background image

® U.S. Registered Trademark
Copyright © 2002 Honeywell •  

 • All Rights Reserved 

INSTALLATION INSTRUCTIONS

69-1535-3

T8665A Chronotherm

®

 IV

 Deluxe Programmable

Wireless Thermostat

APPLICATION

The T8665 Chronotherm® IV Wireless Thermostat 
provides electronic control of 24 Vac heating and cooling 
systems. It must be used with a W8665 Receiver

Module. Refer to Table 1 for a general description of the 
thermostat. The T8665A Thermostats are battery-
powered.

MERCURY NOTICE

If this control is replacing a control that contains 
mercury in a sealed tube, do not place your old 
control in the trash.

Contact your local waste management authority 
for instructions regarding recycling and the 
proper disposal of the old thermostat.

INSTALLATION

Accessory Required (Not Included)

Select one of the receiver modules for your application:

— W8665A Receiver Module (RM) for single zone 

applications.

— W8665E RF Zone™ Panel for up to three zones.

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
the instructions can damage the product or cause 
a hazardous condition.

2.

Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After completing installation, use these instructions 
to check out the product operation.

Location

Install the thermostat about 5 ft (1.5m) above the floor in 
an area with good air circulation at average temperature. 
See Fig. 1.

Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall 

behind the thermostat.

Wallplate Installation

The thermostat can be mounted horizontally on the wall. 

1.

Position and level the wallplate (for appearance 
only). The thermostat functions correctly even 
when not level.

2.

Use a pencil to mark the mounting holes. See Fig. 
2.

3.

Remove the wallplate from the wall and drill two 
3/16 in. holes in the wall (if drywall) as marked. For 
firmer material such as plaster, drill two 7/32 in. 
holes. 

4.

Gently tap anchors (provided) into the drilled holes 
until flush with the wall.

5.

Position the wallplate over the holes.

6.

Loosely insert the mounting screws into the holes.

7.

Tighten the mounting screws.

Table 1. T8665A Thermostat Description.

T8665

System

Changeover

System Selection

Fan Selection

Comments

A

Heat-Cool

Automatic

Heat-Off-Cool-Auto

On-Auto

System and fan 
selections are entered at 
keyboard.

Summary of Contents for T8665A Chronotherm IV

Page 1: ...ur application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in c...

Page 2: ...nd wall plate See Fig 3 2 Press lower edge of case to close and latch NOTE To remove the thermostat from the wall first pull out at the bottom of the thermostat remove top last Fig 3 Mounting thermostat on wallplate 5 FEET 1 5 METERS YES NO NO NO M10106 WALL MOUNTING HOLES M20592 MOUNTING SCREWS WALL ANCHORS 2 M14628 PRESS LOWER EDGE OF CASE TO LATCH ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE ...

Page 3: ...p one zone at a time to ensure a unique address is used for each zone 1 Place the Zone 1 DIP switch on the W8665E Receiver to the On position NOTE Observe that the Zone 1 LED on the W8665 flashes 2 Press the thermostat Fan key to the On position The Receiver accepts the message stores the identity of that zone and stops flashing the Zone 1 LED The thermostat is now set up to send signals to Zone 1...

Page 4: ...he system fan as follows On Fan operates continuously Auto Fan operates with equipment Fig 6 Thermostat System and Fan key locations NOTE Always press the keys with your fingertip or sim ilar blunt tool Sharp instruments like a pen or pencil point can damage the keyboard Programmed Temperature Settings Refer to Table 2 for the default program If the daytime energy savings period is not used press ...

Page 5: ...r Setup press the Time V key To change a setting use the increase V or decrease W key To scroll the Installer Setup numbers backward press the Time W key To exit the Installer Setup press Run Program Fig 7 DIsplay of all LCD segments Fig 8 Display of Installer Setup number and settings CAUTION Equipment Damage Hazard Electric heat and heat pump systems must run with fan Configure to 1 in Installer...

Page 6: ...system starts early so setpoint is reached by start of program period 1 Conventional recovery system starts recovery at programmed time Degree temperature display 14 0 Temperature is displayed in F 1 Temperature is displayed in C Not used 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not used 17 and 18 Extended fan operation in heatinga 19 0 No extended fan operation after the c...

Page 7: ...ture display adjustment 37 0 No difference in displayed temperature and actual room temperature 3 thru 3 1 Display adjusts to 1 F higher than actual room temperature 2 Display adjusts to 2 F higher than actual room temperature 3 Display adjusts to 3 F higher than actual room temperature 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temp...

Page 8: ...umber of days remaining at any time by pressing the i key three or four times If more than one timer is active all active timers show sequentially when pressing the i key several times M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Set Day Time Mon PM M14620 Time Set Program System...

Page 9: ...r Time W and then the Run Program key to exit Table 4 Tests Available in Installer System Test Test Number System Test Description 10 19 Heating equipment can be turned on and off 30 39 Cooling equipment can be turned on and off 40 49 Fan equipment can be turned on and off 60 0 to 60 19 Keyboard keys test 70 79 Thermostat information including date code and software versions are displayed M14559 A...

Page 10: ... of the year example 027 February 1997 3 Press the increase key V again to display the soft ware identification code Example 02 software ID code 2 4 Press the increase key V again to display the software revision number example 001 revision number 1 5 Press the increase V key again to display the EEPROM identification code example 314 EEPROM ID 314 6 Press the Run Program key to exit the system te...

Page 11: ...signals Thermostat minimum off time is activated Wait up to five minutes for the system to respond System selection is not set to Heat Set system selection to Heat Heating setpoint is below room temperature Check heating setpoint Set heating setpoint to desired temperature Cooling does not come on Thermostat minimum off time is activated Wait up to five minutes for the system to respond Enter Inst...

Page 12: ...nable protection against such interference in a residential installation However there is no guarantee that interference will not occur in a particular installation If this equipment does cause interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures I...

Reviews: