69-0219-9    G.H.  Rev.  1-03 

www.honeywell.com/yourhome

Automation and Control Solutions

Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN  55422

Scarborough, Ontario
M1V 4Z9

Checkout

CAUTION

Equipment Damage Hazard. 
Shorting across system terminals can 
damage heat anticipator.

Do not check operation by shorting across 
system controls terminals.

IMPORTANT

To assure accurate temperature control, do not 
touch or breathe on bimetal of thermometer.

Observe the system through at least one complete 
automatic cycle. Be sure the system operates as 
intended. Check for correct operation of the positive Off 
switch as used.

Calibration

This thermostat is carefully calibrated at the factory and 
should not require field adjustment. If the thermostat 
appears to be out of adjustment, check as follows:

1.

Move the temperature setting lever to the lowest 
end setting on the temperature scale. Do not move 
the lever all the way to Off on models with positive 
Off switch. Wait at least five minutes.

2.

Remove the thermostat cover. Slowly move the 
temperature lever until the snap switch just makes 
contact.

3.

Replace the cover and wait five minutes for the 
cover and the thermostat to lose the heat gained 
from your hands. If the thermometer pointer and 
the setting lever indicator read approximately the 
same, no recalibration is needed.

If thermostat needs recalibration, order part no. 104994A 
Open-end Wrench. Follow the recalibration instructions 
included with the wrench.

Summary of Contents for T810C

Page 1: ...the old thermostat INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazard ous condition 2 Check the ratings given in the Instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check ...

Page 2: ...y control in the system See Heat Anticipator Setting T810D sec tion 5 Fasten the thermostat to the wall or outlet box with screws through the mounting holes at each side of the device See Fig 1 or 2 Level the thermostat for best appearance 6 Replace the thermostat cover Fig 3 T810D in typical gas heating system M8502A MOUNTING HOLES THERMOSTAT TO WALL OR OUTLET BOX TEMPERATURE SETTING LEVER MOUNTI...

Page 3: ...rmance The rating of the primary control is stamped on the control nameplate To adjust move the anticipator indicator lever to correspond to the control rating If the setting and current rating are not available wire the thermostat into the system but do not attach it to the wall If the thermostat is already mounted remove it from the wall leaving it connected to the system wiring Connect an ammet...

Page 4: ...ive Off switch as used Calibration This thermostat is carefully calibrated at the factory and should not require field adjustment If the thermostat appears to be out of adjustment check as follows 1 Move the temperature setting lever to the lowest end setting on the temperature scale Do not move the lever all the way to Off on models with positive Off switch Wait at least five minutes 2 Remove the...