SYSNet™ QS7700A NETWORK INTERFACE ControlBus™ MODULE

63-2284—2

4

3. Recommended wiring for ControlBus™ Module for

communications routing purposes is unshielded 22 AWG,
two-wire twisted cable and one wire for ground, if the
leadwire run and noise conditions permit. If necessary,
Belden 8771 shielded cable or equivalent can be used.
Be aware that the BCS7700 chassis module must be at
one end of the daisy chain and the module on the
farthest end of the daisy chain configuration string require
a 120 ohm, 1/4 watt (minimum) resistor termination
across terminals 1 and 2 of the electrical connectors.
See Fig. 6.

a.

Do not route the ControlBus™ cable in conduit
with line voltage circuits.

b.

Do not route the ControlBus™ cable close to the
ignition transformer.

c.

Route the ControlBus™ cable outside of conduit
if properly supported and protected from damage.

d.

Route the ControlBus™ cable so that all devices
are connected in a daisychain(A-A, B-B, C-C).
The BCS 7700 Chassis Module must be at one
end of the daisy chain configuration string. The
interconnection of all other devices is not
important, except that the device at the distant
end of the daisy chain configuration string must
be terminated with a 120 ohm, 1/4 watt resistor
between terminals A and B.

4. Maximum wire lengths can be 4000 ft (1219m) for the

ControlBus™ RS-485 interface under ideal conditions.

Procedure

���

Refer to Fig. 6 for proper wiring.

���

Be sure that power is removed from the control panel
by opening the main disconnect before beginning wiring
to the electrical connectors. More than one
disconnection can be involved.

���

Select the location of the Network Interface Unit to be
mounted:

a.

Near a phone line.

b.

Within 4000 ft (1219m) of all BCS 7700s that will
be connected to the Network Interface Unit.

c.

Within 50 ft (15m) of the personal computer that
will be connected to the 25-pin RS-232 port of the
Network Interface Unit.

���

Mount the Network Interface Unit and insert the
ControlBus™ Module into the Network Interface Unit
slot, see Fig. 2 and 5.

���

Route the ControlBus™ cable so that all devices are
connected in a daisychain (A-A, B-B, C-C). The BCS
7700 Chassis Module must be at  one end of the daisy
chain configuration string. The interconnect of all other
devices is not important, except that the device at the
distant end of the daisy chain configuration string must
be terminated with a 120 ohm, 1/4 watt resistor
between terminals A and B. Remove any other
termination resistors and install a 120 ohm, 1/4 watt
resistor at the final device in the string.

���

Connect L1, L2 and Ground (GND) to the pigtails
(Q7700A 

only).

���

Connect the 5-pin DIN connector cord, from the
switching power supply, to the 5-pin DIN conctor on the
Network Interface Unit. Connect the IEC power cord,
from the switching power supply, to a line voltage
source (Q7700B only).

Fig. 2. ControlBus™ Module mounting.

M7437B

ELECTRICAL
CONNECTOR

EDGE
CONNECTOR

CONTROLBUS
MODULE

NETWORK
INTERFACE
UNIT

Fig. 3. RS-232 Interface insertion

(serial communications).

25-PIN 
RS-232C
CONNECTOR

NETWORK
INTERFACE
UNIT

M7432B

���

Insert the plug-in card slots into any open slots of the
Network Interface Unit.

���

Install the covers, power wiring compartment and
Network Interface Unit.

Connect the serial port of the modem to the 9-pin
RS-232 connector of the Network Interface Unit
(see Fig 4).

Connect the serial port of the personal computer to the
25-pin RS-232C port on the Network Interface Unit for
local personal computer application, see Fig. 3.

Do not exceed 600 mA current draw, six card
maximum, total capacity of the plug-in cards. Refer to
the ControlBus™ Module device label and this
specification for individual loads.

Check all wiring with Fig. 6 before installing an
electrical connector.

Install all electrical connectors.

Restore power to the Network Interface Unit.

Summary of Contents for SYSNet QS7700A

Page 1: ...ler Control System BCS 7700 FEATURES Up to six ControlBus Modules per Network Interface Unit Remote programming of nonsafety BCS 7700 values via the ControlBus Modules Local and remote annunciation of BCS 7700 faults Personal computer user interface Modular construction Microsoft Windows based Combustion System Manager user interface Microsoft Windows based SYSNet Operator user interface Contents ...

Page 2: ...g 1 Weight 8 oz unpacked Accessories 221237 1698 Cover Assembly Q7700 Network Interface Unit 221240 1698 Cover Assembly Q7700 Electrical Enclosure Network Interface Unit 202433 Slot Inserts ControlBus Slots Base Unit 200603 ControlBus Electrical Connector Approvals Underwriters Laboratories Inc File No MP268 Guide No MCCZ2 Canadian Standards Association LR80141 Federal Communications Commission Pa...

Page 3: ...ation and removal of the wiring compartment cover Network Interface Unit cover electrical connectors and ControlBus Modules a Allow for an additional 2 1 2 inches 64 mm minimum below the Network Interface Unit for electrical connector installation b Allow for an additional 1 1 2 inches 38 mm minimum on each side for electrical housing cover insertion and wiring Remove the ControlBus Module by usin...

Page 4: ...sonal computer that will be connected to the 25 pin RS 232 port of the Network Interface Unit Mount the Network Interface Unit and insert the ControlBus Module into the Network Interface Unit slot see Fig 2 and 5 Route the ControlBus cable so that all devices are connected in a daisychain A A B B C C The BCS 7700 Chassis Module must be at one end of the daisy chain configuration string The interco...

Page 5: ...EEN GROUND THE SYSTEM CONTROLBUS MUST BE ROUTED SO THAT ALL DEVICES ARE CONNECTED DAISY CHAIN CONFIGURATION A A B B C C THE SYSTEM CHASSIS AND PROGRAM MODULES MUST BE AT ONE END OF THE STRING THE INTERCONNECTION OF DEVICES IS NOT IMPORTANT EXCEPT THE DEVICE ON THE FARTHEST END OF THE DAISY CHAIN CONFIGURATION STRING MUST BE TERMINATED WITH A 120 OHM 1 4 WATT RESISTOR BETWEEN TERMINALS A AND B REMO...

Page 6: ...SYSNet QS7700A NETWORK INTERFACE ControlBus MODULE 63 2284 2 6 ...

Page 7: ...SYSNet QS7700A NETWORK INTERFACE ControlBus MODULE 63 2284 2 7 ...

Page 8: ... Hong Kong Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 Honeywell Latin American Division Miami Lakes Headquarters 14505 Commerce Way Suite 500 Miami Lakes FL 33016 Helping You Control Your World 63 2284 2 G R Rev 7 96 Printed in U S A www honeywell com bbc Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapo...

Reviews: