DIGITAL BURNER CONTROLLER 

TBC2800 SERIES 

 

 

 
 

FEATURES 

PRODUCT HANDBOOK 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

APPLICATION 

 

TBC2800 series is the high-performance burner controller which is de- 

signed for commercial and industrial application and suitable for gas 

firing. 

 

TBC2800 series can be used for pulse firing and modulating 
firing mode. 

 

TBC2800 series applies to multiple burners application, such as steel, 

machinery  manufacturing,  non-ferrous  metals,  glass,  ceramic,  petro- 

chemical and other industries. 

INSTALLATION 

 

TBC2800  can  be  installed  with  DIN  rail  or  two  M4  screws.  While 

install-ing  with  M4  screw,  it  is  necessary  to  put  the  sealing  gasket 

beforehand so as to ensure IP 54 protection. 

 

TBC2800 reserves 7 x M16 holes for cable wiring. 

 

  

WARNING 

Improper operation will cause personal injury or equipment damage! 
Disconnect the power connection before installation! 

Must consider the electric shock protection! Make sure the end- 
users can not access the parts not proper insulated 

 
 
 
 
 
 
 

 

 

Compatible to UV, Double rod (separated flame rod and 
igni-tion rod) and 1 rod (integrated flame rod and ignition 
rod) flame detection which can be set manually

 

Integrate 6 kinds of timing choices which can be set 

manually according to the application requirements

 

24 hours continuous operation (except UV application)

 

Life-

cycle ≥ 250K times (Note 1)

 

IP54 protection 

field or cabinet installation

 

Multifunctional  LED  lights  and  buttons  indicate  the 

Flame  strength,  fault  &  operation  sequence  and 

parameters

 

Remote or on-site reset

 

Adjustable flame on-off threshold

 

Comply with EN298

SPECIFICATIONS 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

UV sensor C7027A/C7035A/C7044A 

 

CAUTION 

Read these instructions carefully. Failure to follow them 
could  damage  the  product  or  cause  a  hazardous 
condition. 

 

Check the ratings given in the instructions and marked on 
the product to make sure the product is suitable for the 
application.

 

Installer must be a trained, experienced, flame 
safeguard ser-vice technician.

 

After  installation  is  completed,  the  operation 
parameters  should  be  set  by  the  authorized  person 
according  to  the  application  requirements  and  this 
product handbook.

 

Keep the flame detector cable and ignition cable as 
far as possible.

 

C7027A/C7035A/C7044A  is  not  the  self-checking  UV 
sensor, so TBC2800 should be restarted once every 24 
hours.

Note1: If one rod flame detection is applied, TBC2800 lifecycle will be 

100,000 times.

 



W x D x H: 

 

122.5 x 82 x 131.2mm 

Mains input 

 

220/230VAC 

–15/+10% 

50 60Hz 

Power consumption 

 

 

9 VA 

Cable length of flame rod: 

 

75m(max) 

Cable length of UV 75m max) 

Flame threshold setting 

 

1~10µA 

Cover 

material 

 

 

PC/ABS 

Protection class 

 

 

I P54 

Ambient  temperature 

-20 

 

Ambient humidity 

 

95%, non condensing 

Lifecycle 

 

 

250,000 cycles comply with EN298 

Drive gas valve  1A(max) power factor 

 

Drive ignition transformer 2A(max) 

PF 

0.2 

Maximum output for terminal 

2A 

242Vac 

 

Summary of Contents for TBC2800 Series

Page 1: ...ts 24 hours continuous operation except UV application Life cycle 250K times Note 1 IP54 protection field or cabinet installation Multifunctional LED lights and buttons indicate the Flame strength fault operation sequence and parameters Remote or on site reset Adjustable flame on off threshold Comply with EN298 SPECIFICATIONS UV sensor C7027A C7035A C7044A CAUTION Read these instructions carefully...

Page 2: ...00 starts the flame simu lation delay time T5 If the flame disappears during T5 the burner will start up Otherwise the fault lock out occurs The LED display blinks and indicates 1 4 Lock out immediately or restart once after flame fail They can be set according to the application requirements The immediate lock out is default 1 Lock out immediately after fault TBC2800 will perform the fault lock o...

Page 3: ...pond two start ups with T2 is too short T7 Last time of Re 10s Permanent mote Reset remote reset Note If T3 2s follow EN746 2 11 Running state information summary 1 Sleep code 2 Stand by code 0 3 Flame simulation T1 code 1 4 Ignition process T2 code 2 5 Working process code 3 6 Fault lock code refer to Table 1 Fault lock information 12 Button operation 1 Press the INFO button for 2s then the param...

Page 4: ...l ignition transformer UV Flame Detection Mounting plate Pilot and Main firing control Double Rod for example UV sensor W white cable B blue cable Dimension mm Product Code Timing Code T2 sec T3 sec 1 3 1 2 5 1 3 10 1 4 3 2 5 5 2 6 10 2 Wiring diagram Double Rod Flame Detection Start up signal High voltage Fault signal Gas valve Flame signal Reset signal Ignition transformer Operation signal Safet...

Reviews: