Honeywell Super Tradeline Q674L Installation Instructions Manual Download Page 2

69-0392—9

2

T874R THERMOSTATS AND Q674L SUBBASES

OPERATION

On a 2-heat thermostat, the two stages of heat 

make

sequentially as the temperature drops. 

Make refers to the

mercury switch initiating a call for heat or cool.

There is about 1

°

 F (0.6

°

 C) between stages so the sec-

ond stage makes only when the first stage can not handle
the load. The 1

°

 F (0.6

°

 C) is referred to as the 

interstage

differential.

The light emitting diodes (LED) on the subbase light when
something specific happens within the system. When an
LED lights, refer to this list for the meaning:

EM. HT.: Emergency heat is operating. The compres-

sor has failed, and the heat pump is not operating.
LED lights when system switch is placed in the
EM.HT. position by the homeowner.

AUX.HT.: Auxiliary heat is operating, which means the

weather is so cold that the heat pump cannot handle
the load.

CHECK: System needs to be checked. See heating

sys-tem instructions for specific meaning.

NOTE:

LEDs are not field replaceable or addable.

RECYCLING NOTICE

This control contains mercury in a sealed tube. Do n

ot

place control in the trash at the end of its useful life.

If this control is replacing a control that contains
mer-cury in a sealed tube, do 

not place your old

control in the trash.

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of this control, or of an old control
containing mercury in a sealed tube.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazard-
ous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

CAUTION

1.

Disconnect power supply to prevent electrical
shock or equipment damage.

2.

To prevent interference with the thermostat
linkage, keep wire length to a minimum and
run wires as close as possible to the subbase.

3.

Push excess wire back into the hole and plug
hole to prevent drafts from affecting thermo-
stat operation.

4.

Do not overtighten thermostat captive
mounting screws because damage to
subbase threads can result.

5.

Do not short across coil terminals on heating
relay or gas valve. This can burn out the
thermostat heat anticipator.

6.

Never install more than one wire per terminal
unless factory-supplied jumper with spade
terminals is used.

IMPORTANT

Thermostats are calibrated at the factory using
subbase mounted at true level. Inaccurate
subbase leveling causes the actual temperature
to deviate from the setpoint temperature.

Location

Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
Do not install the thermostat where it can be affected by:

drafts or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

Mounting The Subbase

The thermostat subbase can be mounted on a vertical
outlet box, horizontal outlet box or directly on the wall.

1. If you must mount the subbase on a vertical outlet

box, order Honeywell 193121A Adapter Assembly.
See Fig. 1. The assembly includes an adapter ring,
two screws and a cover plate to cover marks on the
wall. Install the ring and cover plate on the vertical
outlet box.

For a wall installation, hold subbase in position and
mark holes for anchors. See Fig. 2. Obtain wall
anchors locally. Be careful that the wires do not fall
back into the wall opening. Set aside subbase. Drill
two 3/16 in. (5 mm) holes and gently tap anchors
into the holes until flush with the wall.

Summary of Contents for Super Tradeline Q674L

Page 1: ... AUX HT EM HT CHECK Manual Heat or Cool SUPER TRADELINE fixed heat anticipation Factory installed jumper across W1 and Y1 Auto fan in EM HT 8 Y594R1615 T874R1822 Q674L1710 AUX HT EM HT CHECK Manual Heat or Cool TRADELINE fixed heat anticipation Auto fan in EM HT 10 Y594R1664 T874R1871 Q674L1736 EM HT Manual Cool TRADELINE exact replacement for York model no 2TH11702224 9 Y594R1672 T874R1889 Q674L1...

Page 2: ...e check out product operation as provided in these instructions CAUTION 1 Disconnect power supply to prevent electrical shock or equipment damage 2 To prevent interference with the thermostat linkage keep wire length to a minimum and run wires as close as possible to the subbase 3 Push excess wire back into the hole and plug hole to prevent drafts from affecting thermo stat operation 4 Do not over...

Page 3: ...l adjustments IMPORTANT An incorrectly leveled subbase causes the temperature control to deviate from setpoint Wiring the Subbase All wiring must comply with local electrical codes and ordinances Follow equipment manufacturer wiring instructions when available To wire subbase proceed as follows 1 Connect the system wires to the subbase See Fig 5 12 A letter code for identification is located near ...

Page 4: ...L POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FIELD REMOVABLE JUMPER 1 2 2 M2970 THERMOSTAT SUBBASE SYSTEM COMPONENTS M5072A HOT L1 L2 1 LACO CHP Y B E O G L X W2 W3 R ODT 1 RTD 1 EHR 1 RTD 2 ODT 2 EHR 2 RTD 3 RD SYSTEM MONITOR FAN RELAY COMPRESSOR CONTACTOR COOL CHANGEOVER VALVE EM HT RELAY RTD 1 AUX HT LED GREEN EM HT LED RED FAN SWITCH ON AUTO SYSTEM SWITCH EM HT H...

Page 5: ...TO ON SYSTEM SWITCH EM HT HEAT OFF COOL EM HT LED RED AUX HT LED GREEN M1030A H1 FALL C L1 HOT L2 1 EM HT LED RED AUX HT LED GRN W3 O L G R W2 E X X2 B W1 Y AUX HT RELAY EM HT RELAY HEAT CHANGEOVER VALVE W1 RELAY COMPRESSOR RELAY W3 RELAY COOL CHANGEOVER VALVE COMPRESSOR MONITOR FAN RELAY H2 FALL H1 ANTICIPATOR C ANTICIPATOR H2 ANTICIPATOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECT...

Page 6: ... DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M3173A THERMOSTAT SUBBASE SYSTEM COMPONENTS 1 H2 FALL H1 FALL C L1 HOT L2 1 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED THERMOSTAT SUBBASE SYSTEM COMPONENTS M5068 H1 ANTICIPATOR C ANTICIPATOR H2 ANTICIPATOR 11 6 5 4 3 2 1 FAN SWITCH AUTO ON SYSTEM SWITCH EM HT HEAT OFF COOL AUX HT LED GREEN EM HT LED RED Y B X E ...

Page 7: ...TOR RESET HEATER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M3173A THERMOSTAT SUBBASE SYSTEM COMPONENTS 1 L1 HOT L2 1 X L W2 EM HT LED RED AUX HT LED GRN AUX HT RELAY FAN RELAY B RELAY G COOL CHANGEOVER VALVE EM HT RELAY COMPRESSOR CONTACTOR O Y E B SYSTEM SWITCH EM HT HEAT OFF COOL H1 C1 ANTICIPATOR C1 H1 FALL H2 W3 AUX HT RELAY H2 ANTICIPATOR 1 2 3 2 3 POWER SUPPLY...

Page 8: ...ol nameplate has no rating or if further adjustment is necessary use the following procedure to determine the current draw Measure the current draw with the thermo stat removed and the power on 1 Connect an ac ammeter of appropriate range between the heating terminals of the subbase Stage 2 between W2 and R 2 Move the system switch to HEAT 3 After one minute read the ammeter and record the reading...

Page 9: ...ctric strip heater should de energize The EM HT LED remains on until system switch is moved to another position Fan Move the subbase system switch to OFF and the fan switch to ON The fan should run continuously When the fan switch is in the AUTO position fan operation is con trolled by the heating or cooling system CALIBRATION Thermostat T874 Thermostats are accurately calibrated at the factory Th...

Page 10: ...69 0392 9 10 T874R THERMOSTATS AND Q674L SUBBASES ...

Page 11: ...69 0392 9 11 T874R THERMOSTATS AND Q674L SUBBASES ...

Page 12: ...BASES 69 0392 9 G H Rev 10 97 www honeywell com yourhome Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Reviews: