Honeywell T4098A Product Data Download Page 6

T4098A,B DELUXE ELECTRIC HEAT THERMOSTATS

68-0146—3

6

Fig. 7. Locking cover.

M5799

ALLEN WRENCH

THERMOSTAT 
COVER

LOCKING 
COVER 
CLIP

THERMOSTAT 
BASE

LOCKING 
COVER SCREW

50

90

60

8

0

°F

50    70    90

7

0

CHECKOUT

IMPORTANT

Make sure that all wiring connections are secure
before beginning checkout.

After thermostat installation is complete, check operation as
follows:

���

Move the thermostat setting knob clockwise until the
switch makes (clicking sound); the electric heater starts.

���

Move the setting knob fully counterclockwise; the switch
breaks and the electric heater stops.

���

Allow the thermostat to operate for several hours to
determine the appropriate temperature setting. Adjust
the setting as necessary.

OPERATION

The T4098 Thermostat provides precise temperature control
of resistance-rated electric baseboard heating equipment with
minimum droop. The T4098 controls room temperature within
2

°

F (1

°

C), regardless of the load of the baseboard heater.

The vapor-filled dual diaphragm sensing element is more
sensitive to temperature changes than a bimetal sensor. This
accuracy, usually associated with low voltage thermostats, is
now available for line voltage control.

Electric heat thermostats are often affected by the heat
generated in the control. Temperature control points may vary
or droop 2

°

 to 4

°

F (1

°

 to 3

°

C) depending on the load demand;

however, temperature settings are adjusted to provide offset.
The T4098 provides precise control with minimum droop. This
allows better control of room temperatures from day-to-night
and season-to-season while saving energy.

Summary of Contents for T4098A

Page 1: ...nsive vapor filled dual diaphragm sensing element provides 2 F 1 C sensitivity with minimum droop Replaces virtually all standard wall mounted line voltage thermostats Includes long lasting Micro Switch mechanism Color coded leads allow easy installation Protective cover door opens to provide access to setpoint knob Attractive sloped faceplate allows easy viewing of temperature Classic styling CON...

Page 2: ...rds Association Performance Certified C273 4 Accessories 272804A Range Stop and Locking Screw Assembly Includes locking cover screws Tinnerman clips wrench and range stops two plastic pins to insert inside cover for field selection of minimum and maximum temperature settings ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE wholesaler or distributor re...

Page 3: ...lectrical shock or equipment damage 2 If connecting with aluminum conductors use CO ALR solderless wire connectors to avoid fire hazard 3 Do not remove thermostat cover until wiring is complete to avoid damaging the sensing element Location Install a vertical outlet box that is used to mount the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at room temperature Do ...

Page 4: ...thermostat base with one hand use the other hand to remove the thermostat cover by grasping the bottom cover edge and pulling outward away from the thermostat base Mount the thermostat on the outlet box as shown in Fig 4 Secure the thermostat by tightening the two mounting screws WALL MOUNTING SCREWS 2 M5794 OUTLET BOX THERMOSTAT BASE Fig 4 Mounting thermostat to outlet box New Applications Discon...

Page 5: ...se the range stops included to limit the maximum and minimum temperatures that may be set Move the thermostat setting knob to the desired maximum temperature Remove the thermostat cover Adjust the knob indicator tab between the range stop positions to prevent interference Insert the range stop pins in the desired positions on the back of the thermostat cover See Fig 6 Make sure pins are completely...

Page 6: ...setting as necessary OPERATION The T4098 Thermostat provides precise temperature control of resistance rated electric baseboard heating equipment with minimum droop The T4098 controls room temperature within 2 F 1 C regardless of the load of the baseboard heater The vapor filled dual diaphragm sensing element is more sensitive to temperature changes than a bimetal sensor This accuracy usually asso...

Page 7: ...T4098A B DELUXE ELECTRIC HEAT THERMOSTATS 68 0146 3 7 ...

Page 8: ...ll Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 68 0146 3 C H Rev 4 96 Printed in U S A Home and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 Printed on recycled paper containing at least 10 post consumer paper fibers www honeywell com building components ...