
T7460A,B,C,D,E,F WALL MODULES – INSTALLATION INSTRUCTIONS
3
EN1B-0291GE51 R0718B
Table 2. Wiring terminal references for non-Excel 10/12 devices
signal
T7460A
terminal
T7460B
terminal
T7460C
terminal
Excel 800
XF82x term.
(example)
Excel 500
XF52xB term.
(example)
Excel 500
XFL52x term.
(example)
Excel 100
terminal
(example)
Excel 50
terminal
(example)
Excel 20
terminal
(example)
CPO-
FB22344R
term. (ex.)
Smart I/O
XFC2 / XFC3
term. (ex.)
sensor signal
1
1
2
XF821: 1 (AI)
XF521: 1 (AI)
XFL521: 1 (AI)
1 (AI)
33 (AI)
19 (AI)
39 (AI)
11 (AI)
COM/GND
3
3
1
XF821: 11
(AI GND)
XF521: 2
(AI GND)
XFL521: 18
(AI GND)
55 (GND)
34 (AI GND) 20 (AI GND)
40 (AI GND)
10 (AI GND)
SETPT
--
2
3
XF821: 2 (AI)
XF521: 3 (AI)
XFL521: 2 (AI)
2 (AI)
35 (AI)
21 (AI)
41 (AI)
14 (AI)
BYP/FAN (no fan)
--
--
4
XF823: 1 (DI)
XF523: 1 (DI)
XFL523: 1 (DI)
13 (DI)
23 (DI)
34 (DI)
36 (DI)
6 (DI)
BYP/RTN
--
--
6
XF823: 13
(DI GND)
XF523: 14
(DI GND)
XFL523: 18
(DI GND)
56 (GND)
24 (DI GND)
18 (COM)
37 (DI GND)
5 (DI)
LED (10 Vdc / 3mA
permanent)
--
--
5
XF822: 1 (AO)
XF522: 1 (AO)
XFL522: 1 (AO)
37 (AO)
15 (AO)
12 (AO)
19 (AO)
32 (AO)
LED/RTN
(0Vdc = LED OFF,
10Vdc = LED ON)
--
--
7
XF822: 2 (AO)
XF522: 3 (AO)
XFL522: 2 (AO)
38 (AO)
17 (AO)
13 (AO)
17 (AO)
35 (AO)
signal
T7460D
terminal
T7460D,E,F
terminal
Excel 800
XF82x term. (ex.)
Excel 500
XF52xB term. (ex.)
Excel 500
XFL52x term. (ex.)
Excel 100
term. (ex.)
Excel 50
term. (ex.)
Excel 20
term. (ex.)
CPO-FB22344R
term. (ex.)
sensor signal
2
2
XF821: 1 (AI)
XF521: 1 (AI)
XFL521: 1 (AI)
1 (AI)
33 (AI)
19 (AI)
39 (AI)
COM/GND
1
1
XF821: 11 (AI GND)
XF521: 2 (AI GND) XFL521: 18 (AI GND)
55 (GND)
34 (AI GND)
20 (AI GND)
40 (AI GND)
SETPT
3
3
XF821: 2 (AI)
XF521: 3 (AI)
XFL521: 2 (AI)
2 (AI)
35 (AI)
21 (AI)
41 (AI)
BYP/FAN (no fan)
4
4
XF821: 3 (AI)
XF521: 5 (AI)
XFL521: 3 (AI)
3 (AI)
37 (AI)
23 (AI)
altern. to SETPT
BYP/RTN
6
6
XF821: 13 (AI GND)
XF521: 6 (AI GND) XFL521: 20 (AI GND)
56 (GND)
38 (AI GND)
24 (AI GND)
altern. to SETPT
LED (10 Vdc / 3mA
permanent)
--
5
XF822: 1 (AO)
XF522: 1 (AO)
XFL522: 1 (AO)
37 (AO)
15 (AO)
12 (AO)
19 (AO)
LED/RTN
(0Vdc = LED OFF,
10Vdc = LED ON)
--
7
XF822: 2 (AO)
XF522: 3 (AO)
XFL522: 2 (AO)
38 (AO)
17 (AO)
13 (AO)
17 (AO)
NOTE:
In the case of Excel 10/12 wiring, please refer to the respective Excel 10/12 Installation Instructions.
NOTE:
In the case of the T7460A,B,C, bypass signaling is via digital input. In the case of the T7460D,E,F, bypass signaling
(which includes fan-speed signaling) is via analog input.
Jumper Settings
The jumpers on the PCB of the T7460C,D,E,F must be set according to the type of controller connected. See also Fig. 6.
Jumper positions for W77xx: Jumper A = 1, Jumper B = 1
Const. Vol. Air Handling Unit
W7750A,B
(Smart) Variable Air Volume
W7751B,D,F,H
Fan Coil Unit (FCU2)
W7752D,E,F,G
Fan Coil Unit (FCU3)
W7754
Remote Input/Output Device
W7761A
Hydronic
W7762A,B
Chilled Ceiling
W7763C,D,E
Excel 12
W7704xx
Jumper positions for W7753: Jumper A = 2, Jumper B = 2
Unit Ventilator
W7753
Jumper positions for XL500: Jumper A = 3, Jumper B = 3
Excel 800
XCL8010A
Excel 500
XC5010x, XC5210x
Excel 100
XL100x
Excel 50
XL50xxxx
Excel 20
XL20x
CPO-FCU
CPO-FB22344R-xxx
Smart I/O
XFC2xxxx/XFC3xxxx
Excel 10/12:
JUMPER A IN POS. 1
JUMPER B IN POS. 1
W7750, W7751, W7752, W7754,
W7761, W7762, W7763, W7704
(FACTORY DEFAULT)
Excel 10:
JUMPER A IN POS. 2
JUMPER B IN POS. 2
W7753A (unit ventilator)
Excel 20, 50, 100, 500, 600, 800,
CPO-FCU, and Smart I/O
with fan
JUMPER A IN POS. 1
JUMPER B IN POS. 3
Excel 20, 50, 100, 500, 600, 800,
CPO-FCU, and Smart I/O
without fan
JUMPER A IN POS. 3
JUMPER B IN POS. 3
1:W7750
W7751
W7752
W7762
W7763
2:W7753
3:XL500
JUMPER
A B
1:W7750
W7751
W7752
W7762
W7763
2:W7753
3:XL500
JUMPER
A B
1:W7750
W7751
W7752
W7762
W7763
2:W7753
3:XL500
JUMPER
A B
1:W7750
W7751
W7752
W7762
W7763
2:W7753
3:XL500
JUMPER
A B
Fig. 6. Jumper settings for T7460C,D,E,F Wall Modules