T7560A,B,C DIGITAL WALL MODULES 

EN0B-0237GE51 R0208 

 

SPECIFICATIONS 

Models 

Table 1. Types of DWM 

 

sensor

1

 

colors 

(dial / housing) 

pre-conf.

units

 

T7560A1000 

Tmp blue/white 

°

T7560A1026 

Tmp white/white 

°

T7560A1018 

Tmp white/white 

°

T7560B1008 

Tmp/Hum blue/white 

°

T7560B1024 

Tmp/Hum white/white 

°

T7560B1016 

Tmp/Hum white/white 

°

T7560C1006 

Tmp/Hum blue/white  n.a. 

Tmp = Temperature sensor; Hum = Humidity sensor 

 

Temperature Sensor Accuracy 

The DWM is furnished with a 20k

 NTC temperature 

sensor that follows a specific temperature-resistance curve. 

See Fig. 1. Honeywell controllers used with the DWM 

employ an algorithm that provides readings close to the 

actual temperature. Table 2 summarizes the DWM sensor 

accuracy for normal operating temperatures. Across the 

range of 43 to 104°F (6 to 40°C), the accuracy is better 

than ±0.75°F (±0.42°C). 

 

80 K

70 K

60 K

50 K

40 K

30 K

20 K

10 K

30

0

10

20

30

40

40

50

60

70

80

90 100 110 ° F

°C

temperature (degrees)

elec

tr

ical 

re

si

st

an

ce

 (

o

hm

s)

 

Fig. 1. Temperature vs. resistance for 20k

 sensor 

 

Table 2. Temperature sensor accuracy 

ambient tem. (°C)

max. error (°C) 

nominal re-

sistance (

15.5 ±0.29 31543 

18.3 ±0.27 27511 

21.1 ±0.27 24047 

26.7 ±0.27 18490 

29.5 ±0.29 16264 

 

Humidity Sensor 

Table 3. Humidity sensor specifications 

parameter 

value 

humidity sensing range 

5 … 95% r.h. 

output signal 

0.5 … 10 Vdc (5…100% r.h.) 

accuracy ±5% 

(full-scale) 

 

Fan Speed Button (T7560A,B, only) 

Table 4. Fan speed resistances 

switch position 

resistance (

) fan 

behavior 

auto 

1681.4 ±100 

runs as scheduled 

0 2686.4 

±100 OFF 

3866.4 ±100 

runs at speed 1 

3041.4 ±100 

runs at speed 2 

4601.4 ±100 

runs at speed 3 

bypass activated 

0 ... 100 

unchanged 

 

NOTE:

  If connected to Excel 10 UV Controller W7753, fan 

output will not be shorted to ground on pressing 
the BYPASS button; with every other Excel 10 
Controller, it will be shorted. 
See T7560A,B,C Installation Instructions (product 
literature no.: EN1B-0146GE51) for configuration. 

 

Power Supply 

24 Vac/dc with a valid range of 18 ... 30 V 

5 Vdc via LED input with a valid range of 5 ... 12 V 

See T7560A,B,C Installation Instructions (product literature 

no.: EN1B-0146GE51) for details. 

 

Power Consumption 

<

2 VA at 24 Vac, 50/60 Hz 

 

DWM Setpoint Adjustment 

The relation between setpoint and resistance is given in 

Table 5 and Table 6. Accuracy of resistance is: 

 

±

5% in middle position, e.g. 5225 

 to 5775 

 

 

±

10% in end position, e.g. 9450 

 to 11550 

Setpoint accuracy: ± 0.2 K 

Summary of Contents for T7560B

Page 1: ...hange configuration information such as the DWM s engineering units The T7560C Digital Wall Module see inset above has no user interface e g LCD buttons or setpoint dial and issues only temperature and humidity values These wall modules are not compatible with Honeywell W7751A C E G VAV1 and W7752D1 FCU1 Controllers FEATURES Fully compatible with all current Excel 10 and Excel 20 to 600 controller...

Page 2: ...ominal re sistance Ω 15 5 0 29 31543 18 3 0 27 27511 21 1 0 27 24047 26 7 0 27 18490 29 5 0 29 16264 Humidity Sensor Table 3 Humidity sensor specifications parameter value humidity sensing range 5 95 r h output signal 0 5 10 Vdc 5 100 r h accuracy 5 full scale Fan Speed Button T7560A B only Table 4 Fan speed resistances switch position resistance Ω fan behavior auto 1681 4 100 runs as scheduled 0 ...

Page 3: ... 3 4142 0 79 3053 0 4 3689 3 81 2509 3 5 3236 7 83 1965 6 6 2784 0 85 1421 9 7 2331 3 8 1878 7 9 1426 0 10 973 3 Field Wiring 16 to 22 AWG 1 5 to 0 34 mm2 depending on application 18 AWG 1 0 mm 2 min for 24 Vac power wiring Max length of wire from a device to a wall module is 164 ft 50 m Twisted pair wire recommended for wire runs longer than 100 ft 30 5 m Setpoint Adjustment Range A and B Setpoin...

Page 4: ...n to decrease increase the room temperature setpoint The display toggles the setpoint value either relative or absolute as configured After the new setpoint has been set the display returns to normal mode after approx 5 sec Set Fan Speed The manually set fan speed is represented by a bargraph Depending on configuration the fan speed can be set as follows Three speed fan override AUTO OFF 1 2 3 Two...

Page 5: ...ode MOON continuously ON Unit Off No Frost Protection OFF without snowflake Unit Off With Frost Protection OFF WITH SNOWFLAKE Override Standby mode from central HALF SUN FLASHING Wink mode NEURON ID sent SUN MOON SNOWFL FLASHING Only with FCU HYD CHC Press the BYPASS button to set the desired mode To activate Override Occupancy or Bypass mode press and release the BYPASS button To activate Overrid...

Page 6: ...e further options depend on the configuration of the controller Occupancy mode SUN continuously ON Standby mode generated by time program HALF SUN continuously ON Unoccupancy mode MOON continuously ON To adapt the T7560 to the CARE control strategies for Excel 20 to 600 a standard ModAL software module is available Contact your local Honeywell distributor or refer to T7560A B C Installation Instru...

Reviews: