T7771A REMOTE TEMPERATURE SENSOR

3

63-2617

Fig. 3. Releasing/replacing terminal block.

INSTALLATION

CAUTION

Equipment Damage Hazard.

Electrostatic discharge can short equipment 

circuitry.

Ensure that you are properly grounded before 

handling the unit.

Touch only the plastic cover, casing, and buttons.

Mount the T7771A Wall Module on an inside wall 

approximately 54 in. (1372 mm) from the floor (or in the 

specified location) to allow exposure to the average zone 

temperature. Do not mount the wall module on an outside 

wall, on a wall containing waterpipes or near air ducts. Avoid 

locations that are exposed to discharge air from registers or 

radiation from lights, appliances, or the sun.

The wall module can be mounted on a wall, on a standard 

utility conduit box using No. 6 (3.5 mm) screws or on a 60 mm 

wall outlet box (see Fig. 5). When mounting directly on a wall, 

use the type of screws appropriate for the wall material.

NOTE: See Fig. 4 for subbase mounting dimensions.

Fig. 4. T7771A Subbase dimensions in in. (mm).

Fig. 5. Mounting wall modules on standard utility 

conduit box or 60 mm wall outlet box.

Wiring

Attach the wires from the device sensor terminals to the 

appropriate wall module terminals. See Fig. 6.

CAUTION

Improper Electrical Contact Hazard.

Screw type terminal blocks are designed to accept 

no more than one 14 AWG (2.5 sq mm) conductor.

Connect multiple wires that are 14 AWG (2.5 sq mm) 

with a wire nut. Include a pigtail with this wire group 

and attach the pigtail to the individual terminal block.

Wire the terminal blocks as follows:

1.

For single wires, strip 3/16 in. (5 mm); for multiple wires 

going into one terminal, strip 1/2 in. (13 mm) insulation 

from the conductor.

2.

If two or more wires are being inserted into one 

terminal, twist the wires together before inserting.

NOTE: When two or more wires are being inserted 

into one terminal, be sure to twist them 

together. Deviation from this rule can result 

in improper electrical contact. See Fig. 9.

3.

Insert the wire in the required terminal location and 

tighten the screw to complete the termination.

4.

Verify wall module wiring with Fig. 6.

NOTE: Wire the E-Bus using Level IV 22 AWG (0.34 sq mm) 

plenum or non-plenum rated, unshielded, twisted 

pair, solid conductor wire.

M17988

PRESS SHADED AREA 
OF TAB WITH THUMB TO 
RELEASE TERMINAL BLOCK 
FOR EASIER WIRING

On/Off

Normal

Cooler

Warmer

Temperature Control

15/16 

(23)

M22174

3-3/16 (80)

5-1/16

(128)

KNOCKOUTS FOR 
EUROPEAN APPLICATIONS

2-3/8 (60)

2-3/8

(60)

STANDARD

UTILITY

CONDUIT

BOX (2 X 4)
MOUNTING

HOLES

M22173

STANDARD UTILITY 
CONDUIT BOX

SUBBASE

NO. 6 SCREW

60 mm WALL
OUTLET BOX

SUBBASE

3.5 mm SCREW

FRONT COVER

FRONT COVER

On/Of

f

Normal

Cooler

Wa

rm

er

Temperatur

e Control

On/Of

f

Normal

Cool

er

Wa

rm

er

Temperatur

e C

ontrol

Summary of Contents for T7771A

Page 1: ...4 to 22 AWG 2 0 to 0 34 sq mm connects to a terminal block in the subbase Wall module is activated by plugging into prewired subbase Mounting Options The T7771 can be mounted on a standard two by four inch junction box or on a 60 mm diameter junction box Dimensions H W D 5 1 16 x 3 1 8 x 1 in 128 x 80 x 25 mm Setpoint Adjustment The setpoint offset allows for 3 F from the programmed T7350 setpoint...

Page 2: ...button is pushed the T7350 setting changes to Temporary Occupied If pressed again the T7350 setting changes back to Occupied The override button has no effect when the T7350 programmed setting is already Occupied BEFORE INSTALLATION Cover Disassembly One locking mechanism is used on the wall module cover After installation to disassemble the cover and the subbase see Fig 2 Fig 2 Cover disassembly ...

Page 3: ... blocks are designed to accept no more than one 14 AWG 2 5 sq mm conductor Connect multiple wires that are 14 AWG 2 5 sq mm with a wire nut Include a pigtail with this wire group and attach the pigtail to the individual terminal block Wire the terminal blocks as follows 1 For single wires strip 3 16 in 5 mm for multiple wires going into one terminal strip 1 2 in 13 mm insulation from the conductor...

Page 4: ...th two sensors Fig 8 Temperature averaging with four sensors Fig 9 Attaching two wires at wall module terminals When all wiring is complete attach the cover of the T7771A Wall Module by reversing step 2 of Fig 2 1 2 3 4 5 6 7 8 9 SENSOR GND E BUS E BUS M22175 BYPASS STATUS SETPT 10K OHM OUTPUT J2 20K OHM OUTPUT J2 M22280 T4 T3 T7350 SUBBASE T7770A3002 T4 T3 T7771A J2 T4 T3 10K OHM OUTPUT J2 1 1 AP...

Reviews: