Honeywell Tradeline Q674A-E Installation Instructions Manual Download Page 10

10

60-1165—6

2. Move the system switch to AUTO or HEAT (if

used).

3. After one minute, read the ammeter and record the

reading:

Stage 1: __________ amperes.
Stage 2: __________ amperes.

NOTE: If equipment cycles too fast, set the indicator to a

higher current rating, not more than one-half division at
a time, and recheck cycle rate. Most conventional
2-stage heating equipment is designed to operate at three
cycles per hour per stage, and 1-stage heating equipment
at six cycles per hour, at 50 percent load condition.
When using the T874 Thermostat in heat pump systems,
set the heat anticipator at 140 percent of the actual
primary control current draw to reduce the cycling rate.

Most heat pump systems should cycle 2-1/2 to 3 times

per hour.

4. Hang the upper edge of the thermostat cover on top of

the thermostat base and swing the cover downward until it
engages with the cover clip.

TEMPERATURE SETTING

Move the heating and cooling set point levers (Fig. 23)

to the desired comfort positions. One lever controls all
stages of heating, and another lever controls all stages of
cooling. The minimum differential between heating and
cooling set point is 3

°

 F [1.7

°

 C].

Fig. 23—Location of external components.

Fig. 22—Adjustable heat anticipator scales.

SUBBASE SETTING

The subbase switching positions control the system

operation as described below (Fig. 23).

SYSTEM SWITCH (some subbases do not have all of
the following functions):

OFF: Both the heating and cooling systems are off. If

the fan switch is in AUTO position, fan is also off.

AUTO: Thermostat automatically changes between

heating and cooling system operation, depending
on the indoor temperature.

HEAT: Heating system is automatically controlled

by the thermostat. Cooling system is off.

COOL: Cooling system is automatically controlled

by the thermostat. Heating system is off.

FAN SWITCH

ON: Fan operates continuously.
AUTO: Fan operates with cooling equipment as con-

trolled by the thermostat or with the heating equip-
ment as controlled by the plenum switch.

To move the subbase switches to the desired control

positions, use thumb and index finger to slide lever. Lever
must stop over desired function indicator position for proper
circuit operation.

Checkout

HEATING

Move the system switch on the subbase to AUTO or

HEAT (if used) and the fan switch to AUTO. Move the
heating set point lever on the thermostat about 10

°

 F [6

°

 C]

above room temperature. Heating should start and the fan
should start after a short delay. Fan starts immediately in
heat pump systems. Move the heat lever 10

°

 F [6

°

 C] below

room temperature. The heating should shut off; fan should
shut off after a short delay. Fan shuts off immediately in
heat pump systems.

NOTE: In heat pump applications, time delays are involved

before the compressor is activated to prevent short cy-
cling. The delays are provided by a minimum-off timer
that prevents the compressor from starting for up to five
minutes from when the thermostat last turned off the
compressor, or from when the system first received
power.

COOLING

Move the system switch on the subbase to AUTO or

COOL (if used) and the fan switch to AUTO. Move the
cooling set point lever on the thermostat about 10

°

 F [6

°

 C]

below room temperature. The cooling and fan should start
(see NOTE above). Move the cool lever about 10

°

 F [6

°

 C]

above room temperature. The cooling and fan should stop.

FAN

Move the subbase system switch to OFF, and the fan

switch to ON. The fan should run continuously. Move the fan
switch to AUTO. In the AUTO position, fan operation is
controlled by the heating or cooling system control circuit.

Summary of Contents for Tradeline Q674A-E

Page 1: ...age 2 To prevent interference with the thermostat linkage keep wire length to a minimum and run wires close as possible to the subbase 3 Do not overtighten thermostat captive mount ing screws because damage to subbase threads can result 4 Do not short across coil terminals on heating relay or gas control This can burn out the thermostat heat anticipator IMPORTANT Thermostats are calibrated at the ...

Page 2: ...t the system wires to the subbase as shown in Figs 8 through 16 A letter code is located near each terminal for identification The terminal barrier permits straight or conventional wraparound wiring connections See Fig 4 Fig 4 Wiring connections 2 Your Q674 Subbase can require one or more jumpers that may or may not be factory supplied Refer to the wiring diagrams for specific terminals to be jump...

Page 3: ...he T874D Thermostat is shown with the subbases Thisthermostat subbaseprovides2 stageheat ing and 2 stage cooling connections If using another model see Fig 16 and Table 4 TABLE 4 THERMOSTAT BULB CONFIGURATOIN Model No Heating Bulbs Cooling Bulbs T874A H1 C1 T874B H1 C1 C2 T874C H1 H2 C1 T874D H1 H2 C1 C2 T874E C1 C2 T874F H1 H2 Fig 7 For nonadjacent terminals use jumper supplied with subbase TABLE...

Page 4: ...FF COOL SYSTEM SWITCH H1 ANTICIPATOR C1 ANTICIPATOR AUTO ON FAN SWITCH 2 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RH RC FOR SINGLE TRANSFORMER 2 M933C B HEAT CHANGEOVER VALVE L1 HOT L2 1 COOL CHANGEOVER VALVE FAN RELAY COMPRESSOR CONTACTOR 2 COMPRESSOR CONTACTOR 1 1 4 6 8 9 10 11 H2 FALL C2 ANTICIPATOR RISE RISE C1 C2 X1 3 OPTIONAL LED ON SOME MODELS THERM...

Page 5: ... 6 Fig 10 T874D Q674B in standard heating cooling system with single transformer for heating and cooling Exact replacement for York model no 2TB04700324 Fig 11 T874D E F Q674C in standard heating cooling system ...

Page 6: ...6 60 1165 6 Fig 12 T874A D F Q674D in standard heating cooling system Fig 13 T874D Q674E in standard heating cooling system ...

Page 7: ...7 60 1165 6 Fig 14 T874A F Q674G in standard heating cooling system Fig 15 T874C Q674B in standard application ...

Page 8: ...e locked in place at a specific temperature control point Do not use standard screws that provide metal to metal contact with the lever brackets To install 1 Refer to Fig 20 for screw hole locations 2 Install the two screws with insulated heads in the indicated holes Do not overtighten screws 3 Set the HEAT lever and the COOL lever at desired temperature control points 4 Firmly tighten both screws...

Page 9: ... each stage See Setting the Heat Anticipator section 5 Note the two tabs on the top inside edge of the thermostat base The tabs fit into corresponding slots on top of the subbase Mount the thermostat on the subbase 6 Align the two captive mounting screws in the ther mostat base with the posts on the subbase See Fig 21 Tighten both screws Do not overtighten screws or damage to subbase posts can res...

Page 10: ... controlled by the thermostat Cooling system is off COOL Cooling system is automatically controlled by the thermostat Heating system is off FAN SWITCH ON Fan operates continuously AUTO Fan operates with cooling equipment as con trolledbythethermostatorwiththeheatingequip ment as controlled by the plenum switch To move the subbase switches to the desired control positions use thumb and index finger...

Page 11: ...s the mounting slots 2 Set the thermostat cover on a table near an accurate thermometer 3 Allowtenminutesforcoverthermometertosensearea temperature compare the readings Be careful not to touch the thermometer or breathe on it 4 If the readings are the same replace cover and put the system into operation 5 If the readings are different insert a small screwdriver in the thermometer slot Fig 24 and t...

Page 12: ...ww honeywell com yourhome Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Reviews: