T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
5
62-0125—3
Deadband.
30
2
Heating and cooling
setpoints can be set no
closer than 2°F
(1.1°C).
3 thru
10
Heating and cooling
setpoints can be set no
closer than the chosen
value:
3—3°F (1.7°C)
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
Interstage
control point
(Q7300C,D
only).
31 0
Disabled.
1
thru
12
Temperature has to change
more than the chosen
value before the system
calls for the next stage.
(Example: 68°F (20°C) is
the heat setpoint, 2°F
(1.1°C) is the interstage
setting, temperature is
65.5°F (18.5°C), the
second stage turns on,
brings the temperature to
66°F (19°C) and turns off.
The heat pump continues
to run until the setpoint is
met.)
Minimum on-
time.
32
2
2-minute minimum on-
time for heating and
cooling.
0 or 1
No minimum on-time or
1-minute minimum on-time
for heating and cooling.
Minimum off-
time for the
compressor.
33
4
4-minute minimum off-
time for the
compressor.
0, 1, 2,
3 or 5
Minimum number of
minutes (0 thru 5) the
compressor will be off
between calls for the
compressor.
Temperature
range stops in
heating.
34
90
Highest setpoint for
heating.
40 to 89 Temperature range (1°F
[0.6°C] increments) for
heating setpoint.
Temperature
range stops in
cooling.
35
45
Lowest setpoint for
cooling.
46 to 99 Temperature range (1°F
[0.6°C] increments) for
cooling setpoint.
Not used.
36
—
—
—
—
—
Table 2. Thermostat Installer Setup Options (Continued)
Select
Installer Setup
Number
(Press
Unoccupied
Temp Key to
change)
Factory Setting
Other Choices
(Press
∆
or
∇
key to change)
Actual
Setting
Display
Description
Display
Description
a
Number 2 must be set to 1 to extend fan operation.
b
Number 22 must be set to 1 and remote sensor(s) must be installed.