Heating-Cooling Therm ostats

INSTALLATION  INSTRUCTIONS

APPLICATION

The T841A Thermostats provide 24 Vac control of two- 
stage heating and one-stage cooling in heat pump 
systems using manual changeover.

The T841A provides EM.HT.-HEAT-OFF-COOL system 
switching and AUTO-ON  fan switching.

Test holes are provided on the front of the thermostat to 
accommodate test meter leads without removing the 
thermostat from the wall.  Remove the cover of the 
thermostat to expose test holes that are labeled to 
correspond with the terminals on the back of the thermostat.

Table 1. Thermostat Features.

Thermostat

Terminal

Designations

LEDs

A uto Fan  in 

EM.  HT.

Figure

Numbers

T841A

W3, W2, Y,  G,  R,  E, X,  O,  B,  L

AUX.  HT.,  EM.  HT.,  CHECK

Yes

2

W3, W2, Y,  G,  R,  E, X,  O,  B,  L

AUX.  HT.,  EM.  HT.

Yes

3,  4

W, Y,  R,  T,  F,  G, X2,  O,  B

EM.  HT., AUX.  HT.

Yes

5

W3, W2, Y,  G,  R,  E, X,  O,  B

Yes

6

W3, W2, Y,  G,  R,  E, X,  O,  B

EM.  HT., AUX.  HT.

Yes

7

W2, W1, Y1,  G,  R,  E, X,  O,  B

EM.  HT., AUX.  HT.

Yes

8

W3, W2, Y,  G,  R,  E, X,  O,  B

EM.  HT., AUX.  HT.

Yes

9

W2, W1, Y,  G,  R,  K, Z, X

EM.  HT.,  SERVICE

No

10

W2, H, Y,  G,  R,  E, X, A,  O,  B

EM.  HT.,  COMP.  FAULT

No

11

W, Y,  G,  R, X,  O,  B

EM.  HT., AUX.  HT.

Yes

12

W2, W1, Y1,  G,  R,  E, X,  O,  B,  L

EM.  HT., AUX.  HT.

Yes

13

W2, W1, Y,  G,  R,  E,  C/X,  O,  B,

EM.  HT., AUX.  HT.

Yes

14

W, Y,  G,  R, T,  F, X2,  O,  B,  U

EM.  HT., AUX.  HT.

Yes

15

W2, Y,  G,  R,  E,  B, X

Yes

16

OPERATION

The stages of heat 

make

 sequentially as the temperature 

drops.  Make refers to the mercury switch initiating a call for 

heat or cool.

There is about  1 °F (0.6°C) between stages so the second 
stage (auxiliary heat)  makes only when the first stage 
cannot handle the load. This 1°F is the 

interstage

 

differential.

The light emitting diode (LED)  indicators on certain 
thermostat models light when something specific happens

within the system. The AUX.  HT.  LED lights when auxiliary 

heat (second stage heat)  is operating due to extremely 

cold weather that requires additional heat to supplement 
the heat pump. When the red  EM.  HT.  LED lights, the 
emergency heat is operating (usually electric strip 

heaters),  because the homeowner has physically switched 

to the  EM.  HT.  position. When the red CHECK LED lights, 

it indicates that something needs to be done to maintain 

efficient system operation.  See heating/cooling 

manufacturer's instructions for specific meaning. When the 

yellow COMP.  FAULT LED lights, a compressor problem 

requires attention. When the yellow SERVICE  LED lights, 

see heating/cooling manufacturer's instructions for specific 

meaning.

C o p y r i g h t   ©   1 9 9 8   H o n e y w e l l   In c .

A ll  R i g h t s   R e s e r v e d

69-1218

Summary of Contents for T841A

Page 1: ...W1 Y G R E C X O B EM HT AUX HT Yes 14 W Y G R T F X2 O B U EM HT AUX HT Yes 15 W2 Y G R E B X Yes 16 OPERATION The stages of heat make sequentially as the temperature drops Make refers to the mercury switch initiating a call for heat or cool There is about 1 F 0 6 C between stages so the second stage auxiliary heat makes only when the first stage cannot handle the load This 1 F is the interstage ...

Page 2: ...rage temperature Do not mount thermostat where it may be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas behind the thermostat such as an outside wall This thermostat is a precision instrument and was carefully adjusted at the factory Handle itcarefully Mounting and Wiri...

Page 3: ... w s at the m id d le o f the d evice 8 Install tw o s c re w s in the top m o u ntin g h o le s and tig hte n IMPORTANT An incorrectlyleveled subbase willcause the temperature control to deviate from setpoint It is not a calibrationproblem 9 R e place the th e rm o sta t cover ODT 1 L1 HOT L2 CHANGEOVER RELAY COOL POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTIONAS REQUIRED DO NOT JUM...

Page 4: ...Internal schematic and typical wiring diagram for T841A with EM HT and AUX HT LEDs Provides cool changeover relay control only Cool changeover O wire must be connected for proper operation Use L terminal for compressor malfunction indication 69 1218 4 ...

Page 5: ... for T841A with fan in Emergency Heat mode 2 stage heat 1 stage cool manual changeover L1 L2 HOT Fig 5 Internal schematic and typical wiring diagram for T841A with EM HT and AUX HT LEDs Provides outdoor reset when used with C815 Thermistor Provides cool changeover relay control 5 69 1218 ...

Page 6: ...JUMPER E TO W2 TERMINAL L1 L2 HOT W 3 a R W 2 AUX HT LED GREEN E a y RTD 1 ODT 1 J HhH T HHl EHR 1 RTD 2 ODT 2 m TEEh EHR 2 RTD y r m a t J VH A EM HT LED RED X h Y c EM HEAT RELAY A V H V CHANGEOVER VALVE HEAT COMPRESSOR CONTACTOR VH CHANGEOVER VALVE COOL T v Fig 7 Internal schematic and typical wiring diagram for T841A with AUX HT and EM HT LEDs Provides both heat and cool changeover relay contr...

Page 7: ... typical wiring diagram for T841A with AUX HT and EM HT LEDs Provides both heat and cool changeover relay control CHANGEOVER VALVE COOL Fig 9 Internal schematic and typical wiring diagram with AUX HT and EM HT LEDs Provides both heat and cool changeover relay control 7 69 1218 ...

Page 8: ...T841A HEATING COOLING THERMOSTATS FAN RELAY Fig 11 Internal schematic and typical wiring diagram for T841A with EM HT and COMP FAULT LEDs Common X wire must be connected for proper operation 69 1218 8 ...

Page 9: ...MOVE W1 Y1 JUMPER WHEN HEAT RELAY 1 IS USED WHEN L TERMINAL IS CONNECTED TO SYSTEM MONITOR EM HEAT LED ALSO INDICATES COMPRESSOR MALFUNCTION X TERMINAL MUST BE CONNECTED FOR PROPER OPERATION M1103C Fig 13 Internal schematic and typical wiring diagram for T841A with EM HT and AUX HT LEDs Provides both heat and cool changeover relay control 9 69 1218 ...

Page 10: ...ERMOSTATS L1 L2 Fig 14 T841A with two auxiliary heat stages and AUX HT and EM HT LEDs Provides auto fan in emergency heat Fig 15 T841A with EM HT and AUX HEAT LEDs Provides outdoor reset when used with C815 Thermistor 69 1218 10 ...

Page 11: ...cale System Switch Setting T h e s yste m s w itch in g p o sitio n s co ntro l the sys te m o p e ra tio n a s follow s EM HT T 8 4 1 A o n ly e m e rg e n c y h ea t re la y is e n e rg ize d C o oling s yste m is off C o m p re s s o r is d e e n e rg ize d Fan runs w ith call fo r h eat in A U T O position EM HT LE D is on H E A T h ea ting sy ste m is a u to m a tic a lly c o n tro lle d b y ...

Page 12: ...fan operation is controlled by the heating or cooling system control circuit Outdoor Reset Thermistor Honeywell C815A1005 For system shown in Fig 5 the thermistor must be used if not thermostat performance deviates radically from proper operation The proper thermostat operation must be verified to assure the correct operation of the thermostat Check thermistor operation as follows 1 Disconnect the...

Reviews: