Honeywell TB7220 COMMERCIALPRO Product Data Download Page 19

TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

19

63-2635—03

Partially Locked Screen

When partially locked:

— Pressing a locked key prompts the screen to indicate 

SCREEN LOCKED for five to seven seconds.

— Pressing an unlocked key with SCREEN LOCKED active 

removes SCREEN LOCKED from the display.

PARTIAL LOCKOUT 1

This mode locks all keys except HOLIDAY, OVERRIDE, and 

temperature Up/Down arrows:

— User can change the temperature setpoint, but cannot 

change schedule settings.

— The temporary temperature change lasts until next 

scheduled period. The screen displays that time.

— User can change the temperature setpoint, but cannot 

change schedule settings.

— Pressing HOLIDAY sets the temperature to the Unoccupied 

setting for the selected period of time. The next Occupied 

period switches back to the program settings.

— Pressing OVERRIDE sets the temperature to the Occupied 

setting for the selected period of time. The next Unoccupied 

period switches back to the program settings.

— To cancel the temperature override and follow the 

programmed schedule, press CANCEL.

— To unlock the screen, see Advanced Settings section.

PARTIAL LOCKOUT 2

This mode locks all keys except HOLIDAY and OVERRIDE:

— Pressing HOLIDAY sets the temperature to the Unoccupied 

setting for the selected period of time. The next Occupied 

period switches back to the program settings.

— Pressing OVERRIDE sets the temperature to the Occupied 

setting for the selected period of time. The next Unoccupied 

period switches back to the program settings.

— To cancel the temperature override and follow the 

programmed schedule, press CANCEL.

— To unlock the screen, see Advanced Settings section.

Temperature Recovery

The thermostat is equipped with a feature to eliminate 

guesswork when setting a schedule. That is, the user need not 

know the amount of time for the HVAC system to bring the 

space to temperature (without overshoot) prior to the 

scheduled time.The thermostat manages that automatically.

Simply set the program schedule to the desired time to have 

the space at comfort temperature. In addition, program the 

temperature to this comfort temperature. The thermostat 

activates the heating or cooling at the proper time to reach the 

scheduled temperature at the scheduled time.

NOTE: The setpoint changes gradually to use economical 

stages and avoid overshoot.

For example—the space will be occupied at 8:00 AM and the 

desired temperature is 70°F. Set the OCC 1 period for 8:00 AM 

and 70°F. The thermostat turns on the heat prior to 8:00 AM to 

raise the temperature to 70°F by 8:00 AM.

The thermostat provides an alert that the heating or cooling 

system is coming on before a scheduled time by displaying 

“Recovery” on the screen.

Minimum-Off Timer Compressor Protection

The thermostat has an adjustable Minimum-Off Timer that can 

be set from zero to five minutes (Factory Setting—five 

minutes). The Minimum-Off Timer can be bypassed through 

the Installer System Test or it can be bypassed permanently by 

setting the Minimum-Off Timer to 0 minutes in the Installer 

Setup. The Minimum-Off Timer is activated after the 

compressor turns off:

— If the thermostat is system powered (common wire), the 

Minimum-Off Timer is also activated upon initial startup and 

after power interruptions.

— If there is a call for cooling or heating during the Minimum-

Off Time, the thermostat displays “Wait.”

— When the Minimum Off Timer expires, “Cool On” or “Heat 

On” (heat pumps only)” appears solidly in the display and 

the compressor and fan turn on.

Economizer/TOD Logic (Table 8)

Table 8. Operation of Terminal A.

Heat Pump Temperature Lockouts

Dual Fuel Heat Pump and Outdoor Temperature 
Sensor

In this operation, there is no external fossil fuel kit (dual fuel kit) 

installed; the thermostat controls this function:

1.

Choose correct heat pump application in ISU 0170.

2.

Choose 

Outdoor Temperature Sensor for Heat Pump 

Temperature Lockouts

 

Option

 in ISU 0340.

3.

Choose appropriate 

Balance Point Temperature

 in 

ISU 0350.

OPERATION IN HEAT MODE ABOVE BALANCE POINT (OUTDOOR 
TEMPERATURE)

When the outdoor temperature is above the selected Balance 

Point Temperature (ISU 0350), only the compressor operates 

and the fan (G terminal) energizes when the thermostat calls 

for heat.

OPERATION IN HEAT MODE BELOW BALANCE POINT (OUTDOOR 
TEMPERATURE)

When the outdoor temperature is below the selected Balance 

Point Temperature (ISU 0350), only the Fossil Fuel (auxiliary 

heat) operates and the fan (G terminal) does not energize 

when the thermostat calls for heat.

Heat Pump with Auxiliary (Backup) Heat and Outdoor 
Temperature Sensor

1.

Choose correct heat pump application in ISU 0170.

2.

Choose 

Outdoor Temperature Sensor for Control 

Option 

in ISU 0340.

3.

Choose 

Compressor Lockout Temperature

 in 

ISU 0350.

4.

Choose 

Auxiliary Lockout Temperature 

in ISU 0360.

Effective 

Occupancy

Call for 

Cool

Terminal A

Economizer

TOD

Occupied

Energized

Energized

Unoccupied Yes

Energized

De-energized

No

De-energized

De-energized

Override

Energized

Energized

Summary of Contents for TB7220 COMMERCIALPRO

Page 1: ...riven programming make setup effortless Beautiful ergonomic design is smart and sophisticated to match your customers lifestyle Real time clock keeps time during power failures and automatically updates to daylight savings Saving Changes notification lets you know when the schedule changes have been saved Change reminders let you know when to replace the batteries Holiday Override options allow yo...

Page 2: ...ifferential Droopless control Once the first stage is running at 90 load the thermostat energizes the second stage Cool Indication Displays Cool On when Cool is activated Heat Indication Displays Heat On when Heat is activated Auxiliary Heat Indication Displays Aux Heat On when Auxiliary Heat is activated Clock Accuracy 1 minute per month Finish TB7000 Premier White color C7189U Wall Mount Remote ...

Page 3: ... Plate is used to cover marks left on the wall by the old thermostat Dimensions TB7220 Thermostat See Fig 1 C7089U Outdoor Sensor Mounting Clip See Fig 3 C7189U Remote Indoor Sensor see Fig 5 T7770A See Fig 4 32003796 001 Cover Plate See Fig 2 Fig 1 TB7220 Thermostat dimensions in in mm Fig 2 32003796 001 Cover Plate dimensions in in mm Fig 3 C7089U Outdoor Sensor Mounting Clip dimensions in in mm...

Page 4: ... instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation Select Thermostat Location Select a location for the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 6 Fig 6 Select thermostat location Do not install the thermostat where it c...

Page 5: ...before connecting wiring IMPORTANT All wiring must agree with applicable codes ordinances and regulations Use 18 gauge thermostat wire Shielded cable is not required NOTES Refer to Table 5 for terminal designation descriptions See Fig 12 through 21 for wiring diagrams for specific equipment applications 1 Select set of terminal identifications that correspond to your system type conventional or he...

Page 6: ...the thermostat the cooling transformer must power the economizer The A signal is powered from the R terminal and energizes the economizer to signal occupied status and drive the damper to the set minimum position System Type Wallplate Terminal Identifications Wiring Diagram Figure Standard Heat Cool Conventional 12 13 Heat Only Conventional 14 Cool only Conventional 15 Standard Multistage up to 2 ...

Page 7: ...NSFORMER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE FACTORY INSTALLED JUMPER WHEN USING BATTERIES THE 24V COMMON CONNECTION IS OPTIONAL WHEN USED THE COMMON MUST CONNECT TO THE COOLING TRANSFORMER SECONDARY 1 3 2 3 ECONOMIZER L1 HOT L2 1 24 VAC L1 HOT L2 1 24 VAC C G Y W RC R W2 Y2 A S1 S2 2 M23013 OUTDOOR INDOOR TEMPERATURE SENSOR HEAT RELAY POWER SUPPLY PROV...

Page 8: ...OLING TRANSFORMER SECONDARY 1 3 2 3 COOL RELAY 1 HEAT RELAY 1 COOL RELAY 2 L1 HOT L2 1 24 VAC L1 HOT L2 1 24 VAC ECONOMIZER C G Y W RC R W2 Y2 A S1 S2 2 COOLING TRANSFORMER HEATING TRANSFORMER COMPRESSOR CONTACTOR M23018 CHANGEOVER VALVE 1 2 3 4 5 FAN RELAY POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FACTORY INSTALLED JUMPER WHEN USING BATTERIES THE 24V COMMON CONNECT...

Page 9: ...me clock Fig 23 Remove tab labeled REMOVE from thermostat back COMPRESSOR CONTACTOR ECONOMIZER M23020 CHANGEOVER VALVE 1 2 3 4 5 FAN RELAY POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FACTORY INSTALLED JUMPER WHEN USING BATTERIES THE 24V COMMON CONNECTION IS OPTIONAL O B TERMINAL SET TO CONTROL AS EITHER O OR B IN THE INSTALLER SETUP OPTIONAL OUTDOOR OR INDOOR REMOTE S...

Page 10: ...panels Use shielded cable to reduce interference when rerouting is not possible 1 Wire C7089U Outdoor Sensor to S1and S2 terminals on the thermostat If leadwire provided is not long enough 60 in run a cable to a hole at C7089U location a Using color coded 18 gauge thermostat wire is recommended For example of general wiring of C7089U see Fig 25 2 Mount C7089U in its mounting clip 3 Plug wiring hol...

Page 11: ... network Fig 28 Wiring two T7770A1006 20K ohm Sensors and one T7770A3002 10K ohm sensor to provide a temperature averaging network Fig 29 Wiring four C7189U 10K ohm Sensors to provide a temperature averaging network SET CALENDAR AND TIME This thermostat is designed to under normal use automatically keep current time and day in memory for up to ten years once the calendar is set There are two ways ...

Page 12: ...ed to the right NOTE To cycle through the Setup Numbers press the up or down arrow Fig 32 Entering Installer Setup User Settings Simple Set Access to the user settings is obtained as follows 1 From the main screen press SYSTEM Five blank touch keys show on the bottom of the screen between DONE and CANCEL 2 Press and hold the center blank key approximately five seconds 3 The Setup Number displays t...

Page 13: ...C HP 12 3H 2C HP 0175 TOD Economizer output 0 0 Unused 1 TOD 2 Economizer Economizer energizes A during a call for cool TOD energizes A during Occupied period and deenergizes A during Unoccupied 0180 Heat Fan Operation 0 0 Fossil 1 Electric Only shown for conventional system with heat stages and fan capability selected If heat pump is selected fan defaults to electric 0185 Pre occupancy Purge Dura...

Page 14: ...5 1 5 35 F 1 5 C 40 4 5 40 F 4 5 C 45 7 0 45 F 7 0 C Only shown for heat pump systems with more heat stages than cool selected and remote sensor selection is outdoor for control Must enforce a dead band between this and Auxiliary Lockout 0360 Heat Pump Auxiliary Lockout 0 0 None 40 4 5 40 F 4 5 C 45 7 0 45 F 7 0 C 50 10 0 50 F 10 0 C 55 13 0 55 F 13 0 C 60 15 5 60 F 15 5 C Only shown for heat pump...

Page 15: ...ges Only integral gains affected Affects control operation in all control regimes not just recovery or setpoint change More Aggressive stops signal prior to reaching the setpoint For use with oversized equipment 0695 Recovery Cool Ramp Rate 3 0 20 F hour Only shown if system has cool stages 0 disables ramped recovery step setpoint change at period start time 0700 Temperature Display Offset 0 3 1 5...

Page 16: ... Available schedule times are at 15 minute intervals Editing Schedule 1 Press MORE 2 Press SCHEDULE 3 Press EDIT 4 Press SELECT DAY to select the days you wish to schedule 5 Press NEXT when finished selecting days NOTES Multiple days can be selected To skip over a day press the Up or Down arrow keys Checkmarks appear next to selected days These are scheduled with identical times and tempera tures ...

Page 17: ...LE to cancel Hold Tempera ture Until and resume the schedule OVERRIDE Changes temperature setting until the next period takes effect For use during Unoccupied periods 1 Press OVERRIDE The settings change by default to the next Occupied period NOTE Changes are limited to those allowed by the lockout level 2 Press Up or Down arrow to change the override temper ature and NEXT to adjust override time ...

Page 18: ...ostat displays the indoor temperature from the remote sensor s NOTE If connected to an installed remote indoor temperature sensor the thermostat internal sensor is not used ONE REMOTE INDOOR SENSOR INSTALLED If one remote indoor temperature sensor is used the screen showing the Inside temperature reading displays the temperature at the indoor remote sensor location MULTIPLE REMOTE INDOOR SENSORS I...

Page 19: ...he desired temperature is 70 F Set the OCC 1 period for 8 00 AM and 70 F The thermostat turns on the heat prior to 8 00 AM to raise the temperature to 70 F by 8 00 AM The thermostat provides an alert that the heating or cooling system is coming on before a scheduled time by displaying Recovery on the screen Minimum Off Timer Compressor Protection The thermostat has an adjustable Minimum Off Timer ...

Page 20: ...energizes such as load conditions environmental conditions P I control and home insulation The second stage energizes when the thermostat senses 1st stage is running at 90 capacity This operation is droopless control Temperature Sensor Operation and Checkout Allow outdoor or indoor temperature sensor to absorb the air for a minimum of five minutes before taking a reading See the Sensor instruction...

Page 21: ...ure resistance curve in Fig 42 Fig 42 10K ohm sensor resistance versus temperature T7770A Remote Temperature Sensor Operation When installed with Thermostat ISU 0340 set to 3 or 4 the remote inside temperature is displayed on the Thermostat Home Screen as Inside Temperature The thermostat internal temperature sensor is not used The T7770A can be used to provide one remote sensor input or as a temp...

Page 22: ... or broken wire connection between thermostat and heating equipment Check for 24 Vac between the heat terminal W and transformer common If voltage is not present check wire connection loose or broken between the thermostat and the heating equipment Cooling does not turn on Cool On is solid in the display Cooling equipment failure Check for 24 Vac at the equipment on the secondary side of the trans...

Page 23: ...l System Type ISU 0170 is set to Heat Only or Heat Only with Fan Set System Type ISU 0170 to match the installed heating and or cooling equipment Heat On is not in the display System setting is not set to Heat and or temperature setting is not set above room temperature Set the system setting to Heat and set the temperature setting above the room temperature Cool On is not in the display System se...

Page 24: ...ed Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com TB7220 COMMERCIALPRO PROGRAMMABLE THERMOSTAT U S Registered Trademark 2011 Honeywell International Inc 63 2635 03 M S Rev 03 11 Printed in U S A ...

Reviews: