TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS
5
62-2016—05
Wiring Identification and Screw Terminal Arrangement
Table 1.
Terminal identification
Fig. 5. Screw terminal arrangement
NOTES:
—
If auxiliary output is used to toggle occupancy of the electronic control card inside the equipment, configure
the relay parameter (
Aux cont)
to the N.O. setting. A second relay can be added for additional functionality
of the occupancy output.
—
If the same power source is used for the heating stages, install jumper across RC and RH. Maximum cur-
rent is 2.0 amps.
—
Economizer output uses a half bridge rectifier. Reference of the control signal is the common of the power
supply of the thermostat (terminal C).
—
Electromechanical contacts are to be used with the digital inputs. Electronic triacs cannot be used as mean
of switching for the input. The switched leg to the input for the input to activate is terminal C (common).
—
The transformer of the unit provides power to the thermostat and the additional loads that will be wired to
the thermostat.
Model Number
Multistage
1H/1C
Model Number
Heat Pump
TB7656B TB7605B TB7652B TB7600B TB7652A TB7600A
TB7652H TB7600H
Programmable
Yes
No
Yes
No
Yes
No
Programmable
Yes
No
Top left terminal block
1- Cool Stage 2 Y2
Y2
Y2
Y2
Blank
Blank
1- Compressor
Stage 2
Y2
Y2
2- Cool Stage 1 Y1
Y1
Y1
Y1
Y1
Y1
2- Compressor
Stage 1
Y1
Y1
3- Fan
G
G
G
G
G
G
3- Fan
G
G
4- 24 V - Hot
RC
RC
RC
RC
RC
RC
4- 24 V - Hot
RC
RC
5- 24 V - Com
C
C
C
C
C
C
5- 24 V - Com
C
C
Top right terminal block
6- RH
RH
RH
RH
RH
RH
RH
6- RH
RH
RH
7- Heat Stage 1 W1
W1
W1
W1
W1
W1
7- AUX Heat
W1
W1
8- Heat Stage 2 W2
W2
W2
W2
Blank
Blank
8- O/B
O/B
O/B
Bottom terminal block
9- Econo
EC
EC
Blank
Blank
Blank
Blank
9- Not Used
Blank
Blank
10- Auxiliary
Output
Aux
Aux
Aux
Aux
Aux
Aux
10- Auxiliary
Output
Aux
Aux
11- Digital Input
1
DI1
DI1
DI1
DI1
DI1
DI1
11- Digital Input
1
DI1
DI1
12- Digital Input
2
DI2
DI2
DI2
DI2
DI2
DI2
12- Digital Input
2
DI2
DI2
13- Remote
Sensor
RS
RS
RS
RS
RS
RS
13- Remote
Sensor
RS
RS
14- Scom
S COM
S COM
S COM
S COM
S COM
S COM
14- Scom
S COM
S COM
15- Remote
Outdoor
Sensor
OS
OS
OS
OS
OS
OS
15- Remote
Outdoor
Sensor
OS
OS
16- Mixed Air
Sensor
MS
MS
MS
MS
MS
MS
16- Mixed Air
Sensor
MS
MS
5 POLE LEFT TOP CONNECTOR
3 POLE LEFT TOP CONNECTOR
8 POLE BOTOM CONNECTOR
MS
EC
AU
D1
D2
RS
Y2
Y1
G
RC
C
Scom OS
RH
W1
W2
O/B
M16928