Honeywell T8631A Installation Manual Download Page 5

When the batteries are low, the display will flash REPL

BAT. REPL BAT indication will disappear when thermo-
stat is mounted back on the powered subbase with fresh
batteries. This may take up to 15 minutes to occur.

If batteries are completely dead, the display will go

blank when the thermostat is removed from subbase.

MOUNTING THE THERMOSTAT

With system switch set to OFF, hang the thermostat on

the tabs at the top of the subbase.  See Fig. 10A. Swing
down and press on lower edge until thermostat snaps into
place.  See Fig. 10B. Open cover and tighten the captive
mounting screws.  See Fig. 10C.

SETTING DAY AND TIME

NOTE: Thermostat must be mounted on powered subbase

to program.

Restore 24V power to the thermostat. When power is

applied to the thermostat, the display will read 1:00 PM and
32

°

 for a minute or less, followed by 1:00 PM and room

temperature. It will go off for a few seconds, then begin to
flash on and off. Set present day and time.

Press

   .

Press                 to set the current day. Each press of

the DAY key advances the display one day.

Press TIME                     or                    to set the current time.

If the display will not come on:

— check mounting of thermostat to subbase. If loose

or misaligned, remove thermostat and reinstall on
the subbase, making sure it is firmly attached.

— check to see that system power is on.
— check to see that voltage between R and C is 20 to

30 Vac.

Fig. 10—Mounting the thermostat on subbase.

M3059

PM

RETURN

MON

HEAT ON

SYSTEM

AUTO

PM

RETURN

MON

HEAT ON

SYSTEM

RUN

PROGRAM

TIME

TEMPERATURE

PRESENT

SETTING

SKIP

NEXT

PERIOD

CHANGE
TO LAST

PERIOD

SET

PRESENT
DAY/TIME

HOLD
TEMP

DAY

SET

HEAT/COOL

SLEEP

LEAVE

AHEAD

WARMER

RETURN

BACK

COOLER

WAKE

A.

B.

C.

HEAT

AUTO

COOL

OFF

ON AUT

O

FAN

EM. HT

.

AUX. H

EAT

BACK

AHEAD

SET

PRESENT
DAY/TIME

DAY

5

69-0689—2

Checkout

CAUTION

During cold weather, some heat pumps will re-
quire that crankcase heater be energized several
hours before operating heat pump. Refer to
manufacturer’s recommendations.

HEATING

Move the system switch to HEAT and the fan switch to

AUTO. Press WARMER key until the setting is about
10

°

 F [6

°

 C] above room temperature. Heating should start

and the fan should run (there may be a delay of 5-10
minutes before heat turns on). Press COOLER key until the
setting is about 10

°

 F [6

°

 C] below room temperature. The

heating equipment and fan should shut off. The fan will run
a short time after equipment shuts off with T8631A unless
fan operation switch set for electric.

COOLING

CAUTION

Do not operate cooling if outdoor temperature is
below 50

°

 F [10

°

 C]. Refer to manufacturer’s

recommendations.

NOTE: When cooling setting is changed, thermostat can

wait up to five minutes before turning on the cooling
equipment. This delay is to protect the compressor.

!

!

Summary of Contents for T8631A

Page 1: ...tion is complete check out product operation as provided in these instructions 5 Allow thermostat to warm to room temperature before operating IMPORTANT Afterwiringiscomplete pushexcesswire back into the hole and plug hole with nonhardening caulk putty or insulation to prevent drafts from affecting thermostat operation LOCATION Install thermostat and subbase about 5 ft 1 5 m above the floor in an ...

Page 2: ...es Fig 1 Removing thermostat from subbase AUX HEAT HEAT AUTO COOL OFF ON AUTO FAN M3060 SYSTEM Fig 2 Mounting subbase on wall WIRES THROUGH WALL OPENING WALL WALL ANCHORS 2 SUBBASE MOUNTING HOLES MOUNTING SCREWS 2 M3061 HBUS SWITCH FAN OPERATIONAL SWITCH FOR T8631A ONLY 1 2 1 2 SWITCH UP DISCONNECTS THE HBUS FAN CAN BE SET FOR ELECTRIC HEAT OR CONVENTIONAL Fig 3 T8631A 1 stage heat 1 stage cool th...

Page 3: ...RELAY EMERGENCY HEAT RELAY STAGE 1 HEAT RELAY COMPRESSOR CONTACTOR E HIGH LIMIT L E HEAT HIGH LIMIT TRANSFORMER E HEAT RED AUX HEAT GREEN HEAT 2 M3065A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE JUMPER IF PRESENT FOR SYSTEM WITH ISOLATED STAGE 1 HEATING AND COOLING CONNECTIONS DENOTES THERMOSTAT TO SUBBASE INTERCONNECT DO NOT CONNECT H BUS WIRES TO THERMOSTAT ...

Page 4: ...naces it can be necessary to change the cycle rate to the hot water setting Cooling cycle rate is not adjustable but heating can be adjusted by turning one or both 1A and 1B screws on the back of the thermostat See Fig 8 for adjustments The screw should only be backed out about one half turn or be turned in until tight ADAPTIVE INTELLIGENT RECOVERY CON VENTIONAL RECOVERY CONVERSION The T8631A and ...

Page 5: ...check to see that system power is on check to see that voltage between R and C is 20 to 30 Vac Fig 10 Mounting the thermostat on subbase M3059 PM RETURN MON HEAT ON SYSTEM AUTO PM RETURN MON HEAT ON SYSTEM RUN PROGRAM TIME TEMPERATURE PRESENT SETTING SKIP NEXT PERIOD CHANGE TO LAST PERIOD SET PRESENT DAY TIME HOLD TEMP DAY SET HEAT COOL SLEEP LEAVE AHEAD WARMER RETURN BACK COOLER WAKE A B C HEAT A...

Page 6: ... AHEAD and BACK keys at the same time While holding keys down all segments of the display should be on See Fig 11 2 SetsystemswitchtoOFF PressAHEADandBACK and PRESENT SETTING keys at the same time to enter self test 3 Press each key as listed below and look for re sponses listed as key is held down and released Look For This Response Press This Key Key Down Key Released PRESENT SETTING 15 see note...

Page 7: ...O OWNER S MANUAL FOR PROGRAM MING INSTRUCTIONS AND HOMEOWNER TROUBLESHOOTING 7 69 0689 2 This equipment is a Class B digital apparatus which complies with Canadian Radio Interference Regulations CRC c 1374 CAUTION Do NOT operate cooling if outdoor temperature is below 50 F 10 C Refer to manufacturer s recommendations First press cooling system and SYSTEM LED on Second press cooling system and SYST...

Page 8: ...ding Control Home and Building Control Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley Minnesota 55422 Scarborough Ontario M1P 2V9 Printed in Taiwan R O C ...

Reviews: