background image

® U.S. Registered Trademark
© 2003 Honeywell International Inc.  •  

  • All Rights Reserved 

INSTALLATION INSTRUCTIONS

69-1160B-1

T810D; TS810B Heating

 Thermostats

APPLICATION

The T810D and TS810B are low voltage, spst controls 
for heating systems.

The T810D is for 24 Vac control of heating-only systems. 
The TS810B can control 750mV circuits.

A positive Off feature is available on the TS810B and 
select T810D models.

Heat anticipation is fixed in most models. The current 
rating is stamped on the thermostat. TheT810D has an 
adjustable heat anticipator rating of 0.18A to 0.8A at 
30 Vac. See Fig. 1.

MERCURY NOTICE

If this control is replacing a control that contains 
mercury in a sealed tube, do not place your old 
control in the trash.

Contact your local waste management authority 
for instructions regarding recycling and the 
proper disposal of the old thermostat.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition.

2.

Check the ratings given in the Instructions and on 
the product to make sure the product is suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

CAUTION

Electrical Hazard.    
Can cause personal shock or equipment 
damage.

Disconnect power supply before beginning 
installation.

Location

Locate the thermostat about 5 ft (1.5m) above the floor in 
an area with good air circulation at average temperature.

Do not mount the thermostat where it can be affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall 

behind the thermostat

IMPORTANT

This is a precision instrument. Rough handling 
can decrease its accuracy. Handle it carefully.

The wiring run for TS810B millivolt systems should be 
kept as short as possible.

Summary of Contents for T810D

Page 1: ...ad these instructions carefully Failure to follow them could damage the product or cause a hazard ous condition 2 Check the ratings given in the Instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION E...

Page 2: ...mounting holes at each side of the device See Fig 1 Level the thermostat for best appearance 6 Replace the thermostat cover Fig 2 T810D in typical gas heating system Fig 3 Typical hookup for TS810B in millivolt system Fig 4 Internal schematic for all standard and positive Off heating models Table 1 Maximum Wiring Length Wire Size Maximum Length 2 Wire Cable Maximum Combined Length 2 Single Wires f...

Page 3: ...to a low setting so the contacts are broken In cold weather it may be necessary to hold the switch so the controls remain open Allow the system to operate through the ammeter for one minute Adjust the anticipator to match the meter reading NOTE For best performance the heat anticipator can require further adjustment To lengthen burner on time move the indicator in the direction of the longer arrow...

Page 4: ...l com yourhome T810D TS810B HEATING THERMOSTATS Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Page 5: ...entes instructions Le fait de ne pas les suivre risque d endommager le produit ou pourrait constituer un danger 2 Vérifier les caractéristiques nominales indiquées dans les instructions et sur le produit et s assurer que l appareil convient à l application prévue 3 L installateur doit être un technicien d expérience ayant reçu une formation pertinente 4 Une fois l installation terminée vérifier le...

Page 6: ...au le thermostat à des fins esthétiques 6 Remettre le couvercle sur le thermostat Fig 2 Le T810D dans un système type de chauffage au gaz Fig 3 Raccordement type du TS810B dans un système à tension millivolt Fig 4 Schéma interne pour tous les modèles pour chauffage standard et à coupure à OFF Tableau 1 Longuer maximale des fils Calibre de fils Longueur maximum Câble bifilaire Longueur combinee max...

Page 7: ...pérature suffisamment basse pour couper les contacts Par temps froid il faut parfois tenir les contacts pour que les commandes restent ouvertes Faire fonctionner le système en laissant l ampèremètre branché pendant une minute Régler l anticipateur pour qu il indique la même grandeur que celle de l ampèremètre REMARQUE Pour un meilleur rendement il est parfois nécessaire d effectuer d autres réglag...

Page 8: ...rhome THERMOSTATS DE CHAUFFAGE T810D ET TS810B Solutions de régulation et d automatisation Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...