T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS 

SPECIFICATIONS 

IMPORTANT

 

The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not 

exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, 

and some minor differences in performance can be expected if those conditions are changed. 

MODELS: T7984A,B,C, 2 to 10 Vdc analog output 

Table 1. Model Specifications 

Model 

Output 1 

Cool/Heat

Changeover

For Output 1 

Output 2 

Night Setback 

Main 

Temperature 

Sensor * 

Mode Selection 

Input 

T7984A 

Modulating 2 to 

10 Vdc 

Dry Contact or 

Sensor 

On/off 

-

Internal or 

remote 

-

T7984B 

Modulating 2 to 

10 Vdc 

-

-

Dry Contact 

Internal or 

remote 

Jumper 

T7984C 

Modulating 2 to 

10 Vdc 

Dry Contact or 

Sensor 

Modulating 2 to 

10 Vdc 

Dry Contact 

Internal or 

remote 

-

* Remote sensor models are: 

272845 Remote wall mount sensor 

272847 Remote duct mount sensor 

DIMENSIONS 

See Figure 1. 

MOUNTING: 

Mounts to single-gang NEMA-standard 2"x 4" 

electrical box, or directly to wall requires 1 1/8“ [35„mm] 

access hole for wiring. 

WIRING: 

Four to eight 1/8“ screw terminals suitable for 2 no. 

18 AWG [1 mm 2] wires each depending on model. 

POWER SUPPLY: 

19-30 Vac, 50-60 Hz, 2 VA, Class 2. (Does 

not include actuator or reheat stage power requirements.) 

OPERATING AMBIENT: 

32-104°F [0-40°C] at 5-95% Relative Humidity (non-

condensing). 

ACCURACY: 

1°F (0.6°C) PRECISION: ±1°F (0.5°C) tempera-

ture after stabilization. 

PRECISION: 

±1°F (0.5°C) temperature after stabilization. 

SETPOINT RANGE: 

55-90°F [13-32°C], T7984A. 

Heating: 

55-75°F [13-24°C], T7984B, C*. 

Cooling: 

75-90°F [24-32°C], T7984B, C*.

ORDERING INFORMATION 

* The maximum heating setpoint and minimum cooling 

setpoint is electronically limited to 75°F [24°C]. 

REMOTE SENSOR: 

47 k

 NTC thermistor [part nos. 272845 

and 272847]. 

ANALOG OUTPUT: 

2 to 10 Vdc, 2 mA max. 

SWITCHED OUTPUT RATING: 

0.5A running, 1.1A inrush, 

24Vac, protected with selfresetting fuse. 

OPERATING PARAMETERS: 

See Table 2 for installer selections.

 APPROVALS: 

Designed for Class II low voltage installation only. 

Case and cover meets UL„94-5V flammability requirements, 

and North American codes for line voltage thermostat 

enclosures. 

Meets requirements of F.C.C. Part 15 Class B, IEC 801-3 for 

radio frequency interference. 

ACCESSORIES: 

272845 - Remote sensor (wall mounted). 

272846 - Adaptor plate for 2-gang NEMA, or British 75 mm 

electrical box.

 272847 - Remote sensor (duct mounted). 

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number. 

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone: 

1.

  

Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 

2.

  

Honeywell Customer Care

 

1885 Douglas Drive North

 

Minneapolis, Minnesota 55422-4386

 

In Canada–Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.

 

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

 

95C-10815–2

  

Summary of Contents for T7984 A

Page 1: ...lve actuators such as ML7285 ML7421 VC7930 or M7410 All models feature user friendly set point knob All models feature output status LEDs for installer check out Locking cover and range stops are standard Night setback models feature selection of two different offset temperatures and use central time switch control Night setback models feature 2 1 2 hour local timed override Heat cool models featu...

Page 2: ...lization SETPOINT RANGE 55 90 F 13 32 C T7984A Heating 55 75 F 13 24 C T7984B C Cooling 75 90 F 24 32 C T7984B C ORDERING INFORMATION The maximum heating setpoint and minimum cooling setpoint is electronically limited to 75 F 24 C REMOTE SENSOR 47 kΩ NTC thermistor part nos 272845 and 272847 ANALOG OUTPUT 2 to 10 Vdc 2 mA max SWITCHED OUTPUT RATING 0 5A running 1 1A inrush 24Vac protected with sel...

Page 3: ...hermostats must be configured for proper operation by setting DIP switches T7984B Reheat output control action 7 5 or 15 minutes T7984B C Zero energy band ZEB 3 F 2 C or 5 F 3 C Setpoint adjustment cooling centred heating centred with limit override for commissioning Night setback amount see Table 2 for complete listing of option settings T7984A B C Main sensor internal or remote Table 3 T7984 DIP...

Page 4: ...act or the changeover sensor across Fig 2 T7984A Wiring Input 2 10 Vdc 24 Vac Common 2 10 Vdc valve or VAV analog actuator Duct or Room Not used Remote sensor input 0 Vac Output 1 2 10 Vdc Changeover input for Out 1 Changeover contact OR Changeover sensor 24 Vac Power supply 0 Vac 24 Vac Transformer SEQUENCE SETPOINT DIAL CENTERED End Heating mode End Opened Cooling mode Device Device changeover 1...

Page 5: ... Device closed off 2 Vdc 0 OUTPUT 2 ON OFF OUTPUT 1 ANALOG ZERO ENERGY BAND Temperature increase Fig 6 T7984B Sequence Mode A DIP SWITCH SETTINGS DEFINITION S3 S4 75 F OVERRIDE 1 1 HEATING DIAL 0 1 COOLING DIAL 1 0 CENTERED HC 0 0 SETPOINT DIAL DEFINITION ZEB S2 5 F 3 C 3 F 1 5 C 1 0 ZERO ENERGY BAND CYCLES HOUR S1 FAST 8 CPH 1 SLOW 4 CPH 0 OUTPUT 2 ON OFF CPH ON 1 1 2 3 4 5 6 OFF 0 COOLING SETPOI...

Page 6: ... valve or VAV analog actuator 24 Vac Transformer Fig 9 T7984C Wiring SEQUENCE SETPOINT DIAL DEFINITION SETPOINT DIAL DEFINITION SETPOINT SETPOINT HEATING COOLING HEATING COOLING SETPOINT CENTERED SETPOINT SETPOINT CENTERED End End Device closed 2 Vdc IN ZERO ENERGY BAND OUTPUT 2 ANALOG OUTPUT 1 ANALOG SETPOINT End IN ZERO End End Device Device 100 ENERGY BAND 100 Device Device opened 10 Vdc 50 End...

Page 7: ...model on how to wire the sensor The remote sensor are not to be used for supply control applications Zero Energy Band T7984B C Thermostats which have cooling and heating outputs T7984B C have 2 distinct setpoints one for heating the other for cooling see the control curves section for each model When the room temperature is between these to setpoints both heating and cooling outputs are off and th...

Page 8: ...ctuator or SCR power controller which is normally used to control terminal reheat in a zone system This type of output on the T7984C uses a half wave rectifier bridge If the same transformer is to be used for the thermostat and the end device be sure to select end devices which also use a half wave rectifier bridge There is a status LED mounted internally that indicates the action of the output Th...