Honeywell T4031A Product Data Download Page 3

3

T4031A,B,P; T6031A,B REFRIGERATION TEMPERATURE CONTROLLERS

60-2177—3

7617ABZ Bag Assembly—for mounting controller to fan coil

units

801534 Calibration Wrench
7640HY Standoff Bracket Bag Assembly—to mount

controller to an insulated duct

130883 Universal Mounting Bracket
194899 Tamper-resisting Insert Button
Celsius Scaleplates:
194486 D: -15

°

C to +35

°

C replaces (0

°

F to 100

°

F)

scaleplate

194486H: 15

°

C to 75

°

C replaces (55

°

F to 175

°

F)

194486F: 75

°

C to 125

°

C replaces (160

°

F to 260

°

F)

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow them

could damage the product or cause a hazardous
condition.

2. Check the ratings given in the instructions and on the

product to make sure the product is suitable for your
application.

3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation

as provided in these instructions.

CAUTION

• Disconnect power supply before installation to prevent

electrical shock and equipment damage.

• Do not damage or change shape of capsule. De-

formed capsule will cause calibration offset.

Mounting

Install controller in any convenient location. Make sure that the
sensing bulb reaches the system to be controlled. The ambient
temperature must not exceed 125

°

F (52

°

C) in the area where

the controller is installed.

Install the sensing element where it can sense the average
temperature. Avoid sharp bends or kinks in the capillary tubing
that can affect the accuracy of the controller. Carefully coil the
excess capillary tubing and leave it directly beneath the
controller.

The 130883 Mounting Plate furnished with TRADELINE®
models allows the control to be mounted in existing mounting
holes.

Duct Installation

Position the sensing bulb in the duct to sense the average air
temperature. Avoid mounting the bulb close to hot pipes,
cooling coils, etc.

The 107324A Bulb Holder is available for suspending the bulb
in a duct. See Fig. 2.

Electrical Ratings:

120 Vac

240 Vac

Normally

Closed

Normally

Open

a

Normally

Closed

Normally

Open

a

Full Load

Amp

8

16

5.1

8

Locked Rotor

Amp

48

80

30.6

40

a

Makes on temperature rise.

Pilot Duty:

125 VA

Dimensions:

See Fig. 1

M4496

KNOCKOUT FOR 1/2 IN. (13 MM)
CONDUIT (2)

2  (51)

15/16

(24)

2-1/8  (54)

4-3/16

(107)

29/32

(23)

7/32

(6)

5-5/8
(136)

2-1/4  (57)

1-3/16

(30)

3/8

(9)

17/32

(13)

7/32 (6)
DIA. (3)

3/8 (10)
DIA. (3)

Fig. 1. Dimensions of T4031, T6031 in in. (mm).

Underwriters Laboratories Inc.:

Listed

Maximum Ambient Operating Temperature:

125

°

F (52

°

C)

Accessories:

112622AA Immersion Well—short-necked, 1/2 in. NPT,

copper

7617ABY Compression Fitting—50 psi water, 15 psi air
107324A Bulb Holder—for duct installation
105900 T-strap—for strapping bulb to pipe

Summary of Contents for T4031A

Page 1: ...es and defrost termination Universal mounting bracket is available for easy replacement of other controllers Models are available with various control ranges Control setpoint is dial knob adjustable Models are available with fixed or adjustable tempera ture differentials Capillary lengths are 5 8 or 20 ft 1 5 2 4 6 1m depending on model Reliable snap acting spst or spdt switch Ambient temperature ...

Page 2: ...trol Sales office check white pages of your phone directory 2 Home and Building Control Customer Relations Honeywell 1885 Douglas Drive North Minneapolis Minnesota 55422 4386 In Canada Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 International Sales and Service Offices in all principal cities of the world Capillary Lengths and Temperature Ranges Capillary Length...

Page 3: ...ed The ambient temperature must not exceed 125 F 52 C in the area where the controller is installed Install the sensing element where it can sense the average temperature Avoid sharp bends or kinks in the capillary tubing that can affect the accuracy of the controller Carefully coil the excess capillary tubing and leave it directly beneath the controller The 130883 Mounting Plate furnished with TR...

Page 4: ... tubing 5 Slide assembly into boiler plug and tighten packing nut 6 Refill system and check for leaks Neatly coil excess capillary tubing Using Immersion Well Fig 4 1 Drain system Screw the well into threaded fitting 2 Refill system and check for leaks 3 Insert sensing bulb into well until it bottoms 4 Fit bulb retaining clamp over immersion well flange and capillary tubing and tighten screw M8970...

Page 5: ...All controllers are carefully tested and calibrated at the factory under controlled conditions If the controller is not operating at a temperature corresponding to the scale and differential setting verify that the bulb senses the average temperature of the medium If the temperature of the controlled medium is changing rapidly the differential will appear wider than its setting M4497 TERMINAL SCRE...

Page 6: ...6 T4031A B P T6031A B REFRIGERATION TEMPERATURE CONTROLLERS 60 2177 3 ...

Page 7: ...7 T4031A B P T6031A B REFRIGERATION TEMPERATURE CONTROLLERS 60 2177 3 ...

Page 8: ... World Home and Building Control Honeywell Limited Honeywell Limitée 740 Ellesmere Road Scarborough Ontario M1P 2V9 Home and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 60 2177 3 J H Rev 5 95 Printed in U S A QUALITY IS KEY www honeywell com building components ...