T4398A,B HIGH PERFORMANCE ELECTRIC HEAT THERMOSTATS

68-0147—2

3

RECYCLING NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do 

not place your old

control in the trash.

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of any control containing mercury in a
sealed tube.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow these

instructions could damage the product or cause a
hazardous condition.

2. Check the ratings on the product to make sure the

product is suitable for your application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

WARNING

HIGH VOLTAGE CONTROL.
ELECTRICAL SHOCK HAZARD.
Follow local codes and ordinances when installing this
thermostat. Improper handling can cause serious
injury or death.

CAUTION

1.

Disconnect power supply to prevent electrical
shock or equipment damage.

2.

If connecting with aluminum conductors, use CO/
ALR solderless wire connectors to avoid fire
hazard.

3.

Do not remove thermostat cover until wiring is
complete to avoid damaging the sensing element.

Location

Install a vertical outlet box, which is used to mount the
thermostat on, about 5 ft (1.5 m) above the floor in an area
with good air circulation at room temperature.

Do not install the thermostat where it may be affected by:

drafts or dead spots behind doors, in corners or under
cabinets.

hot air from convectors.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

Wiring and Mounting

CAUTION

1.

Handle the thermostat with care to avoid
damaging the sensing element or control.

2.

Use a separate limit control in the heating
appliance.

IMPORTANT

If locking cover feature is desired, insert the locking
cover clip in the thermostat base before mounting
the thermostat on the wall. See Fig. 7.

Replacement Applications

���

Disconnect power to thermostat to prevent electrical
shock or equipment damage. All wiring must comply
with local electrical codes and ordinances.

���

Remove the old thermostat from the wall, taking care
not to damage the wiring insulation.

���

Check the old wire insulation for cracks, nicks or fraying.
Apply approved electrical tape to insulate wires or
replace wires as necessary.

���

Do not remove T4398 Thermostat Cover. Using wire
connectors approved for No. 12 wires, make line
voltage connections directly to leadwires on thermostat.
See Figs. 2 and 3 for typical wiring connections.

���

Prebend and push solid wires into the outlet box.

���

Remove the thermostat cover by grasping the top and
bottom edges and pulling outward away from the base.

���

Turn the setting dial so the indicator is at the 12 o’clock
position to prevent damaging the sensing element when
mounting the thermostat.

���

Mount the thermostat on the outlet box as shown in
Fig. 4. Secure the thermostat by tightening the two
mounting screws.

M5795A

FRONT VIEW

SIDE VIEW

80

70

60

50

˚F

4-3/8
(111)

2-7/8 (73)

1-1/2

(39)

1-3/4 

(48)

3/4

(19)

1/2 (13)

1/2 (13)

2-1/8

(54)

3-1/4

(83)

Fig. 1. T4398 approximate dimensions in in. (mm).

Summary of Contents for T4398A1021 - Electric Heat Thermostat

Page 1: ...asy installation Cover thermometer indicates room temperature Rugged plastic mounting base Contemporary white finish complements almost any decor T4398A B High Performance Electric Heat Thermostats Contents General 1 Features 1 Specifications 2 Ordering Information 2 Installation 3 Settings and Adjustment 4 Checkout 5 Operation 6 GENERAL The T4398A B High Performance Electric Heat Thermostats prov...

Page 2: ...riters Laboratories Listed File no E47434 guide no XAPX Canadian Standards Association Listed File no LR1322 Accessories 272804A Range Stop and Locking Screw Assembly Includes locking cover screws Tinnerman cilps wrench and range stops two plastic pins to insert inside cover for field selection of minimum and maximum temperature settings Table 1 Thermostat Specifications Model Number Switching Tem...

Page 3: ...ehind doors in corners or under cabinets hot air from convectors radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat Wiring and Mounting CAUTION 1 Handle the thermostat with care to avoid damaging the sensing element or control 2 Use a separate limit control in the heating appliance IMPORTANT If locking cover featur...

Page 4: ...ith local electrical codes and ordinances Run line voltage wiring to the thermostat location Do not remove T4398 Thermostat Cover Using wire connectors approved for No 12 wires make line voltage connections directly to leadwires on thermostat See Figs 2 and 3 for typical wiring connections Prebend and push solid wires into the outlet box Remove the thermostat cover by grasping the top and bottom e...

Page 5: ...d the thermometer Turn the setting dial clockwise until the switch makes click sound Firmly hold the setting dial with one hand Using the other hand turn the outer scale ring counterclockwise until the 12 o clock position of the scale ring is the same temperature as the cover thermometer See Fig 5 Wait five minutes and recheck the calibration Fig 5 Calibrating thermostat Setting Range Stops Use th...

Page 6: ...nt is more sensitive to temperature changes than a bimetal sensor This accuracy usually associated with low voltage thermostats is now available for line voltage control Electric heat thermostats are often affected by the heat generated in the control Temperature control points can vary or droop 2 to 4 F 1 to 3 C depending on the load demand Temperature settings are adjusted to offset this The T43...

Page 7: ...T4398A B HIGH PERFORMANCE ELECTRIC HEAT THERMOSTATS 68 0147 2 7 ...

Page 8: ... Printed in U S A Home and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 Printed on recycled paper containing at least 10 post consumer paper fibers www honeywell com yourhome ...

Reviews: