NOTE: The T8132C Thermostat does not have a setting for

steam/gravity air. Cycles would not be long enough for
accurate temperature control.

IMPORTANT: When using a high efficiency furnace such

as a 90% or greater Average Fuel Utilization Effi-
ciency (AFUE) unit, adjust screw A out one turn and
screw B in.

TABLE 2—BURNER ON-TIME ADJUSTMENTS.

If you want a longer on-time, readjust the screws as

follows (refer to the heating system table in Fig. 7):

If the burner on-time
screws A,B are adjusted
to match this system:

Then for longer burner
on-time,  readjust
screws A,B to match this
system:

Electric furnace

Warm air furnace

Warm air furnace

Hot water boiler

Fig. 7—T8132C Thermostat back.

R

Rc

W      Y      G

B               D

A               C

THERMOSTAT BACK

M1708B

DISPLAY °F

DISPLAY °C

C–IN

C–OUT

1 TURN

FOR HIGH EFFICIENCY FURNACE (90%+ AFUE)

ADJUST: SCREW A–OUT ONE TURN

SCREW B–IN
FUEL SWITCH – F POSITION

F

E

FUEL SWITCH

WARM AIR
FURNACE
HOT WATER
BOILER
ELECTRIC 
FURNACE

A–IN

A–OUT
1 TURN
A–IN

ADJUST SCREWS THROUGH HOLES
TO SELECT OPERATION DESIRED

B–IN

B–IN

B–OUT
1 TURN

FUEL SWITCH

POSITION

F

F

E

HEATING SYSTEM

INSTALL BATTERIES

IMPORTANT: Batteries must be installed for program-

ming and operation of the thermostat and heating/
cooling system.

Use two AA alkaline batteries; nonalkaline batteries do

not last as long. We recommend Energizer

®

 batteries.

Make sure the thermostat is set to OFF position.
Use a coin to remove battery door (see Fig. 8).
Install the fresh batteries as shown, making sure positive

and negative terminals are oriented correctly (see Fig. 9).

Replace battery door.

Fig. 9—Installing position for batteries.

M1719C

REMOVING
BATTERY
DOOR

Fig. 8—Removing battery door.

As the batteries are running low, a 

bAt  Lo

 indicator

flashes for one to two months before batteries run out
completely. Replace the batteries as soon as possible after
the indicator starts flashing. If the batteries are not replaced
while the 

bAt Lo

 indicator is flashing, the indicator eventu-

ally stops flashing. When the batteries are almost com-

INSTALL TWO AA ALKALINE 
BATTERIES AS SHOWN

M1713

pletely dead, 

bAt Lo

 stays on without flashing to indicate

the thermostat and heating/cooling system have stopped
working.

After the batteries are completely dead, the 

bAt  Lo

indicator disappears, leaving a completely blank display.

Press down on left ends of batteries to remove. If the

new batteries are inserted within 20 to 30 seconds of
removing the old ones, the thermostat will not require
reprogramming. However, if the display is blank, the bat-
teries are dead or incorrectly installed and require repro-
gramming. See Owner’s manual to reprogram.

IMPORTANT: Although the thermostat has a low battery

indicator, replace the batteries once a year to pre-
vent the thermostat and heating/cooling system from
shutting down due to lack of battery power.

MOUNTING THE THERMOSTAT

To mount the thermostat on the subbase, engage the tabs

at the top of the thermostat and mounting plate (see Fig. 10)
and then press the lower edge of the case to latch.

Summary of Contents for T8132C

Page 1: ...L WIRES THROUGH WALL OPENING WALL ANCHORS 2 MOUNTING PLATE MOUNTING SCREWS 2 M1718 WIRING All wiring must comply with all applicable electrical codes ordinances and regulations Follow instructions provided with the controlled equipment Run the required number of wires to the thermostat location check the appropriate wiring diagram Refer to Fig 3 through 6 for typical wiring diagrams In 5 wire inst...

Page 2: ...R VALVE COIL 1 1 Fig 6 3 wire cool only application jumper intact R Rc W Y G B D A C 3 WIRE COOL ONLY JUMPER INTACT L1 HOT L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 JUMPER M848A COOLING CONTACTOR COIL FAN RELAY ADJUST FAN OPERATION SWITCH AS REQUIRED The thermostat fan operation switch labeled FUEL SWITCH see Fig 7 is factory set in the F position This is the c...

Page 3: ... battery door see Fig 8 Install the fresh batteries as shown making sure positive and negative terminals are oriented correctly see Fig 9 Replace battery door Fig 9 Installing position for batteries M1719C REMOVING BATTERY DOOR Fig 8 Removing battery door As the batteries are running low a bAt Lo indicator flashes for one to two months before batteries run out completely Replace the batteries as s...

Page 4: ...ove room temperature After a short delay heating should start and the fan should run immediately if fan operation switch is set in E position Press key until setting is about 10 F 6 C below room temperature The heating equipment should shut off Cooling To avoid possible compressor damage do not operate the cooling system when outside temperature is below 50 F 10 C See compressor manufacturer instr...

Page 5: ...or higher 45 F to 88 F than 88 F 31 C during programming Heating will not come on Check that switch on thermostat is set to HEAT Check the system fuse or circuit breaker and replace or reset if necessary If display is blank or displays bAt Lo install fresh batteries If temperature setting is higher than current temperature and SYSTEM ON indicator is lit see furnace manufacturer instructions Coolin...

Page 6: ...uently The burner on time Readjust according to instructions on page 2 is too short or too long IF THEN The thermostat current setting does Check that the wiring hole in the wall behind the wallplate was not match the display temperature plugged with insulation to prevent drafts that might adversely affect thermostat operation Be aware that it is normal for the current setting and display temperat...

Reviews: