these instructions.

M3375

Summary of Contents for Tradeline T874A-F

Page 1: ...ights refer to the following list for the meaning FILTER Clogged filter needs replacement EM HT Emergency heat is operating The compres sor has failed and the heat pump is not operating LED lights when system switch is placed in the EM HT position AUX HT Auxiliary heat is operating which means the weather is so cold that the heat pump can not handle the load alone LOCKOUT Systemisshutdownandneedsm...

Page 2: ...al outlet box The horizontal outlet box requires placing the subbase on the box and tightening two mount ing screws For a wall installation hold the subbase in position and mark the holes for the anchors See Fig 2 Obtain wall anchors locally Be careful that the wires do not fall back into the wall opening Set subbase aside Drill two 3 16 in 5 mm holes and gently tap anchors into the holes until fl...

Page 3: ... as possible to the subbase Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to pre vent drafts from affecting the thermostat Fig 4 Wiring connections M932A 1 2 3 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC RH FOR SINGLE TRANSFORMER OPTIONAL CHECK LITE ON SOME MODELS COMPRESSOR CONTACTOR 1 H2 ANTICIPATOR C1 C1 ANTICIPATOR C2 H...

Page 4: ...T RELAY 1 HEAT RELAY 2 FALL L1 HOT 1 L2 RH W1 W2 B FALL H2 AUTO ON FAN SWITCH 3 2 2 Fig 7 T874D Q674C in standard heating cooling system M933A 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC AND RH FOR SINGLE TRANSFORMER SYSTEMS OPTIONAL LIGHT ON SOME MODELS COMPRESSOR CONTACTOR 1 H2 ANTICIPATOR C1 C1 ANTICIPATOR C2 H1 ANTICIPATOR H1 HEAT DAMPER OR CHANGEOVE...

Page 5: ... Y2 Y1 L1 HOT L2 RC FALL H2 RISE C2 ANTICIPATOR RISE NO FAN SWITCH NO SYSTEM SWITCH W1 B 1 1 3 2 3 2 Fig 9 T874D Q674E in standard heating cooling system M934 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC RH FOR SINGLE TRANSFORMER COMPRESSOR CONTACTOR 1 H2 ANTICIPATOR C1 C1 ANTICIPATOR C2 H1 ANTICIPATOR H1 HEAT RELAY 1 HEAT RELAY 2 COMPRESSOR CONTACTOR 2 F...

Page 6: ... ANTICIPATOR Fig 11 Typical Q674 terminal designations The thermostat used determines the number of connections STAGE 1 HEATING RELAY HEATING DAMPER MOTOR OR CHANGEOVER VALVE STAGE 2 HEATING RELAY STAGE 3 HEATING RELAY CLOGGED FILTER SWITCH SYSTEM MONITOR OUTDOOR THERMISTOR EMERGENCY HEAT RELAY LED STAGE 1 COOLING RELAY STAGE 2 COOLING RELAY COOLING FAN RELAY COIL COOLING DAMPER MOTOR OR CHANGEOVE...

Page 7: ...F 2 C The T874 is equipped with a restricted set point feature for fuel efficiency Factory installed stops are set so the set point levers cannot be set above 68 F 20 C or 72 F 22 C on heating depending on the model or below 78 F 26 C on cooling Fig 12 Do not attempt to change the location of these stops because they are nonadjustable SUBBASE SETTING System switching positions control thermostat o...

Page 8: ...il it clears the locking springs 2 Set the cover on a table near an accurate thermometer 3 After allowing five or ten minutes for stabilization compare the readings If they are the same replace the cover and put the system into operation If they are differ ent recalibrate the thermostat thermometer see step 4 4 Insert a small screwdriver in the thermometer shaft Fig 13 and turn it until the thermo...

Reviews: