This manual is intended as a quick reference installation guide. Please refer
to the control panel installation manual for detailed system information.
GENERAL INFORMATION
The TC810E series of modules are a family of microprocessor controlled
interface devices permitting the monitoring and/or control of auxiliary
devices. The TC810E1040, TC810E1040-KO and TC810E1057 are output
modules, providing 250VAC 5A rated voltage free contacts, both normally
open and normally closed.
SPECIFICATIONS
Operating Voltage Range:
15 to 30VDC (Min 19.5VDC to ensure LED
operation - TC810E1040-KO 17.5VDC)
Maximum Standby Current (µA): 275µA - No Communication
445µA - Communication LED blink enabled - 5 secs
375µA - Read 16 sec. LED blink 8 sec
Fault Current:
8.8mA (Yellow LED illuminated)
Coil Activation/Deactivation Current: 76mA Maximum for 12mS
Relay Contact Rating:
5A, at 30VDC, 5A at 250VAC
Maximum rated continuous current with the
isolator
closed (I
c
max): 1A
Maximum rated isolator current (under short circuit) (I
s
max): 1A
Maximum leakage current (I
L
max) with the isolator open (isolated state): 15mA
Maximum series impedance with the isolator closed (Z
c
max): 170 m ohm at 15Vdc
Operating Temperature:
-20°C to 60°C
Humidity:
5% to 95% Relative Humidity
Dimensions TC810E1040 and TC810E1040-KO: 134mm(H) x 139mm(W) x 40mm(D)
Dimensions TC810E1057:
127mm(H) x 76mm(W) x 48mm(D) (Including terminals)
Weight TC810E1040 and TC810E1040-KO: 195g
Weight TC810E1057:
140g
Maximum Wire Gauge
1.5mm² - TC810E1040 (-KO), 2.5mm² - (-DIN)
INSTALLATION
Note: These modules must only be connected to control panels using
compatible proprietary analogue addressable communication
protocols for monitoring and control.
CAUTION
Disconnect loop power before installing modules or sensors.
High voltages may be present on terminals 7 to 12.
TC810E1040 and TC810E1040-KO
1. The TC810E1040(-KO) includes a custom low profile surface-mounting
box with several options for fixing centres. To access all fixing points,
and the rear cable entry knock out, the circuit board must be removed.
It is held in place by two screws through the circuit board. Ensure that
these screws are replaced when refitting the circuit board.
2. If rear cable entry is not required, the box has several cover drill points
permitting the entry of cables using suitable glands.
3. Wiring to the TC810E1040(-KO) is made via two 6 way terminal strips
on the module circuit board, capable of supporting conductors up to
1.5mm². See figure 2 for connections.
4. An earthing terminal is provided in the surface mount box for connection
of the loop cable screen, if used, to ensure continuity. See figure 1a.
TC810E1057
1. TC810E1057 mounts onto standard 35mm x 7.5mm "Top Hat" DIN rail.
It must be mounted in a suitable cabinet meeting the applicable safety
standards.
2. Wiring to the TC810E1057 is via plug in type terminals capable of
supporting conductors up to 2.5mm². See figure 2 for connections.
WARNING
Ensure that the correct terminals are used for the loop and
switched voltage as damage may result from incorrect usage.
For both modules, the address is selected by means of rotary decade
address switches (see figure 2), accessed at the front of the module. A
screwdriver should be used to rotate the wheels to select the desired
address. (Note: The number of addresses available will be dependent on
panel capability, check the panel documentation for information on this.)
Short Circuit Isolators
All TC810E series modules are provided with short circuit monitoring and
isolators on the intelligent loop. If required the isolators may be wired out of
the loop to facilitate the use of the modules on high current loaded loops, for
example if sounders are used. To achieve this, the loop out positive should
be wired to terminal 5 rather than terminal 2.
Figure 1a: TC810E1040(-KO) Surface Mount
Output Module with 240V Relay Contacts
Figure 1b: TC810E1057 Din Rail Mounted
Output Module with 240V Relay Contacts.
TO MOUNT, LOCATE LUG OVER TOP
OF RAIL AND ROTATE THE MODULE
DOWN TO CLIP INTO PLACE.
TO REMOVE, PUSH UPWARDS, AND
ROTATE TOP OF MODULE AWAY
FROM RAIL.
Figure 2: Module Wiring
NOTE:
Wiring is the same for TC810E1040(-KO) and TC810E1057
Loop -, Out
Loop +, Out - See Note 1
Loop -, In
Loop +, In
Loop +, Out - See Note 1
T6 - Not Connected
Relay 1, N/O
Relay 2, N/C
Ground
Ground
Relay 2, N/C
Relay 1, N/O
TENS UNITS
LOOP CABLE SCREEN TERMINAL
TC810E1040, TC810E1040-KO
AND
TC810E1057
INSTALLATION INSTRUCTIONS FOR MAINS SWITCHING OUTPUT MODULES
ROTARY DECADE ADDRESS SWITCHES
Notes:
1. If short circuit isolation is not required, then the loop output should
be wired to terminal 5 rather than terminal 2. Terminal 5 is internally
connected directly to terminal 4.
2. In order to meet the requirements of European Safety Standards,
ensure that all cables carrying voltages in excess of 48V are suitably
fused.