PRODUCT DATA

Copyright © 1996 Honeywell Inc.   •            •   All Rights Reserved

T8141A

 Electronic Heat Pump Thermostats

APPLICATION

The T8141A Electronic Heat Pump thermostats provide low
voltage (24 Vac) control of two-stage heating and one-stage
cooling in single speed heat pump systems.

FEATURES

24 Vac, 60 Hz direct wired operation.

Manual heat-cool changeover.

Two heat, one cool output stages.

Setpoint temperature range 45

°

F to 90

°

F (7

°

C to 32

°

C)

for heating and 60

°

F to 95

°

F (16

°

C to 35

°

C) for cooling.

Retains setpoint temperature during power outage.

Cover thermometer.

Fan mode selection of AUTO, ON.

System mode selections of EM. HEAT, HEAT, OFF,
COOL (some models have EM. HEAT, GEO HEAT, OFF,
GEO COOL).

LED display for second stage AUX. HEAT operation.

LED display for EM. HEAT selection and external fault
indication (some models have GEO LOCK).

EM. HEAT LED can also be powered to light when the
heat pump shuts down.

Contents

Application ...........................................................................

1

Features ..............................................................................

1

Specifications ......................................................................

2

Ordering Information ...........................................................

2

Installation ...........................................................................

3

Setting .................................................................................

6

Operation ............................................................................

7

Checkout .............................................................................

7

Calibration ...........................................................................

7

Troubleshooting ..................................................................

8

68-0169-1

Summary of Contents for T8141A

Page 1: ...32 C for heating and 60 F to 95 F 16 C to 35 C for cooling Retains setpoint temperature during power outage Cover thermometer Fan mode selection of AUTO ON System mode selections of EM HEAT HEAT OFF COOL some models have EM HEAT GEO HEAT OFF GEO COOL LED display for second stage AUX HEAT operation LED display for EM HEAT selection and external fault indication some models have GEO LOCK EM HEAT LED...

Page 2: ...oducts from your contractor distributor or Honeywell sales representative please specify 1 Model number 2 Color choice for Heat or Cool changeover thermostat Cool Only changeover thermostat is only available in taupe 3 Thermostat changeover desired 4 System switches desired If you have additional questions need further information or would like to comment on our products or services please write o...

Page 3: ...behind the thermostat If Replacing an Existing Thermostat A Turn off the thermostat power at the heat pump In two transformer systems with two switches or disconnects turn off power to both B Remove any existing wallplate or subbase from the wall C To avoid miswiring later as the wire is removed label or write down each wire color with the letter or number on the wiring terminal If New Installatio...

Page 4: ...thermostat UP WALL MOUNTING SCREW M5948B TERMINAL STRIP TERMINAL WIRES FAN SWITCH SYSTEM SWITCH TEMPERATURE SETPOINT TEMPERATURE CONTROL DIAL 1 1 2 SNAP THE THERMOSTAT INTO THE TOP HINGES ON THE MOUNTING PLATE M8552 TERMINAL STRIP TERMINAL WIRES THERMOSTAT CABLE OPENINGS FOR STRAIGHT INSERTION STRIP 5 16 IN 8 MM FOR WRAPAROUND STRIP 7 16 IN 11 MM RESTRICT WIRING TO THIS AREA FRONT VIEW OF TERMINAL...

Page 5: ...RELAY AUX HEAT RELAY COOL CHANGEOVER VALVE B HEAT CHANGEOVER VALVE L SYSTEM MONITOR M7777A E H O O C E H O C E H O C E H O C A EM HEAT HEAT OFF COOL SYSTEM SWITCH FAN SWITCH ON AUTO EM HEAT RED AUX HEAT GREEN FAN COMPRESSOR HEAT RELAY AUX HEAT RELAY THERMOSTAT LOGIC POWER SUPPLY TEMPERATURE SENSOR INTERNAL SYSTEM SWITCHES DESIGNATED AS E EM HEAT H HEAT O OFF C COOL INTERNAL FAN SWITCHES DESIGNATED...

Page 6: ...nt during a power outage Temperature Setting Move the temperature control dial to the desired temperatures for heating and for cooling See Fig 7 System and Fan Switching System switch positions control thermostat operation as follows OFF Heating and cooling are off If the fan switch is in the AUTO position the cooling fan is also off HEAT or GEO HEAT Heating system is controlled by the thermostat ...

Page 7: ...ature Cooling NOTE When the cooling setting is changed a minimum off timer delays the compressor from starting or stopping the heat pump for at least five minutes A Set the thermostat system switch to COOL or GEO COOL and the fan switch to AUTO B Set the temperature to about 10 F 6 C below the room temperature C Cooling and fan should start after a delay D Change the temperature setting to about 1...

Page 8: ... the COOL position If the air conditioner comes on compressor could have reached its high limit temperature protection and shut down If cooling still does not start and the fault indicator is connected to terminal L and the EM HEAT indicator is on contact the Original Equipment Manufacturer or your HVAC dealer If the EM HEAT indicator is off contact Honeywell Customer Assistance at 1 800 468 1502 ...

Reviews: