Honeywell Super Tradeline Q674F Installation Instructions Manual Download Page 7

60-1147-4

7

Checkout

HEATING

Move the system switch on the Q674 to HEAT or AUTO

(if used) and the fan switch to AUTO. Move the heating set
point lever on the T874 about 10

°

 F [6

°

 C] above room

temperature. Heating equipment should start and the fan
should run. Move the heat lever about 10

°

 F [6

°

 C] below

room temperature. The heating equipment and fan should
shut off.

NOTE: In heat pump applications, time delays are involved

before the compressor is activated to prevent short cy-
cling. The delays are provided by a timer, which prevents
the compressor from starting for several minutes after the
thermostat last turned the compressor off, or after the
system first received power.

COOLING

Move the system switch on the Q674 to COOL or AUTO

(if used) and the fan switch to AUTO. Move the cooling set
point lever on the T874 about 10

°

  F [6

°

  C] below room

temperature. The cooling equipment should start (see NOTE
above). Move the cool lever about 10

°

 F [6

°

 C] above room

temperature. The cooling equipment and fan should shut off.

FAN

Move the subbase system switch to OFF, and the fan

switch to ON. The fan should run continuously. Move the fan
switch to AUTO. In this position, fan operation is controlled
by the heating or cooling system control circuit.

Calibration

THERMOSTAT

T874 Thermostats are accurately calibrated at the factory.

They do not have provision for field calibration.

THERMOMETER

The thermometer in your thermostat has been accurately

calibrated at the factory. The thermometer should need
adjustment only if it has been dropped or shifted due to
mishandling.

If the set point lever and the thermometer reading do

not agree:

1. Remove the thermostat cover by pulling up from the

bottom of cover until it clears the mounting slots.

2. Set the thermostat cover on a table near an accurate

thermometer.

3. Allow 10 or 15 minutes for cover thermometer to

sense area temperature; compare the readings. Be careful
not to touch the thermometer or breathe on it.

4. If the readings are the same, replace the cover and put

the system into operation.

5. If the readings are different, insert a small screw-

driver in the thermometer slot (Fig. 12) and turn it until the
thermometers have the same reading.

6. Replace thermostat cover and put the system into

operation.

NOTE: Radiant heat from your hands will offset the ther-

mometer reading. After making each adjustment, wait 10
or 15 minutes for the thermometer to stabilize before
comparing.

Fig. 12—Thermometer calibration.

M5070

Summary of Contents for Super Tradeline Q674F

Page 1: ...sedamagetosubbasethreads may result 4 Do not short across coil terminals on the relay This may burn out the thermostat heat anticipator IMPORTANT Thermostats are calibrated at the factory using subbases mounted at true level An inaccurately leveled subbase will cause thermostat control devia tion Operation On a two heat thermostat the two stages of heat make sequentially as the temperature drops M...

Page 2: ...tain wall anchors locally Take care that the wires do not fall back into the wall opening Set aside subbase Drill four 3 16 in 4 8 mm holes and gently tap anchors into the holes until flush with the wall 2 Pullwiresthroughthecoverplate ifused andsubbase cable opening Fig 3 3 Secure the cover plate if used and subbase with the screws provided Do not fully tighten the subbase screws 4 Levelthesubbas...

Page 3: ...nsert is com pletelyseatedinrecessedarea Letsetpointscalepopback and set levers to desired positions FOR STRAIGHT INSERTION STRIP 5 16 in 8 mm FOR WRAPAROUND STRIP 7 16 in 11 mm SUBBASE TERMINAL SCREW M928 BARRIER Fig 5 Internal schematic and typical wiring diagram for T874N and Q674C M1860 G R W2 X L1 HOT L2 AUTO SYSTEM SWITCH AUTO ON FAN SWITCH 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOA...

Page 4: ...ITCH EM HT HEAT OFF COOL H1 ANTICIPATOR H1 H2 H2 ANTICIPATOR 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M3686 FALL R RISE L C1 HEAT RELAY 3 EM HT RELAY CONTACT OUTDOOR THERMOSTAT AUTO ON FAN SWITCH X W3 OPTIONAL COMPRESSOR FAILURE DEVICE DEFROST RELAY REVERSING VALVE EM HT RELAY CONTACT HIGH PRESSURE SWITCH HEAT RELAY 1 HEAT RELAY 2 AUTO FALL C0 C1 ANTICIPATOR ...

Page 5: ...rmostat base and note the spring fingers that engage the subbase contacts Make sure the spring fingersarenotbentflat Flatfingerspreventproperelectrical contact with the subbase 5 Set the second stage heat anticipation indicator to match the current rating of the controlled equipment See Heat Anticipator Setting section The first stage heat antici pator and the cooling anticipator are nonadjustable...

Page 6: ... COOLING SET POINT LEVER THERMOMETER WHEN PROVIDED FAN SWITCH SYSTEM SWITCH OPTIONAL LED ENUNCIATION XXX XXXX XXXX XXXX XXX XXXX The T874N has separate heating and cooling set point levers the T874R has one set point lever for heating and cooling Move the heating and cooling set point levers Fig 10 to the desired comfort positions The minimum differen tialbetweenheatingandcoolingsetpointis3 F 2 C ...

Page 7: ...h to AUTO In this position fan operation is controlled by the heating or cooling system control circuit Calibration THERMOSTAT T874Thermostatsareaccuratelycalibratedatthefactory They do not have provision for field calibration THERMOMETER The thermometer in your thermostat has been accurately calibrated at the factory The thermometer should need adjustment only if it has been dropped or shifted du...

Page 8: ...ited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 60 1147 4 S M Rev 5 93 Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 www honeywell com yourhome ...

Reviews: