69-0617—1

CHECK CAD CELL

1. Disconnect power at system switch, circuit breaker or

fuse.

2. Clean cell face with soft cloth.
3. Make sure cell is seated securely in socket. Be careful

not to disturb socket position.

4. Reconnect cad cell leads to F-F terminals.
5. Reset safety switch, turn on power and set thermostat

TRIP SAFETY SWITCH BEFORE PERFORMING
BURNER MAINTENANCE

CAUTION

Tripping the safety switch shuts down the burner but
does not disconnect the power supply. Turn off power
at system switch or circuit breaker before servicing
the control system, burner motor, oil valve or ignition
to avoid electric shock.

To trip the safety switch, move the safety switch lever

down until the red reset button pops out and the indicator
light comes on. See Fig. 5. Burner will not operate until
safety switch is reset by pushing in the red reset button.

Fig. 4—Move lever down to trip safety switch.

PUSH LEVER DOWN 
TO TRIP SAFETY SWITCH

WHEN SAFETY SWITCH TRIPS

INDICATOR LIGHT COMES ON
(TRADELINE ONLY)

RESET BUTTON POPS OUT

M17882

Summary of Contents for TRADELINE R8184G

Page 1: ...991 Fig 1 Mounting the R8184G controls with 130 F 54 C maximum ambient temprature LOCATION 1 Mount on a 4 x 4 inch junction box directly on the main burner or inside the appliance cabinet In replacement applications mount in the same location as the old control 2 Ensure the operating temperatures are within the am bient temperature range Ambient temperature ranges are either 40 to 130 F 40 C to 54...

Page 2: ...s Strip leads 3 8 in 10 mm and insert under terminal screw See Fig 1 or 2 Connect cad cell leads to F F terminals and thermostat leads to T T terminals See Fig 3 or 4 CHECK SAFETY FEATURES Simulate flame failure 1 Follow starting procedure to turn on burner 2 Close hand valve in oil supply line 3 Safety switch should lock out approximately in safety switch timing indicated on label Indicator light...

Page 3: ...uts down the burner but doesnotdisconnectthepowersupply Turnoffpower at system switch or circuit breaker before servicing the control system burner motor oil valve or ignition to avoid electric shock To trip the safety switch move the safety switch lever down until the red reset button pops out and the indicator light comes on See Fig 5 Burner will not operate until safety switch is reset by pushi...

Page 4: ...omation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 www honeywell com ...

Reviews: