7270B1009 WIRELESS WALL MODULE
EN1B-0241GE51 R0106C
6
•
P1:2
→
Temperatures are displayed in °C.
This is the
default configuration.
P2: Default Display
With this parameter, the user can configure the default
display:
•
P2:1
→
The default display shows the setpoint offset.
•
P2:2
→
The default display shows the current room
temperature.
This is the default configuration.
P3: Fan
With this parameter, the user can configure the fan (i.e.
establish whether a fan is present and how many speed levels
it has) as well as enable/disable the FAN function:
•
P3:1
→
No fan is present in the room. This configuration
disables the FAN function.
•
P3:2
→
An ON/OFF fan is present. This configuration
enables the FAN function.
•
P3:3
→
A 2-speed fan is present. This configuration
enables the FAN function.
•
P3:4
→
A 3-speed fan is present.
This is the default
configuration.
P4: Temperature Setpoint Offset Limits
With this parameter, the user can configure the range over
which the temperature setpoint offset can be adjusted.
•
The max. range is -5...+5 K. The min. range is -1...+1 K.
•
The range can be widened/narrowed with the setpoint
wheel in steps of 1 K.
•
The default configuration is -3…+3 K.
P5: Sunblind Runtime
With this parameter, the user can configure the time during
which the sunblinds rise/descend.
•
The runtime has a range of 1...99 s.
•
This range can be widened/narrowed with the setpoint
wheel in steps of 1 s.
•
The default runtime is 60 s.
P6: Light Groups
With this parameter, the user can configure whether only a
single group of lights or two groups of lights are present.
•
P6:1
→
Only a single group of lights is present.
•
P6:2
→
Two groups of lights are present. Pressing the UP
button turns ON light groups 1 and 2 and pressing the
DOWN button turns OFF light groups 1 and 2.
•
P6:3
→
Two groups of lights are present. Pressing the UP
button turns ON/OFF light group 1 and pressing the
DOWN button turns ON/OFF light group 2.
This is the
default configuration.
•
P6:4 and P6:5 are currently used with special custom
models, only. Do not set these parameters.
•
P6:6
→
No LIGHT function is disabled and the
SUNBLINDS function becomes the default function
P7: Room Temperature Correction Value
With this parameter, the user can correct the room tem-
perature value displayed in the LCD and transmitted to the
W7070A receiver.
•
A value of 50 means "no change", i.e. the temperatures
measured by the wall module are displayed/transmitted
without correction.
This is the default configuration.
•
Values of 49, 48, 47, etc. mean that the temperatures
measured by the wall module are displayed/transmitted
with a correction of -0.1 K, -0.2 K, -0.3 K, etc.
•
Values of 51, 52, 53, etc. mean that the temperatures
measured by the wall module are displayed/transmitted
with a correction of +0.1 K, +0.2 K, +0.3 K, etc.
P8: Unoccupied Room
With this parameter, the user can configure the SETPOINT
OFFSET function and the FAN function to be enabled /
disabled whenever the user has used the OCCUPANCY
function to manually force the controller into the "unoccupied"
state:
•
P8:1
→
The FAN function and the SETPOINT OFFSET
function are both enabled.
This is the default con-
figuration.
•
P8:2
→
The FAN function is enabled and the SETPOINT
OFFSET function is disabled.
•
P8:3
→
The FAN function is disabled and the SETPOINT
OFFSET function is enabled.
•
P8:4
→
The FAN function and the SETPOINT OFFSET
function are both disabled.
P9: Disable/Enable SUNBLINDS Function
With this parameter, the user can enable/disable the
SUNBLINDS function:
•
P9:1
→
There are no sunblinds present in the room. This
configuration disables the SUNBLINDS function.
•
P9:2
→
One set of sunblinds is present. This con-
figuration enables the SUNBLINDS function.
This is the
default configuration.
•
P9:3 and P9:4 are currently used with special custom
models, only. Do not set these parameters.
PA: Disable/Enable OCCUPANCY Function
With this parameter, the user can enable/disable the
OCCUPANCY function:
•
PA:1
→
This disables the OCCUPANCY function.
•
PA:2
→
This enables the OCCUPANCY function.
•
PA:3
→
This partially disables the OCCUPANCY func-
tion. Specifically, the user can then no longer manually
force the controller into the permanent "unoccupied"
(" ") or "occupied" (" ") states. However, he can still
manually force the controller into the "occupied" state for
a limited time (" ").
This is the default configuration.
PB and PC
Currently used with special custom models, only. Do not set
these parameters.