background image

® U.S. Registered Trademark
Copyright © 1999 Honeywell Inc. •                •All Rights Reserved 

INSTALLATION MANUAL

69- 1358

The Round

®

 Creative Series

Y460A2003 Thermostat

The Y460A2003 Thermostat is for 15 to 30 Vac control 
of gas- or oil-fueled warm air, steam or hot water 
heating/electric cooling systems.

Your Y460A Thermostat

Follow these instructions step-by-step for proper 
installation of your Honeywell thermostat. It is 
recommended that as you read, understand and 
complete each step, you check  

  it off with a pencil 

or pen.

1 PREPARE FOR INSTALLATION

Assemble the following required tools:
Flat-bladed screwdriver; hand or power drill with 
3/16 in. (4.8 mm) drill bit; wire cutter/stripper or sharp 
knife; bubble level or plumb bob and line.

IMPORTANT:

For cooling systems, do not operate cooling if 
outdoor temperature is below 50

°

F (10

°

C).

Test your heating and/or cooling systems to be sure 
they are working, especially if they have been 
inoperative for any length of time. If either system 
does not work, contact your local heating/air 
conditioning dealer for assistance.

IMPORTANT: 

Turn off power to the system at the main fuse 
or circuit breaker panel. Most buildings have a 
separate switch box or circuit breaker for dis-
connecting power to the furnace. 

2 UNPACK YOUR THERMOSTAT

Carefully unpack your new thermostat.

Remove and discard the shipping wrap; be sure to 
save the screws and the instructions.

Remove the thermostat cover and set it aside to use 
later. 

Remove the red plastic insert that holds the mercury 
switch in place.

3 REMOVE YOUR OLD 
THERMOSTAT

Remove the cover of the old thermostat. If the cover 
does not snap off when pulled firmly from the 
bottom, look for screw(s) to loosen to unlock the 
cover.

Before removing 
the old thermostat 
from the wall, look 
at it carefully to 
locate the heat 
anticipator 
adjustment 
mechanism. Look 
at the illustration to 
help you recognize 
the heat 
anticipator. Make a 
note here ______________ of that anticipator 
setting for use in Step 7. The heat anticipator pointer, 
if adjustable, will be set at one of a series of numbers 
representing the electrical current rating of the 
primary control in your furnace: .2, .4, .8, etc or 0.2, 
0.4, 0.8, etc. If no heat anticipator/indication is 
showing, go on to the next step.

Loosen screw(s) holding the thermostat base to the 
subbase or wall and lift it away.

FLAT BLADE
SCREWDRIVER

HAND OR POWER
DRILL WITH 1/16 INCH
DRILL BIT, IF NEEDED TO
DRILL HOLES IN WALL

WIRE CUTTER/STRIPPER OR SHARP
KNIFE, IF NEEDED TO STRIP WIRES

MASKING TAPE, IF NEEDED
TO LABEL WIRES AS THEY
ARE DISCONNECTED FROM
OLD THERMOSTAT

SPIRIT LEVEL OR PLUMB BOB AND LINE TO LEVEL 
THERMOSTAT FOR ACCURATE OPERATION

M 835

M6115

BULB
SWITCH

ANTICIPATOR
SCALE

ANTICIPATOR
SETTING LEVER

Summary of Contents for THE ROUND Y460A2003

Page 1: ...MOSTAT Carefully unpack your new thermostat Remove and discard the shipping wrap be sure to save the screws and the instructions Remove the thermostat cover and set it aside to use later Remove the red plastic insert that holds the mercury switch in place 3 REMOVE YOUR OLD THERMOSTAT Remove the cover of the old thermostat If the cover does not snap off when pulled firmly from the bottom look for s...

Page 2: ... outlet box with the mounting screws as shown in the illustration Tighten the screws after using a spirit level or plumb line to accurately level the subbase It must be level to maintain accurate calibration 5 WIRE THE SUBBASE Follow the instructions provided by the heating or heating cooling equipment manufacturer If not available refer to the thermostat wiring diagram NOTE All wiring must comply...

Page 3: ...tep 3 this information can be found printed on the primary control at the furnace or boiler The primary control is usually a gas valve a relay or burner control box Aquastat Controller or zone valve with the thermostat wires connected to it These controls are usually located behind the furnace cover see the illustration If the current rating is still unavailable Remove the W wire from the subbase ...

Page 4: ...ge Hazard Can cause permanent damage to the compressor or other equipment To avoid possible compressor damage allow the compressor to remain off for five minutes before restarting To avoid possible equipment damage do not operate cooling when the outside temperature is below 50 F 10 C See equipment manufacturer instructions CAUTION Equipment Damage Hazard Can cause permanent damage to the compress...

Page 5: ...YWELL MAKES ON THIS PRODUCT THE DURATION OF ANY IMPLIED WARRANTIES INCLUDING THE WAR RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE IS HEREBY LIMITED TO THE ONE YEAR DURATION OF THIS WARRANTY Some states do not allow limitations on how long an implied warranty lasts so the above limitation may not apply to you This warranty gives you specific legal rights and you may have other ri...

Page 6: ... Mexico www honeywell com Home and Building Control Home and Building Control Honeywell Inc Honeywell Limited Honeywell Limitée Honeywell Plaza 155 Gordon Baker Road P O Box 524 North York Ontario Minneapolis MN 55408 0524 M2H 3N7 ...

Reviews: