background image

T6380 - SPECIFICATIONS, ORDERING INFORMATION 

SPECIFICATIONS 

MODELS: 

Fan Coil System 

2-pipe System 

•  Cooling only 

•  Heating only 

2-pipe Heat-Cool 

•  Manual Change/Over 

•  Seasonal, auto C/O 

•  Seasonal, auto C/O

 with aux. electric heat 

4-pipe Heat-Cool 

•  Manual C/O 

Electrical Ratings: 

3-Speed Fan Operation 

Constant 

Cycled 

On-Auto 

T6383A 

T6381A 

T6387A 

Fig. 2a 

Fig. 5a 

Fig. 8a 

T6383A 

T6381A 

T6387A 

Fig. 2b 

Fig. 5b 

Fig. 8a 

T6383B 

T6381B 

N/A 

Fig. 3 

Fig. 6 

T6383A 

T6387A

T6381A 

Fig. 2c 

Fig. 5c 

Fig. 8c 

T6383B 

T6381B 

N/A 

Fig. 4b 

Fig. 7b 

T6383B 

T6381B 

N/A 

Fig. 4a 

Fig. 7a 

T6380 Series - Power Supply: 110-130 or 208-277 Vac

 +10/-15%, 50-60 Hz. 

T6381, T6387 - Output Rating, cycled (“Auto”) fan control 

50-60 Hz 

120 V 

208 V 

230 V 

277 V 

Full Load Amps* 

3.8 

2.1 

1.9 

1.6 

Locked Rotor 

22.8 

12.6 

11.4 

9.5 

Pilot Duty 

125 VA 

*  

Equivalent to NEMA 1/8 horsepower rating for a hermetically-sealed 
motor such as a compressor.  Allowable connected load must be 
determined by adding nameplate full load and locked rotor (inrush) ratings 
of all loads. 

T6383 – Output Rating, constant fan operation 
Thermostat (Heat and Cool outputs): 

50-60 Hz 

120 V 

208 V 

230 V 

277 V 

Full Load Amps 

3.8 

2.1 

1.9 

1.6 

Locked Rotor A 

22.8 

12.6 

11.4 

9.5 

Pilot Duty 

125 VA 

Resistive (heat only) 

10.0 A 

N/A 

N/A 

5.6 

Fan (Air Handler): 

Operating range: 

32  to + 104 F [0 to +40 C], 5 to 95% RH, non-condensing. 

Performance Specifications: 

Precision: 

±

1

°

F temperature swing [0.9

°

C differential]. 

Accuracy:  2

°

F [1

°

C] droop with 4 A load. 

Dimensions: 

See Fig. 1 - Nominal Dimensions. 

Mounting: 

Direct mounting on single-gang NEMA 2" x 3" flush-mount 
or 2" x 4" surface-mount electrical box, or on 4" x 4" box 
Models available for vertical or horizontal mount. 

Wiring Connections: 

Screw terminal block suitable for 1 – 14 AWG, 2 – 18 AWG, 
or 1 – 1.5 mm

2

 copper wire. 

Approvals: 

CSA Certified LR1322 
Underwriters Laboratories Listed E47434. 

Accessories: 

272824A-T6380 Range stop/cover locking kit. 
272827A-T6380 replacement cover with Cool-Warmer 

Fig. 1 — Nominal dimensions in inches and

 millimetres 

50-60 Hz 

110-130V 

208 V 

220-240V  277 V 

Full Load Amps** 

5.8 

3.2 

2.9 

2.4 

Locked Rotor 

34.8 

19.2 

17.4 

14.4 

**   Equivalent to NEMA 1/4 horsepower rating for a hermetically-sealed 

motor.  Allowable load must be determined from fan nameplate 
ratings .

 † North American national electrical codes require all ungrounded 

conductors to electric resistance heating to be broken at the thermostat 
OFF setting. The 208V and 230V resistive ratings are not UL approved. 
The 230V rating is site-approveable in Canada on 416V 4-wire Wye 
distributed systems. The non-inductive rating for 230V “a.c. mains” 
with one ungrounded conductor is 6.0A. 

ORDERING INFORMATION 

Before ordering please determine the following: 

1. The body type: 2-way or 3-way 
2. The actuator voltage : 24V/50-60Hz 
3. The pipe fitting, size, and flow capacity rating (Cv) required. 
4. Order Specification Number 
5. Accessories, if desired. 

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 

1. Your local Home and Building Control Sales Office (please check the white pages of your phone directory). 
2. Honeywell Limited, 155 Gordon Baker Rd., North York, ON M2H 3N7. 

In U.S.A. - Honeywell Inc., 1885 Douglas Drive North, Minneapolis, Minnesota 55422-4386 (612) 951-1000.  International Sales and Service 
Offices in all principal cities of the world.  Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, 
Taiwan, United Kingdom, U.S.A. 

Summary of Contents for T6380

Page 1: ...y white sculpted styling Vertical or horizontal mounting configurations Adjustment ranges 55 to 90 F or 13 to 32 C Easy to use set point knob LED system status indicator OFF de energizes all connected loads Three level fan speed selection Constant cycled or on auto selectable fan operation available Models for manual or remote heat cool changeover heating only or cooling only systems Models for 2 ...

Page 2: ... horizontal mount Wiring Connections Screw terminal block suitable for 1 14 AWG 2 18 AWG or 1 1 5 mm2 copper wire Approvals CSA Certified LR1322 Underwriters Laboratories Listed E47434 Accessories 272824A T6380 Range stop cover locking kit 272827A T6380 replacement cover with Cool Warmer Fig 1 Nominal dimensions in inches and millimetres 50 60 Hz 110 130V 208 V 220 240V 277 V Full Load Amps 5 8 3 ...

Page 3: ... terminal block with 1 14 AWG or 2 18 AWG solid or stranded copper wires NEUTRAL Fig 2a T6383A for 2 pipe constant fan cooling only T6383A Fig 3 T6383B 2 pipe heat cool manual changeover constant L2 L1 HOT NEUTRAL FAN RED BLU BRN Heat ORG Cool YEL Off 1 2 3 WHT VIO BLK fan TO COOLING VALVE T6383B WHT L2 NEUTRAL L1 HOT Med BLU Hi BRN Lo RED BLK SYSTEM FAN Heat Off Cool Heat ORG Cool YEL TOHEATING C...

Page 4: ...g only cycled fan Fig 6 T6381B 2 pipe heat cool manual changeover cycled fan T6381A T6381B FAN RED BRN Heat ORG Cool YEL Off 1 2 3 WHT VIO TO COOLING VALVE BLK External jumper BLU L2 HI MED LO L1 HOT WHT L2 NEUTRAL L1 HOT BLU BRN RED BLK SYSTEM FAN Heat Off Cool Heat ORG Cool YEL FAN HI MED LO TO HEATING COOLING VALVE External jumper FAN NEUTRAL Fig 5b T6381A 2 pipe heating only cycled fan Fig 7a ...

Page 5: ...The speed at which the air is circulated is con trolled by the FAN switch Continuous ON or intermittent HI FAN MED LO AUTO fan operation is determined by model number CHECK OUT Turn power on Check out operation according to the SYSTEM switch present SYSTEM switch OFF de energizes valve and fan circuits Fig 8b T6387A 2 pipe heating only on auto fan Models T6381B T6383B SYSTEM HEAT OFF COOL Set the ...

Page 6: ...s marked 55 to 90 F or 13 to 32 C depending on the model Set the dial indicator marker to the desired temperature CALIBRATION T6380 thermostats are accurately calibrated at the factory under controlled conditions Do not attempt to field calibrate this device This thermostat has line voltage connections Home and Building Control In U S A Helping You Control Your World Honeywell Ltd Honeywell Inc 15...

Reviews: