T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
23
62-0255—09
Fig. 49. Setup - Outputs - Options - Min Off/On Time.
1.3.3.2. MIN OFF
or
MIN ON
This is the minimum number of seconds of “off time” or
“on time” for
all
relays.
1.
Press the
u
button to display the Min Off/On value.
2.
Use the
p
and
q
buttons to increase/decrease the
desired number of seconds from 0 to 990 seconds
in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3.
Press the
u
button to accept the seconds and
display the DI OPTIONS.
NOTES:
1.
The minimum off time applies to
all
relay
outputs.
2.
When minimum off time is active, relays
waiting to be energized display a flashing
square underneath the relay number on the
home screen.
3.
If the minimum off time is not equal to zero
(0), the minimum off time activates at power-
up. To manually override, press the
t
button at
any time.