7270B1009 WIRELESS WALL MODULE 

EN1B-0241GE51 R0106C 

6

 P1:2 

 Temperatures are displayed in °C. 

This is the 

default configuration.

 

 

P2: Default Display 

With this parameter, the user can configure the default 
display: 

 P2:1 

 The default display shows the setpoint offset. 

 P2:2 

 The default display shows the current room 

temperature. 

This is the default configuration.

 

 

P3: Fan 

With this parameter, the user can configure the fan (i.e. 
establish whether a fan is present and how many speed levels 
it has) as well as enable/disable the FAN function: 

 P3:1 

 No fan is present in the room. This configuration 

disables the FAN function. 

 P3:2 

 An ON/OFF fan is present. This configuration 

enables the FAN function. 

 P3:3 

 A 2-speed fan is present. This configuration 

enables the FAN function. 

 P3:4 

 A 3-speed fan is present. 

This is the default 

configuration.

 

 

P4: Temperature Setpoint Offset Limits 

With this parameter, the user can configure the range over 
which the temperature setpoint offset can be adjusted. 

  The max. range is -5...+5 K. The min. range is -1...+1 K. 

  The range can be widened/narrowed with the setpoint 

wheel in steps of 1 K. 

 

The default configuration is -3…+3 K. 

 

P5: Sunblind Runtime 

With this parameter, the user can configure the time during 
which the sunblinds rise/descend. 

  The runtime has a range of 1...99 s. 

  This range can be widened/narrowed with the setpoint 

wheel in steps of 1 s. 

 

The default runtime is 60 s. 

 

P6: Light Groups 

With this parameter, the user can configure whether only a 
single group of lights or two groups of lights are present. 

 P6:1 

 Only a single group of lights is present. 

 P6:2 

 Two groups of lights are present. Pressing the UP 

button turns ON light groups 1 and 2 and pressing the 
DOWN button turns OFF light groups 1 and 2. 

 P6:3 

 Two groups of lights are present. Pressing the UP 

button turns ON/OFF light group 1 and pressing the 
DOWN button turns ON/OFF light group 2. 

This is the 

default configuration.

 

  P6:4 and P6:5 are currently used with special custom 

models, only. Do not set these parameters. 

 P6:6 

 No LIGHT function is disabled and the 

SUNBLINDS function becomes the default function 

 

P7: Room Temperature Correction Value 

With this parameter, the user can correct the room tem-
perature value displayed in the LCD and transmitted to the 
W7070A receiver. 

 

A value of 50 means "no change", i.e. the temperatures 
measured by the wall module are displayed/transmitted 
without correction. 

This is the default configuration.

 

 

Values of 49, 48, 47, etc. mean that the temperatures 
measured by the wall module are displayed/transmitted 
with a correction of -0.1 K, -0.2 K, -0.3 K, etc. 

 

Values of 51, 52, 53, etc. mean that the temperatures 
measured by the wall module are displayed/transmitted 
with a correction of +0.1 K, +0.2 K, +0.3 K, etc.

 

 

P8: Unoccupied Room 

With this parameter, the user can configure the SETPOINT 
OFFSET function and the FAN function to be enabled / 
disabled whenever the user has used the OCCUPANCY 
function to manually force the controller into the "unoccupied" 
state: 

 P8:1 

 The FAN function and the SETPOINT OFFSET 

function are both enabled. 

This is the default con-

figuration.

 

 P8:2 

 The FAN function is enabled and the SETPOINT 

OFFSET function is disabled. 

 P8:3 

 The FAN function is disabled and the SETPOINT 

OFFSET function is enabled. 

 P8:4 

 The FAN function and the SETPOINT OFFSET 

function are both disabled. 

 

P9: Disable/Enable SUNBLINDS Function 

With this parameter, the user can enable/disable the 
SUNBLINDS function: 

 P9:1 

 There are no sunblinds present in the room. This 

configuration disables the SUNBLINDS function. 

 P9:2 

 One set of sunblinds is present. This con-

figuration enables the SUNBLINDS function. 

This is the 

default configuration.

 

  P9:3 and P9:4 are currently used with special custom 

models, only. Do not set these parameters. 

 

PA: Disable/Enable OCCUPANCY Function 

With this parameter, the user can enable/disable the 
OCCUPANCY function: 

 PA:1 

 This disables the OCCUPANCY function. 

 PA:2 

 This enables the OCCUPANCY function. 

 PA:3 

 This partially disables the OCCUPANCY func-

tion. Specifically, the user can then no longer manually 
force the controller into the permanent "unoccupied" 
("  ") or "occupied" (" ") states. However, he can still 
manually force the controller into the "occupied" state for 
a limited time ("  "). 

This is the default configuration.

 

 

PB and PC 

Currently used with special custom models, only. Do not set 
these parameters.

 

 

Summary of Contents for T7270B1009

Page 1: ... U S Registered Trademark EN1B 0241GE51 R0106C Copyright 2006 Honeywell Inc All rights reserved T7270B1009 WIRELESS WALL MODULE HONEYWELL EXCEL 5000 OPEN SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS ...

Page 2: ...llowing six basic functions LIGHT SUNBLINDS OCCUPANCY FAN SETPOINT OFFSET and TEMPERATURE DISPLAY TRANSMIT function NOTE The LIGHT function is the default function see also section Default Function on page 5 and Fig 2 Controls The wall module features three control buttons and a large setpoint wheel They are used in the operating mode to select individual functions and to adjust their respective s...

Page 3: ...s LI are displayed in the LCD and the function indication bar appears underneath the light symbol imprinted on the housing NOTE See also section Default Function on page 5 Controlling a Single Light Group P6 1 If the wall module has been configured to control only a single group of lights see section P6 Light Groups on page 6 the LIGHT function settings are performed as described in the following ...

Page 4: ... the DOWN Button Briefly pressing the DOWN button will completely lower the sunblinds in the LCD the sunblinds symbol moves downwards Briefly pressing either the UP or the DOWN button while the sunblinds are descending will stop the sunblinds and the LCD will revert to the default display Pressing the DOWN button for more than 2 sec will lower the sunblinds only as long as it remains pressed in th...

Page 5: ...through the other function symbols Power Up Teach Commands After power up an LCD test will be carried out i e all LCD segments will be activated for approx 1 sec Fig 3 LCD test after power up After that two teach commands will be triggered Please refer to W7070A Receiver System Engineering Product Literature No EN0B 0286GE51 on how to perform a teach in A special LCD sequence t 1 then t 2 will be ...

Page 6: ...tion becomes the default function P7 Room Temperature Correction Value With this parameter the user can correct the room tem perature value displayed in the LCD and transmitted to the W7070A receiver A value of 50 means no change i e the temperatures measured by the wall module are displayed transmitted without correction This is the default configuration Values of 49 48 47 etc mean that the tempe...

Page 7: ...ecified on the installation drawings to allow exposure to the average zone temperature Do not mount the wall module on an outside wall on a wall containing water pipes or near air ducts Avoid locations that are exposed to discharge air from registers or radiation from lights appliances or the sun Fig 4 Mounting Removing the Housing Cover The wall module comes with a sub base that mounts separately...

Page 8: ...te du Bois 37 Switzerland by its Authorized Representative Automation and Control Solutions Honeywell GmbH Böblinger Straße 17 D 71101 Schönaich Phone 49 7031 63701 Fax 49 7031 637493 http europe hbc honeywell com Subject to change without notice Printed in Germany EN1B 0241GE51 R0106C DIMENSIONS F Honeywell 104 85 99 97 2 30 68 100 86 Fig 6 T7270B1009 dimensions in mm ...

Reviews: