69-0964–2
4
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
b
Mode 01 or 02 must be 01 to extend fan operation.
c
Mode 22 must be set to 01 and remote sensor(s) must be installed.
Table 2. Thermostat Installer Setup Options (Continued).
(continued)
Mode Number
(Press
i
key
Factory-Setting
Other Choices
(Press
▲
or
▼
key to change)
Select
to change)
Display
Description
Display
Description
Output stages
of cooling.
08
02
Two stages of cool.
00 or 01
00—No cooling.
01—One stage of cool.
Cooling cycle rate. 09
04
Stage 1.
03
3 cph.
10
04
Stage 2.
Not used.
11
—
—
—
—
Changeover
(T7100F only).
12
00
System setting key is
operational.
01 or 02
01—Manual changeover
02—Auto only.
Not used.
13
—
—
—
—
Degree tempera-
ture display.
14
00
Temperature is
displayed in
°
F.
01
Temperature is displayed in
°
C.
Displaying
temperature.
15
00
Temperature is
displayed.
01
Temperature is not displayed.
Not used.
16 - 18
—
—
—
—
Extended fan
operation in
heating
b
.
19
00
No extended fan
operation after the call
for heat ends.
01
Fan operation is extended
90 seconds after the call for
heat ends.
Extended fan
operation in
cooling.
20
00
No extended fan
operation after the call
for cool ends.
01
Fan operation is extended
90 seconds after the call for
cool ends.
Fan key
adjustment.
21
00
Fan setting key is
operational.
01
Fan setting key is continuously in
the Auto position.
Remote sensing.
22
00
Remote sensing not
activated.
01
Remote sensing activated.
Temperature
averaging
network
c
.
23
00
Temperature averaging
disabled.
01
Temperature averaging between
local sensor and remote sensor(s)
activated.
Not used.
24
—
—
—
—
Keypad lockout
level.
25
0
No lockout.
01 - 02
01—View setpoint only.
02—Lockout all keys.
Not used.
26
—
—
—
—
Heating/cooling
override.
27
00
No temperature change
when override key is
pressed.
01 - 15
°
F the temperature setting is
changed when the override key is
pressed. Temporary is displayed.
Not used.
28 - 29
—
—
—
—
Deadband.
30
02
Heating and cooling
setpoints can be set no
closer than 2
°
F.
03 - 10
Heating and cooling setpoints can
be set no closer than the chosen
value.
Interstage control
point (select
models).
31
01
(Conven-
tional) or
02 (Heat
pump).
Temperature has to
change 1
°
F or 2
°
F
before the system calls
for the next stage.
00 - 12
Temperature has to change the
chosen value before the system
calls for the next stage.
Minimum On time. 32
02
2-minute minimum On
time for heating and
cooling.
00 or 01
No minimum On time or 1 minute
minimum On time for heating and
cooling.
Minimum Off time
for the
compressor.
33
04
4-minute minimum Off
time for the compressor.
00, 01,
02, 03 or
05
Minimum number of minutes (0
thru 5) the compressor will be off
between calls for the compressor.