APPLICATION

The T810C,D and TS810B are low voltage, spst controls 
for heating or cooling systems.

The T810C is for 24 Vac, cooling-only systems. The 
T810D is for 24 Vac control of heating-only systems. The 
TS810B can control 750 mV circuits.

Heat anticipation is fixed in most models. The current 
rating is stamped on the thermostat. The T810D has an 
adjustable heat anticipator rating of either 0.18A to 0.8A 
or 0.32A to 1.2A at 30 Vac (depending on model). See 
Fig. 1 or 2.

A positive Off feature is available on the TS810B and 
select T810D models.

MERCURY NOTICE

If this control is replacing a control that contains 
mercury in a sealed tube, do not place your old 
control in the trash.

Contact your local waste management authority 
for instructions regarding recycling and the 
proper disposal of the old thermostat.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition.

2.

Check the ratings given in the Instructions and on 
the product to make sure the product is suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out product 
operation as provided in these Instructions.

CAUTION

Electrical Hazard. 
Can cause electrical shock or equipment 
damage.

Disconnect power supply before beginning 
installation.

Location

Locate the thermostat about 5 ft (1.5m) above the floor in 
an area with good air circulation at average temperature.

Do not mount the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners. 
— hot or cold air from ducts.
— radiant heat from the sun or appliances. 
— concealed pipes and chimneys.
— unheated (uncooled) areas such as outside wall 

behind the thermostat.

This is a precision instrument. Rough handling can 
decrease its accuracy. Handle it carefully.

Be sure to keep the wiring run for TS810B millivolt 
systems as short as possible.

Summary of Contents for T810C

Page 1: ...the old thermostat INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazard ous condition 2 Check the ratings given in the Instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check ...

Page 2: ...y control in the system See Heat Anticipator Setting T810D sec tion 5 Fasten the thermostat to the wall or outlet box with screws through the mounting holes at each side of the device See Fig 1 or 2 Level the thermostat for best appearance 6 Replace the thermostat cover Fig 3 T810D in typical gas heating system M8502A MOUNTING HOLES THERMOSTAT TO WALL OR OUTLET BOX TEMPERATURE SETTING LEVER MOUNTI...

Page 3: ...rmance The rating of the primary control is stamped on the control nameplate To adjust move the anticipator indicator lever to correspond to the control rating If the setting and current rating are not available wire the thermostat into the system but do not attach it to the wall If the thermostat is already mounted remove it from the wall leaving it connected to the system wiring Connect an ammet...

Page 4: ...ive Off switch as used Calibration This thermostat is carefully calibrated at the factory and should not require field adjustment If the thermostat appears to be out of adjustment check as follows 1 Move the temperature setting lever to the lowest end setting on the temperature scale Do not move the lever all the way to Off on models with positive Off switch Wait at least five minutes 2 Remove the...