Honeywell T4800A Product Data Download Page 2

T4800A PRECISION ELECTRONIC ELECTRIC HEATING THERMOSTAT

68-0151—1

2

SPECIFICATIONS

IMPORTANT

The Specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed
specifications. Also, this product is tested and
calibrated under closely controlled conditions, and
some minor differences in performance can be
expected if those conditions are changed. For exact
engineering specifications, contact your Honeywell
sales representative.

TRADELINE

®

 Models

TRADELINE® models are selected and packaged to provide
ease of stocking and handling and also maximum
replacement value. TRADELINE® model specifications are
as follows:

Model:
T4800A makes heating circuit on temperature fall. Single
pole, single throw. (See Fig. 2.) Range: 40

°

 to 80

°

F (5

°

 to

25

°

C).

Type of Switching:

Cool Switch Triac/relay combination.

Wiring Connections:
6 in. (150 mm) stranded copper leadwires, suitable for
connecting to aluminum wiring when approved special
service CO/ALR solderless connectors are used.

Electrical Rating:

Noninductive (resistive) rating:
2.7A minimum (750W @ 240V; 560W @ 208V) to

16A maximum (3800W @ 240V; 3300W @ 208V)

Performance Certification:
16A at 208 or 240 Vac.

Performance Specifications:

Precision: 

±

1

°

F (0.5

°

C) differential with thermistor time

constant of 10 seconds.

Accuracy: 1

°

F (0.5

°

C) droop average for range of loads.

Conforms to NEMA DC3 standard applied to low voltage

thermostats.

Setpoint Adjustment:
Control knob on front of thermostat.

Sensing Element:
Electronic thermistor.

Dimensions:
See Fig. 1.

Red LED Indicator:
Lights as heat comes on.

Mounting Means:
Mount directly on vertical 2 x 4 inch outlet box, or on
4 x 4 inch outlet box with ring adapter (ordered separately).

Approvals:

CSA certified: LR1322.
Underwriters Laboratories Inc. Listed: File No. E47434,

Guide No. XAPX.

40

50

60

70

80

°F

M7102

3-1/8 (80)

1-5/16
(34)

1-5/16
(34)

4-3/4
(120)

3-1/4
(82)

3/4
(19)

7/8 (23)

Fig. 1. Nominal dimensions in in. (mm).

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number or specify

1. Model number
2. Voltage.

If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:

1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Honeywell Customer Relations

Honeywell, 1885 Douglas Drive North
Golden Valley, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Dr, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

Summary of Contents for T4800A

Page 1: ...writers Laboratories Inc Listed Conforms to NEMA standard DC3 for thermostat accuracy Rugged molded thermoplastic mounting base with captive mounting screws Energy efficient and economical Patented electronic switch requires no leveling High sensitivity solid state temperature sensing element Nonpolarized leadwire connections Adjustment range is 40 to 80 F 5 to 25 C Premier White finish One piece ...

Page 2: ...nt of 10 seconds Accuracy 1 F 0 5 C droop average for range of loads Conforms to NEMA DC3 standard applied to low voltage thermostats Setpoint Adjustment Control knob on front of thermostat Sensing Element Electronic thermistor Dimensions See Fig 1 Red LED Indicator Lights as heat comes on Mounting Means Mount directly on vertical 2 x 4 inch outlet box or on 4 x 4 inch outlet box with ring adapter...

Page 3: ...ications 쐃 Disconnect power to the thermostat to prevent electrical shock or equipment damage All wiring must comply with local electrical codes and ordinances 쐇 Remove the old thermostat from the wall taking care not to damage the wiring insulation 쐋 Check the old wire insulation for cracks nicks or fraying Apply approved electrical tape to insulate wires or replace wires as necessary 쐏 Carefully...

Page 4: ...setting as necessary moving the knob only one or two degrees at a time The precise temperature control of the T4800 allows the user to select a lower temperature setting which saves energy while maintaining comfort OPERATION The T4800 Thermostat provides precise temperature control with minimum droop of resistance rated electric baseboard heating equipment The T4800 controls room temperature withi...

Reviews: