Honeywell T8034C Installation Instructions Manual Download Page 6

69-1598

6

T8034C HEATING/COOLING THERMOSTATS

Automation and Control Solutions
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive Road
Scarborough, Ontario
M1V 4Z9

69-1598   G.H.   11-01

Automation and Control Solutions
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422

Printed in U.S.A. on recycled 
paper containing at least 10% 
post-consumer paper fibers.

CALIBRATION
WRENCH

COIL SHOWN WITHOUT
HEAT ANTICIPATOR

M2044A

CHECKOUT

CAUTION

Can cause damage to heat anticipator.

Do not check operation by shorting across
terminals of system controls.

IMPORTANT

To assure accurate temperature control, do not
touch or breathe on bimetal or thermometer.

Heating

With system switch set at HEAT and fan switch at AUTO,
move the temperature setting lever about 10

°

F (6

°

C)

above the room temperature. In standard systems, the
heating should start and the fan should start after a short
delay. In heat pump or electric heat systems, both the
heating and fan should start.

Move the temperature setting lever about 10

°

F (6

°

C)

below the room temperature. In standard systems, the
heating should shut off and the fan should shut off after a
short delay. In heat pump or electric heat systems, both
the heating and fan should shut off.

COOLING

CAUTION

Can cause damage to compressor.

Do not operate cooling if outdoor temperature is
below 50

°

F (10

°

C). Refer to manufacturer recom-

mendations.

NOTE:

To prevent compressor short cycling, some
manufacturer equipment includes a minimum off-
timer to provide a five-minute time delay before
activating the compressor when the thermostat
last turned the compressor off, or from when the
system first received power. This delay protects
the compressor.

With the system switch set at COOL and fan switch at
AUTO, move the temperature setting lever about 10

°

F

(6

°

C) below the room temperature. Cooling and fan should

start (see NOTE in COOLING section). Move the tempera-
ture setting lever about 10

°

F (6

°

C) above the room

temperature. Cooling and fan should shut off.

Fan

With the system switch set at OFF, and the fan switch at
ON, the fan should run continuously. Move the fan switch
to AUTO. In standard systems, fan operation is controlled
by the plenum fan control in heating and by the thermostat
in cooling. In heat pump or electric heat systems, fan
operation is controlled by the thermostat in heating and
cooling.

Recalibration

These thermostats are calibrated at the factory and should
not need recalibration. If the thermostat needs adjustment,
first check for accurate leveling.

To check calibration:

1.

Move the temperature setting lever to the lower end
of the temperature scale. System switch must be
placed in the OFF position. Wait at least five
minutes.

2.

Remove the thermostat cover. Move the setting
lever until the switch just makes contact. The
mercury in the switch rolls to the left end of the tube.

3.

Replace the cover and wait five minutes for the
cover and the thermostat to lose the heat gained
from your hands. If the thermometer pointer and the
setting lever indicator read approximately the same,
no recalibration is needed.

If recalibration is necessary:

1.

Place the temperature setting lever at the same
setting as the thermometer. Remove the cover by
pulling outward on right edge of cover until it snaps
free of the thermostat base.

2.

Insert 104994A Calibration Wrench (ordered
separately) onto the hex nut under the coil. See
Fig. 9. Hold the setting lever so it does not move and
turn the wrench clockwise           until the mercury
rolls to the right end of the tube. Remove the wrench
and replace the cover.

NOTE:

To assure accurate temperature control, do
not touch or breathe on bimetal or ther-
mometer.

3.

Move the setting lever to a low setting. Wait at least
five minutes for the temperature to stabilize.

4.

Slowly move the setting lever until it reads the same
as the thermometer.

5.

Remove the cover. Hold the setting lever so it does
not move, reinsert the wrench and carefully turn
counterclockwise           until the mercury rolls to the
left end of the tube, but 

no farther

.

6.

Recheck the calibration. Set the thermostat system
switch for the desired operation and replace the
cover.

Fig. 9. Recalibration procedure.

www.honeywell.com/yourhome

Summary of Contents for T8034C

Page 1: ...eck the ratings given in the Instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these Instructions CAUTION Can cause electrical shock or equipment damage Disconnect power supply before beginning installation Location Locate ...

Page 2: ... and discard the foam plastic shipping insert that protects the switch and bimetal assembly during shipping 5 Set the adjustable heat anticipator indicator to match the current draw of the primary heating control see Heat Anticipator Setting 6 Push excess wire back through the hole and plug any opening with insulation to prevent drafts that may affect thermostat performance 7 Loosely fasten the th...

Page 3: ...N AUTO COOL OFF HEAT COOL OFF HEAT SYSTEM SWITCH C1 ANTICIPATOR H1 ANTICIPATOR M1034F W 2 1 Y G R Fig 5 Internal schematic and typical hookup for T8034C in gas or oil fired or central electric heat systems M2297 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED DEFROST RELAY SYSTEM SWITCH HEAT OFF COOL FAN SWITCH AUTO ON H1 TEMP FALL C1 ANTICIPATOR FAN RELAY HEAT OFF COOL C...

Page 4: ...ONNECTED THERMOSTAT WITH NOT ENERGIZE FAN IN AUTO POSITION JUMPER W Y FOR SINGLE STAGE HEAT PUMP APPLICATIONS HEAT RELAY FAN RELAY FAN SWITCH ON AUTO COOL OFF HEAT COOL OFF HEAT SYSTEM SWITCH C1 ANTICIPATOR H1 ANTICIPATOR M2323C W Y B O 2 G 1 R CHANGEOVER RELAY HEAT CHANGEOVER RELAY COOL COMPRESSOR RELAY Fig 8 Internal schematic and typical hookup for T8034C in single transformer heating cooling s...

Page 5: ... C1 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED HEAT RELAY FAN RELAY FAN SWITCH ON AUTO COOL OFF HEAT COOL OFF HEAT SYSTEM SWITCH C1 ANTICIPATOR H1 ANTICIPATOR M13313 B O W Y G R L1 HOT L2 1 CHANGEOVER RELAY HEAT CHANGEOVER RELAY COOL COMPRESSOR RELAY 5 4 If the current rating is not available 1 Turn off the power 2 Wire the thermostat but do not mount it on the wal...

Page 6: ... With the system switch set at OFF and the fan switch at ON the fan should run continuously Move the fan switch to AUTO In standard systems fan operation is controlled by the plenum fan control in heating and by the thermostat in cooling In heat pump or electric heat systems fan operation is controlled by the thermostat in heating and cooling Recalibration These thermostats are calibrated at the f...

Reviews: