T7460A,B,C,D,E,F 

WALL MODULES 

 

INSTALLATION INSTRUCTIONS 

BEFORE INSTALLATION 

All wiring must comply with local electrical codes and 
ordinances or as specified on installation wiring diagrams. 
Wall module wiring can be sized from 16 to 22 AWG (1.5 to 
0.34 mm

2

), depending on the application. The maximum 

length of wire from a device to a wall module is 1000 ft (305 
m). Twisted-pair wire is recommended for wire runs longer 
than 100 ft (30.5 m). 
 

COVER DISASSEMBLY 

The cover of the wall module is fixed in place using a tab 
located on the underside of the unit; to disassemble the cover 
and the sub-base, see Fig. 1. 

PRESS

LIFT

1

2

 

Fig. 1. Cover disassembly 

 

Table 1. Features of T7460 Versions 

 

Sensor

 

Setpoint

 

Bypass/ LED Fan switch

T7460A 

 

T7460B 

 

 

T7460C 

 

 

 

T7460D 

 

 

5-position 

T7460E 

 

 

 

3-position 

T7460F 

 

 

 

5-position 

 

INSTALLATION 

The T7460B,C,D,E,F packages include two setpoint dials. By 
default, the “Celsius Relative” type is mounted. This can be 

easily replaced with the “Celsius Absolute” type by pulling the 
one dial off and inserting the other one. 
Mount the T7460A,B,C,D,E,F Wall Modules on an inside wall 
approximately 54 in. (1.3 m) from the floor (or in the specified 
location) to allow exposure to the average zone temperature. 

NOTE:

  Maintain a mounting clearance of approx. 4 in. 

(10 cm) to the left-hand side of the module in order 
to allow a free airflow for the temperature sensor and 
accessibility of the setpoint dial. 
Do not mount the wall modules on an outside wall, 
on a wall containing water pipes, or near air ducts. 
Avoid locations that are exposed to discharge air 
from registers or radiation from lights, appliances, or 
the sun. 
The T7460D,E,F should not be connected to con-
trollers that do not support fan operation (i.e., the 
W7751, W7762, W7763, W7704, and XFC2xxxx / 
XFC3xxxx). 
When used with CPO-FB22344R-xxx controllers, 
either setpoint override or fan-speed adjustment is 
supported. 
Keep wiring at least 1 ft (305 mm) away from large 
inductive loads such as motors, line starters, lighting 
ballasts, and large power distribution panels. Run 
wall module wiring separately from 50 Vac or greater 
power wiring. 

The wall modules can be mounted on a 60-mm wall outlet box 
using No. 6 (3.5-mm) screws or on a wall (see Fig. 2 and Fig. 
5). When mounting directly on a wall, use the type of screws 
appropriate for the wall material. 

SEN

SO

R

SET

 P

T

BYP/

FA

N

LE

D

BYP/

R

T

N

LE

D

/R

T

N

CO

M

1:W7750

  W7751

  W7752

  W7762

2:W7753

3:XL500

JUMPER

A  B

2-3/8

(60)

3-7/16

(86)

2-11/16

(68)

BORE-HOLE DIMENSIONS
FOR OPTIONAL WALL
MOUNTING

 

Fig. 2. Bore-holes for T7460 wall modules in in. (mm) 

See Fig. 3 for mounting dimensions. 

NOTE:

  Graphics depict E/F model. Dimensions are the 

same for all six models. 

Summary of Contents for T7460B

Page 1: ...exposure to the average zone temperature NOTE Maintain a mounting clearance of approx 4 in 10 cm to the left hand side of the module in order to allow a free airflow for the temperature sensor and accessibility of the setpoint dial Do not mount the wall modules on an outside wall on a wall containing water pipes or near air ducts Avoid locations that are exposed to discharge air from registers or ...

Page 2: ...he 21 Celsius absolute scale or 0 Celsius relative scale is at the 3 o clock position and then insert the dial into the hole W7762 2 W7753 3 XL500 W7762 2 W7753 3 XL500 12 12 1 2 1 5 18 21 24 2 7 3 0 5 4 3 2 1 0 3 5 4 2 1 3 O CLOCK POSITION 12 O CLOCK ORIENTATION 12 O CLOCK ORIENTATION 3 O CLOCK POSITION Fig 4 Mounting position of setpoint dial 6 Remount the cover as depicted in Fig 5 and make sur...

Page 3: ... AI GND 24 AI GND altern to SETPT LED 10 Vdc 3mA permanent 5 XF822 1 AO XF522 1 AO XFL522 1 AO 37 AO 15 AO 12 AO 19 AO LED RTN 0Vdc LED OFF 10Vdc LED ON 7 XF822 2 AO XF522 3 AO XFL522 2 AO 38 AO 17 AO 13 AO 17 AO NOTE In the case of Excel 10 12 wiring please refer to the respective Excel 10 12 Installation Instructions NOTE In the case of the T7460A B C bypass signaling is via digital input In the...

Page 4: ...0C E F WALL MODULE IN CONJUNCTION WITH THE EXCEL 10 UV CONTROLLER W7753 CONNECT TERMINAL 6 BYP RTN WITH THE CONTROLLER S BYPASS INPUT IMPORTANT THE GRAY SHADED TERMINALS ARE INTERNALLY CONNECTED THE WHITE UNSHADED TERMINALS ARE NOT INTERNALLY CONNECTED Wiring of Modules SENSOR SET PT COM T7460D T7460E 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 T7460F T7460C BYP FAN LED BYP RTN LED RTN...

Page 5: ... IN POS 2 Fig 10 Circuitry of T7460C D E F Wall Modules ACCESSORIES T7460 LONJACK The T7460 LONJACK is a small board allowing easy access to LONWORKS or BACnet via the correspondingly wired wall module apply appropriate wiring guidelines for LONWORKS or BACnet networks as the case may be The T7460 LONJACK provides an additional 3 5 mm jack socket for a 3 5 mm jack plug Order quantity set with 5 pi...

Page 6: ... Energy Solutions Division of Honeywell Technologies Sàrl Rolle Z A La Pièce 16 Switzerland by its Authorized Representative Home and Building Technologies Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 0 7031 637 01 Fax 49 0 7031 637 740 http ecc emea honeywell com EN1B 0291GE51 R0718B ...

Reviews: