Honeywell TC840MFES Installation & Maintenance Instructions Download Page 1

I56-3424-002

H200-202-00

TC840MFE(I)S

B501AP

102 mm

63 mm

EN54-7: 2000

EN54-5: 2000 Class A1R

EN54-17: 2005 (EIS only)

0786

09

DOP-IFD168  TC840MFES

DOP-IFD169  TC840MFEIS

Pittway Tecnologica S.r.l. 

Via Caboto 19/3, 34147 

Trieste, Italy

Honeywell Building Solutions, Honeywell House, Arlington Business Park, Bracknell, Berkshire, RG12 1EB, UK

I56-3424-002

X 10

X 1

INSTALLATION AND MAINTENANCE INSTRUCTIONS 

FOR MODEL TC840MFES / TC840MFEIS 

MULTICRITERIA FIRE SENSOR

GENERAL DESCRIPTION

Models TC840MFES and TC840MFEIS intelligent multicriteria sensors are  plug-in type fire 

sensors that combine three types of detection capability with addressable communications.  

A photoelectronic sensing chamber detects smoke, while a thermal element provides rate-

of-rise and fixed temperature heat sensing and an infra-red sensor adds further detection 

ability. These sensors are designed for open area protection and must only be connected 

to control panels that use a compatible proprietary communication protocol for monitoring 

and control. 
The TC840MFEIS sensor contains an isolator, if installing this version check the panel 

documentation for details of how many isolators can be used on a loop.
Two LEDs on each sensor light to provide a local 360

visible sensor indication (operation of 

LEDs are dependent on panel).  Remote LED indicator capability is available as an optional 

accessory wired to the standard base terminals (again dependent on panel). 
SPECIFICATIONS
Operating Voltage Range: 

15 to 32 VDC (15 to 28 for EIS isolated)

Max. Standby Current (no comm.): 

200 µA @24 V and 25

o

C

(comm. LED blink enabled - 5 sec)  

300 µA @24 V and 25

o

C

(Read 16 sec. LED blink 8 sec) 

220 µA @24 V and 25

o

C

 

add 50 µA for EIS Isolated

Max.  Alarm Current (LED on): 

add 3.5 mA @ 24 V and 25

o

C

Operating Humidity Range: 

15% to 90% Relative Humidity, Non-Condensing

Nominal Activation Temperature: 

58°C 

Isolator Characteristics (TC840MFEIS Only)

Maximum rated continuous current with the isolator closed (Ic max): 1A

Maximum rated isolator current (under short circuit) (Is max): 1A

Max. leakage current (IL max) with the isolator open (isolated state): 15mA

Max. series impedance with the isolator closed (Zc max): 170 m ohm at 15Vdc
Independently  tested  and  certified  to:    EN54-7:  2000,  EN54-5:  2000  Class  A1R  and 

CEA4021 (and EN54-17: 2005 for the EIS)
WIRING GUIDE

Refer to the installation instructions supplied with the plug-in sensor bases for wiring details.  

All bases are provided with terminals for power and an optional Remote Indicator.
Note 1: All wiring must conform to applicable local and national codes and regulations.
Note 2: Verify that all sensor bases are installed and that polarity of the wiring is correct at 

each base.

WARNING

Disconnect loop power before installing sensors. Notify proper authorities.

SENSOR INSTALLATION

1.  Set the sensor address (see figure 1) by turning the two rotary switches on the underside 

of the sensor, selecting a number between 01 and 159.  (Note: The number of addresses 

available will be dependent on panel capability, check the panel documentation for 

information on this).  Record the address on the label attached to the base.

Figure 1: Rotary Address Switches

2.  Insert the sensor into the base and rotate it clockwise until it locks into place.

3.  After all the sensors have been installed, apply power to the system.

4.  Test the sensor as described under TESTING.

5.  Reset the sensor by communication command from the panel.
Tamper-Resistance.

These sensors includes a feature that, when activated, prevents removal of the sensor from 

the base without the use of a tool.  Refer to the installation instructions for the sensor base 

for details of how to use this feature.

CAUTION

Dust covers help to protect units during shipping and when first installed. 

They are not intended to provide complete protection against contamination 

therefore sensors should be removed before construction, major re-decoration 

or other dust producing work is started.   Dust covers must be removed before 

system can be made operational.

Figure 2:  Cleaning the Sensor

Sensor Cover

Cover Removal Tabs

Thermistor

Air Guide

Sensing Chamber Cover

 and Screen

Infra-Red Sensor

Thermistor 

Optical Sensing Chamber

MAINTENANCE

Before cleaning, disable the system to prevent unwanted alarms:
1.  Remove the sensor to be cleaned from the system.

2.  Gently release each of the four cover removal tabs that hold the cover in place (see figure 

2) and remove the sensor cover.

3.  Gently remove the thermistor air guide by pulling it straight out.

4  Vacuum the outside of the screen/chamber cover carefully without removing it.

5.  Remove the screen/chamber cover assembly by pulling it straight out (take care to avoid 

damaging the thermistor).  

6.  Use a vacuum cleaner and/or clean, compressed air to remove dust and debris from the 

sensing chamber, sensing chamber cover and thermistor if required..

7.  Re-install the sensing chamber cover by aligning the square and round holes on the 

cover with the square and round pins around the sensing chamber, gently pressing it 

home until it slips into place.

8.  Re-install the thermistor air guide by aligning the holes in the guide with the pins on top 

of the chamber cover (take care to avoid damaging the thermistor).

9  Re-install the sensor cover.  Use the cover removal tabs and LEDs to align the cover with 

the sensor.  Snap the cover into place.

10. When all sensors have been cleaned, restore power to the loop and test the sensor(s) 

as described under TESTING

TESTING

Sensors must be tested after installation and following periodic maintenance.  Disable the 

zone or system undergoing maintenance to prevent unwanted alarms.
Test the sensors as follows:
Magnet Method
1.  Test the sensor by positioning the test magnet (model M02-24-optional) against the 

sensor body approximately 2cm from LED 1, indicated by a mark on the sensor cover 

as shown in figure 3.

2.  Both LED’s on the sensor should latch into alarm within 30 seconds, activating the control 

panel.

Smoke Method
1. At alarm levels 4 and 5, the sensor includes electronic delays of up to 3 minutes for a 

smoke only response. To disable the delay for ten minutes, a magnet test as described 

above should be carried out prior to the smoke tests.  

2. Use either a canned smoke aerosol or a detector tester for generating artificial smoke 

to test the sensor. Inject the smoke into the sensor’s chamber using the test smoke as 

recommended by the manufacturer and ensure that it is present until an alarm occurs 

on the sensor.

3. The red alarm LED should latch on within 30 seconds indicating an alarm and activating 

the panel into a condition to indicate the sensor under test.

Direct Heat Method (Hair dryer of 1000-1500 watts).
1.  Direct the heat toward the sensor from its side.  Hold the heat source about 15 cm away 

to prevent damage to the cover during testing.

2.  The LEDs on the sensor should light when the temperature at the sensor reaches 58°C.  

3.  Reset the sensor at the system control panel.
After completion of the test notify the proper authorities that the system is operational.

WARNING: LIMITATIONS OF SMOKE SENSORS

Fire sensors must be used in conjunction with compatible equipment. 

Smoke sensors will not sense fires which start where smoke does not reach the sensors. 
A sensor may not detect a fire developing on another level of a building. 

Smoke sensors also have sensing limitations.  Consideration must be made of the 

environment when selecting fire sensors.

Fire sensors cannot last forever. Fire sensors contain electronic parts. Even though 

sensors are made to last over 10 years, any of these parts could fail at any time. Therefore, 

test your fire detection system at least semi-annually. Clean and take care of your smoke 

sensors regularly. Taking care of the fire detection system you have installed will significantly 

reduce your product liability risks.

ENGLISH

Figure 3:  Test Magnet Position

Test Magnet

Mark on Cover

LED 2

LED 1

Summary of Contents for TC840MFES

Page 1: ...uld be removed before construction major re decoration or other dust producing work is started Dust covers must be removed before system can be made operational Figure 2 Cleaning the Sensor Sensor Cover Cover Removal Tabs Thermistor Air Guide Sensing Chamber Cover and Screen Infra Red Sensor Thermistor Optical Sensing Chamber MAINTENANCE Beforecleaning disablethesystemtopreventunwantedalarms 1 Rem...

Page 2: ...io rimuovere i coperchi antipolvere prima della messa in funzione del sistema Figura 2 Pulizia del sensore Coperchio del sensore Linguette per la rimozione del coperchio Guida pneumatica del termistore Coperchio e schermo della camera di rilevazione Sensore a infrarossi Termistore Camera di rilevazione ottica MANUTENZIONE Primadiprocedereallapuliziadisabilitareilsistemaondeevitarel attivazionedial...

Page 3: ...ar cualquier tipo de obra remodelación u otra actividad que genere polvo Las fundas protectoras deben extraerse antes de la puesta en marcha del sistema Figura 2 Limpieza del sensor Tapa del sensor Pestañas para extraer la tapa Pieza que guía el aire hacia el termistor Pantalla y tapa de la cámara de detección Sensor infrarrojo Termistor Cámara de detección óptica MANTENIMIENTO Antesdelimpiarloseq...

Page 4: ... ordnungsgemäßen Funktion ist der Staubschutz vor der Inbetriebnahme des Melders abzunehmen Abbildung 2 Reinigung des Melders Meldergehäuse Gehäusehalterungen Thermoelement Luft Führung Messkammerabdeckung mit Schutzgitter Infrarotsensor Thermoelement Optische Messkammer WARTUNG ZurVermeidungvonFehlalarmensolltedasSystembzw dieentsprechendeMeldergruppevorden Wartungsarbeitenabgeschaltetwerden 1 En...

Reviews: